Vermont Casting 36CDVTRN, 36CDVRRN Rear Wall Vent Installations Flex Vent Pipe

Page 14

CDV Series Direct Vent Gas Fireplace

Rear Wall Vent Installations -

45° Flex Vent Pipe

NOTE: Under no circumstances can ridged pipe or a rigid 45° elbow be used. The 7TCDV45KT must be used in a corner installation. The corner placement dimensions on Page 4 of the manual must be ad- hered to! Figures 16 & 18 show general installations. Refer to instructions below for a detailed description of installation.

1.Determine where the termination is to be in- stalled. Locate the center of the hole 29¹⁄₂” (749 mm) off the floor. (Fig. 16)

NOTE: The location of the termination hole must be adhered to!

2.Install the firestop as shown on Page 12.

3.Remove the flex vent and extend the flex vent out to its longest length.

4.Bend the tab on the back of the fireplace up. (Fig. 14)

5.Insert the collar on the flex vent that has the twist lock embosses on it onto the collar of the fire- place. Twist the collar to “lock it” onto the fire- place. Run a screw through the tab and into the collar to secure the collar onto the fireplace.

6.Bend the flex pipe up 90° as close to the fireplace as possible. (Fig. 17)

7.Slide the fireplace partially into the corner and, while holding the vertical portion of the flex vent pipe, grab the exposed end collar and bend it down to the height of the opening in the wall.

8.While pushing the unit in place, slide the collar through the firestop. NOTE: It may be necessary to trim some material off of the collar. The col- lar is made long to accommodate brick finished houses. (Fig. 19)

9.Secure the collar in place by running a screw through the tab in the firestop and through the collar.

10.Slide the termination into the collar and secure with the 4 screws provided. (Fig. 19)

 

Termination

C

 

L

 

to Floor

Flex Section

29 ” Appliance

��� Collars (749 mm)

FP1473

Fig. 16 Grasp the vent pipe close to the collar and bend to 45° angle. Do not exceed 45°.

FP1604

Fig. 17 Bend flex pipe up 90° as close to fireplace as pos- sible.

Corner

FramingDo Not Exceed

45° Bend

Termination

FP1606

Fig. 18 Rear view of corner installation.

14

20010175

Image 14
Contents Builder Direct Vent Models Table of Contents Please Review the Following Carefully Installation & Operating InstructionsLocating Your Fireplace 36CDVR Fireplace Dimensions Rear VentFraming Dimensions Must be adhered toFireplace Dimensions Top Vent 36CDVTHearth Clearance to CombustiblesMantels Final Finishing Hood InstallationFraming and Finishing Gas SpecificationsGas Inlet and Manifold Pressures Gas Line InstallationRemote ON/OFF Switch High ElevationsGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationGeneral Information Assembling Vent Pipes Canadian InstallationsUSA Installations Flex Vent PipesRear Wall Venting Applications How to Use the Vent Graph36CDVR Venting From Rear of UnitRear Wall Installation Twist Lock Pipe StepRear Wall Vent Installations Flex Vent Pipe Bend flex pipe up 90 as close to fireplace as pos- sibleVertical Sidewall Applications Secure collar in place, slide termination into collarVertical Sidewall Installation Maximum horizontal vent runAlways install hori- zontal venting on a level plane Below Grade Installations Vertical Through-the-Roof ApplicationsVertical Through-the-Roof Installation Enlarged ends of the vent section always face downward. FigTypical straight-up installation 36CDVT Vertical Venting+ B = 17 5.2m Max Vertical Sidewall Installations Always install horizontal venting on a level planeThrough the wall Example Maximum horizontal length Roof and ceiling supports Min 610 mm Venting Components Operating Instructions Glass CleaningWindow Frame Assembly Removal Glass InformationLogs Flame CharacteristicsFlame & Temperature Adjustment RN/RP & EN/EP ModelsWhat to do if YOU Smell GAS Lighting and Operating InstructionsTo Turn Off Gas to Fireplace Valve in the on position Lighting InstructionsTurning Off the Gas to the Appliance Troubleshooting the Gas Control System SIT 820 Nova Gas Control Valve Fig Fuel Conversion InstructionsSIT top Convertible Pilot Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Description 36CDVCDV Fuel Conversion KitsRemote Controls Optional Accessories AvailableWiring Instructions Fan KitsCDV Series Direct Vent Gas Fireplace Limited Lifetime Warranty Product Covered by this WarrantyCFM Corporation