Monessen Hearth BWB400I, BWBC400I manual Chimney Installation

Page 55

CHIMNEY INSTALLATION

FIGURE 14

"A"

FLUE OUTLET

HEIGHT

2" MIN. WHEN

2" MIN. WHENDIM."A" IS 10' DIM."A" IS 10'

OR LESS

"A"

FLUE OUTLET

HEIGHT

2" MIN. WHEN DIM."A" IS 10'

3" MIN.

NOTE: FLUE OUTLET SHOULD BE TWO FEET ABOVE ALL PORTIONS OF THE BUILDING WITHIN TEN FEET AS SHOWN BY THESE ILLUSTRATIONS. THE CHIMNEY MUST NOT EXTEND MORE THAN 90 INCHES ABOVE THE ROOF WITHOUT ADDITIONAL SUPPORT.

"A"

FLUE OUTLET HEIGHT

 

2" MIN. WHEN

 

DIM."A" IS 10'

3" MIN.

OR LESS

 

 

 

 

 

1.Lay out, cut and frame openings through all ceilings and the roof at the point where the chimney will pass through. Unless the chimney is to be offset, the point where the center line of the chimney will pass through the ceiling and roof can be determined with a plumb line as shown by Figure 15. The fireplace should be located in the planned installation position. After the center line is established and a nail is driven to mark the point, the opening can be cut if you are satisfied with the chimney location relative to ceiling and roof joists and/or any other obstructions. The roof opening center line should be marked by driving a nail through the roof from underneath that will penetrate the roof and can be located from the rooftop. If the chimney is to penetrate a pitched roof, the hole in the roof must be rectangular instead of square and should be sized according to Table1.

2.Install the firestop spacer as required from beneath the ceiling unless the space above is attic space. In an attic, the firestop spacer should be installed at the floor level of the attic. Figure 17. You must have joists or headers on all four sides of the spacer and use a minimum of four 8-penny nails to secure the spacer.

3.To install the “S” series chimney sections, insert the male end of the flue, the smallest diameter pipe, into the flue outlet of the fireplace and press down until the snap locks engage. Continue the process, adding the chimney sections on top of each other until the chimney is at least six inches above the roof opening on all sides. As the chimney sections are installed, check each joint to make sure it is properly locked to the previous section. If additional strength of the outer pipe joints is desired, you may use two or three sheet metal screws placed through the area where the outer pipes overlap one another. To install these screws, drill a 1/8-inch diameter hole through the chimney sections, taking care not to penetrate the inner flue pipe. Warning: Be very careful when drilling the holes into the outer pipe. The drill must not penetrate the inner stainless steel pipe.

NOTE: If you intend to have a total fireplace installation of more that 30 feet you must use chimney support model SCS at or below 30 feet to support the weight of additional chimney pipe.

To install the chimney support, place the crimped end of the flue and outlet air duct portions into the last section of chimney pipe. Push down until the outside or inlet air duct of the chimney support overlaps and snap locks the chimney support into the chimney section.

Nail the support straps tightly to a building frame member or ceiling joist as shown by Figure 16. You must use at least two 8-penny nails per strap.

15

53D9032. Rev 1 03/03

Image 55
Contents Series BWB400-SERIESTable of Contents Important Information Operation Guidelines Clearances Residential InstallationOutside AIR Connector Centerline Fireplace Location Installation Preparation Single Story Installation with Attic Space Floor Protection Fireplace MIN Floor Line with Raised Hearth Fireplace Components See for Illustration of Fireplace Components Described below Fireplace Installation Chimney Installation 17 x Chimney Offset Installation SF30 Firestop Spacer Chimney Offset and CAP InstallationChimney CAP Installation Intermediate Height Sections Inches Chimney Height and Offset ChartsChimney CAP Chase Installation Outside Combustion AIR Precautions and Recommendations Basement Installation Outside Combustion AIR Precautions & RecommendationsGAS Appliance Installation Combustion AIR AssemblyGAS Appliance Installation From Opening Trim InstallationPart a Glass Door Installation and FAN Accessory Fireplace Operation Species Density Heat Value Maintenance and Safety DO’S DONT’S Model Fireplace Parts Diagram and ListBWBC400/BWBC400I Except Blowers Limited WarrantyYour Duties This page intentionally left blank 53D9031. Rev 1 03/03 Appliance Installer BWB500, BWB500I, BWBC500 Congratulations Intended Product Usage Operation Guidelines Residential Installation Framing Corner Installation Side Wall Installation Joist Insulate Same Single Story Installation with Attic Space Brick or Stone Hearth Floor Line with Raised Hearth Fireplace Metal Safety Strip SCS Model Description Fireplace Installation Chimney Installation 17 x Although Both Halves 14-1/2 Chimney CAP Installation Straight RUN Chimney Sections Intermediate Height Inches Chimney CAP Chase Installation Outside Combustion AIR Precautions & Recommendations Outside Combustion AIR Recommendations Model AK4 Combustion AIR Assembly GAS Appliance Installation Applying Decorative Trim to the Fireplace Outline Fireplace Firebrick FAN Assembly Fireplace Operation Species Density Heat Value Maintenance and Safety DO’S DONT’S Model Fireplace Repair Part Diagrams and ListsBWBC500 / BWBC500I FACTORY-BUILT Fireplace and Components Your Duties This page Intentionally Left Blank 53D9032. Rev 1 03/03 53D9032. REV 1 03/03