Enviro 828 BV. INS, 828 BV. FS owner manual Venting Freestanding Models

Page 11

constructed out of non-combustible materials.

Make sure that all chimney clean outs are tightly fitting and will not permit air to leak into the chimney.

Remove the vent collar plate from the top of the insert and connect it securely with at least 3 sheet metal screws and a 4" hose clamp. Check for any tears in the liner at this point. (See also Assembly and Installation Instructions section 5 )

IMPORTANT: The screw that holds the vent collar plate in it's approved position must be installed.

The draft hood must be in the same pressure zone as the air inlet.

To inspect draft from the front of the unit, open right side hinged flap. Locate 3/8” tube and check for draft using smoke or magnehelic gauge. A vacuum will indicate proper drafting.

B. VENTING FREESTANDING MODELS

This stove should be vented by certified 4" Type B Gas Vent that may be encased in 6" decorative stovepipe. The flue collar of the appliance will fit inside of standard vent and should be fastened directly to the vent.

The ENVIROGAS incorporates its own internal draft hood, so no additional external draft hood is required

The venting system should be assembled and installed according to the vent manufacturer's instructions and the local, state/provincial or national codes.

Figure 12

Figure 13

Two basic venting configurations are shown in fig. 12 & 13.

See vent manufacturer's instructions for vent system clearances to combustibles and vent terminal clearance from roof.

This information is compiled by the manufacturer as a very general rule for single appliance venting of the 828 gas stove with 4" Type B gas vent.

Venting code and regulations may vary from area to area, please check with the local, state/provincial codes regarding the suitability of your application.

11

Image 11
Contents What to do if YOU Smell GAS For Your SafetyGeneral Safety PrecautionsCode Approvals Table of ContentsSpecifications Freestanding Clearances to Combustibles For Installations Above 2000 FeetDimensions and Clearances to Combustibles Fireplace Insert Clearances to CombustiblesPrimary Installation Deciding Where to Locate Your Freestanding StovePreparation for Installation Assembly and Installation InstructionsAssembling Your Envirogas 828 Freestanding Appliance Optional FAN Electrical RequirementsOrifice SIZES, Pressures and Btus GAS Line Connection and TestingNever USE Open Flame for Leak Testing Venting Automatic Flue GAS Spill SwitchVenting Freestanding Models AIR Shutter Adjustment Installing the LOG Installing the Glowing EmbersOperating Instructions For Your Safety Read Before OperatingRoutine Maintenance Problem Possible Cause Solution Trouble ShootingService Parts available from your local Envirogas Dealer Parts and AccessoriesTo the Dealer WarrantyEG-828 Insert BV. FPI Installation Data Sheet