Heatiator C40 owner manual Installation of Fireplace, Install the Outside Air Kit

Page 39

7 Installation of Fireplace

Caution! Risk of Cuts/Abrasions. Wear protective

1. Cut a 6 in. (152 mm) hole in outside wall to accommodate

air piping. See Figure 7.3 on page 40.

gloves and safety glasses during installation. Sheet metal

2. Use 6 in. (152 mm) metal flex or rigid piping (not

edges are sharp.

A. Install the Outside Air Kit

supplied) to directly connect outside air to fireplace

intake. Insulate the pipe to prevent frost condensation.

This fireplace will operate correctly only if adequate ven-

3. Use the supplied termination cap.

tilation is provided to allow proper draft to the fireplace

4. Seal between the wall and the pipe with silicone to

system. See Section 6.

An outside air kit must be used for combustion to mini-

prevent moisture penetration and air leaks.

5. Seal between the termination cap and the house with

mize the effects of negative pressure within the structure.

We recommend you utilize the shortest duct run to opti-

silicone to prevent air infiltration.

mize the performance of the outside air kit. The outside

NOTE: A control knob allows you control of the outside air

air kit inlet should be positioned in a manner that will not

allow snow, leaves, etc. to block the inlet. In some instal-

inlet. Use of outside air for combustion is required to

lations the air duct may need to be run vertically. In such

conserve heated air within the structure and to provide

an installation, a 3 ft (914 mm) height difference must be

make up air to keep the fireplace venting properly.

maintained from the top of the uppermost chimney sec-

IMPORTANT! Outside air control considerations

tion to the outside combustion air inlet. See Figure 7.2

Turn counter-clockwise to “OPEN” positions

on page 40.

Outside air knob must be in the “OPEN” position to oper-

See Figure 7.1 for proper placement of outside air inlet.

ate fireplace properly.

The outside air kit is installed on the right hand side of the

May be closed when not in use to prevent cold air infiltra-

fireplace. See Figure 7.3 for handle location/operation.

tion

 

Caution! Risk of Fire or Asphyxiation! Do not draw outside combustion air from wall, floor or ceil- ing cavity, or enclosed spaces such as an attic or garage.

Do not place outside air hood close to exhaust vents or chimneys. Fumes or odor could be drawn into the room through the fireplace.

Locate outside air inlet to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause com- bustion air starvation.

NO

Attic space

NO

Outlet placed

higher than 3 ft

below the

termination cap

NO

Garage or

combustible

liquids storage

NO

Outlet blocked by snow, leaves, etc.

Use only duct materials specified by manufacturer

Figure 7.1 Outside Combustion Air Placement

4/12

Heatilator • Constitution EPA Fireplace • 480-1091H

Page 39

Image 39
Contents Hot screen/mesh and glass doors will cause burns C40009 Listing Label Information/LocationTable of Contents Limited Lifetime Warranty Warranty Conditions Listing and Code Approvals Appliance CertificationManufactured Home Approved Combustible Materials BTU & Efficiency Specifications Electrical CodesGlass Specifications Non-Combustible MaterialsOperating InstructionsUser Guide Your FireplaceHot glass will cause burns Baffle and Blanket Placement Firebrick PlacementGeneral Information Seasoning Moisture contentWood Fuel Hardwood vs. SoftwoodOutside Air Seasoned WoodStoring Wood Glass Doors Clear Space Near the FireplaceChimney Fire Fire SafetySymptoms of Over-Firing Over-Firing Your Appliance2nd stage Starting a FireBurning Process Kindling or 1st stageAutomatic Combustion Control ACC Final stageSlide Air Control Slide Left to Stop Opacity Manual Timer OverrideBurn Rates Burning GuidelinesTroubleshooting Understanding Vent ProblemsDraft Problems For start-up? Diagnostic Question Possible Causes of Condition Solutions Diagnostics and Problem SolvingDon’t get enough/any heat. What can I do about it? General Maintenance Creosote Chimney Cleaning Maintenance and Servicing the FireplaceDoor and Door Gasket Care and Cleaning of Plated SurfacesGlass Cleaning Disposal of AshesReplacement Maintenance Glass Replacement Maintenance Task ListFire Brick Configurations Firebrick ReplacementBaffle Removal and Installation Fan ReplacementFan Cord Location Removing the fan Fan Replacement Instructions11 Timer Assembly Timer Assembly ReplacementLinkage Arm Slider Control Rod Timer Removal & ReplacementHeatilator Constitution EPA Fireplace 480-1091H Date of Service Performed By Description of Service Service & Maintenance LogTypical Fireplace System Getting Started Installer GuideDesign and Installation Considerations DraftNegative Pressure Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyTools and Supplies Needed Fireplace System RequirementsInspect Fireplace and Components Selecting Fireplace Locations Framing & ClearancesClearances to Combustible Materials ClearancesMinimum Clearances to Combustibles Within Enclosure Area Frame the FireplaceFan Wiring Diagram Electrical Access and Wiring DiagramInstall the Outside Air Kit Installation of FireplaceMm metal flex Fireplace Or rigid pipe Place Protective Metal Hearth Strips Secure the FireplaceChimney Assembly Chimney Termination Requirements Chimney RequirementsExample Using Offsets/ ReturnsAssemble the Chimney Sections Installing CAK4A and Flex PipeInstalling Flex Pipe Install Ceiling FirestopsSecure the Chimney Install Attic Insulation ShieldCut out Hole in Roof Double-check the Chimney AssemblyComplete Installation Install Flashing13 Multiple Chimney Locations Consult local codes for framing details SL-300 Series Ceiling/Roof ThimbleConstruct the Chase Chase InstallationsInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST375 Square Termination Cap TCT375 Terra Cotta Cap = 1/k x inches of thickness FinishingNon-Combustible Materials Non-Combustible Facing Material StallationHearth Extension Non-Combustible Sealant MaterialCardboard or Metal Template Position the Hearth Extension Raised Hearth Extension FramingFireplace and Hearth Extension are flush on the floor Finishing Material Combustible MaterialNon-Combustible Material Mantel 13 Mantel SpecificationsHeat Zone Kit Optional AccessoriesRun Length Cut Pipe 40 ft 6-12m 4 wall Firescreen Fireplace Dimensions Reference MaterialsConstitution Catalog Description Catalog No Chimney Components15-3/4 DTO134 Service Parts Part number list on followingConstitution Woodburning Fireplace Stocked At Depot#3 Brick Set Stocked at Depot Baffle Protection Channel Door Handle AssemblyThis page intentionally left blank Do not Discard this Manual Contact Information
Related manuals
Manual 71 pages 32.62 Kb

C40 specifications

The Heatiator C40 is an innovative heating solution designed to optimize comfort and energy efficiency in residential and commercial spaces. This advanced heating unit combines modern technology with user-friendly features, making it an excellent choice for anyone looking to improve their heating systems.

One of the standout features of the Heatiator C40 is its powerful heating capacity. With an output of up to 40,000 BTUs, this unit is capable of efficiently warming large areas, ensuring that no space is left cold. The C40 utilizes high-efficiency burners that maximize heat output while minimizing fuel consumption. This not only translates to lower energy bills for the consumer but also contributes to a reduced carbon footprint.

The Heatiator C40 is equipped with advanced smart technology, allowing users to control their heating environment remotely. With the Heatiator mobile app, users can adjust the temperature settings, set schedules, and monitor energy usage from their smartphones. This level of control ensures that comfort is maintained without unnecessary energy waste.

Another notable characteristic of the C40 is its versatile design. The unit can be easily installed in various configurations, including wall-mounted, freestanding, or built-in options, making it suitable for any room layout or decor. Its sleek, compact design also ensures that it blends seamlessly into any environment, providing users with both functionality and aesthetic appeal.

Safety is a priority in the design of the Heatiator C40. The unit is equipped with multiple safety features, including overheat protection, a flame failure device, and an automatic shut-off system. These safety measures provide peace of mind, allowing users to enjoy their heating without worry.

Furthermore, the Heatiator C40 operates quietly, making it an ideal choice for bedrooms and living areas where noise can be a distraction. The noise-reduction technology incorporated into the unit ensures that the heating process is unobtrusive, allowing for a peaceful environment.

In summary, the Heatiator C40 is a cutting-edge heating solution that stands out due to its powerful performance, energy efficiency, and user-friendly technology. With its stylish design, safety features, and advanced controls, the C40 is an excellent investment for anyone looking to enhance their heating system while enjoying the comfort of a warm, inviting space. Whether for homes or businesses, the Heatiator C40 promises reliable performance and satisfaction.