Vermont Casting 36CDVTRN Gas Inlet and Manifold Pressures, High Elevations, Gas Line Installation

Page 8

CDV Series Direct Vent Gas Fireplace

Gas Inlet and Manifold Pressures

 

 

Natural

LP (Propane)

Inlet Minimum

5.5” w.c.

11.0” w.c.

Inlet Maximum

14.0” w.c.

14.0” w.c.

Manifold Pressure

3.5” w.c.

10.0” w.c.

 

 

 

 

High Elevations

Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370 m) above sea level.

For elevations above 4,500 feet (1,370 m) in USA, installations must be in accordance with the cur- rent ANSI Z223.1/NFPA 54 and/or local codes hav- ing jurisdiction.

In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370 m).

Gas Line Installation

When purging the gas lines, the front win- dow frame assembly must be removed.

The gas pipeline can be brought in through the rear of the appliance as well as the bottom. Knockouts are provided on the bottom behind the valve to allow for the gas pipe installation and testing of any gas connection. It is most convenient to bring the gas line in from the rear right side of the valve as this allows fan installation or removal without disconnecting the gas line.

The gas line connection can be made with properly

The gas control is equipped with a captured screw type pressure test point, therefore it is not necessary to pro- vide a 1/8” test point up stream of the control.

When using copper or flex connector use only approved fittings. Always provide a union when using black iron pipe so the gas line can be easily disconnected for burner or fan servicing. See gas specification for pres- sure details and ratings.

The fireplace valve must not be subjected to any test pressures exceeding 1/2 psi. Isolate or disconnect this and any other gas appliance control from the gas line when pressure testing.

Remote ON/OFF Switch

Installation

1.Carefully unwrap the remote wire that is attached to the valve. There are two 1/2” (13 mm) knockouts, one on each side of the outer casing.

2.Remove the knockout desired and insert the plastic snap bushing on the remote wire in the 1/2” hole. Feed the remote wire through the outer casing.

3.Attach the wire to an ON/OFF switch and install the switch into the receptacle box. (Fig. 6)

Remote ON/OFF Switch or Thermostat

or Remote Control

TP

TH

Gas

TP Control

Valve

tinned 3/8” copper tubing, 3/8” rigid pipe or an ap- proved flex connector. Since some municipalities have additional local codes, it is always best to consult your local authority and the National Fuel Gas Code, ANSI

TH

Fig. 6 Remote switch wiring diagram.

FP1224

Z223.1/NFPA 54 in the USA or the CSA-B149.1 installa- tion code.

1/2” Gas Supply

1/2” NPT x 1/2” Flare Shut- off Valve

3/8” Flex Line

(From Valve)

FP297A

Fig. 5 Typical gas supply installation.

Always check for gas leaks with a mild soap and water solution. Do not use an open flame for leak testing.

Do not wire the remote ON/OFF wall switch for the gas fireplace to the 120 volt power supply.

120V Electrical Hook Up

The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or, in the ab- sence of local codes, with the current CSA C22.1 Canadian Electrical Code.

For USA installations follow local codes and the national electrical code ANSI/ NFPA No. 70.

It is strongly suggested that wiring of the Electrical Junction Box be carried out by a licensed electrician.

8

20010175

Image 8
Contents Builder Direct Vent Models Table of Contents Please Review the Following Carefully Installation & Operating InstructionsLocating Your Fireplace Fireplace Dimensions Rear Vent Framing Dimensions36CDVR Must be adhered toFireplace Dimensions Top Vent 36CDVTHearth Clearance to CombustiblesMantels Hood Installation Framing and FinishingFinal Finishing Gas SpecificationsGas Line Installation Remote ON/OFF SwitchGas Inlet and Manifold Pressures High ElevationsGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationCanadian Installations USA InstallationsGeneral Information Assembling Vent Pipes Flex Vent PipesHow to Use the Vent Graph 36CDVR VentingRear Wall Venting Applications From Rear of UnitRear Wall Installation Twist Lock Pipe StepRear Wall Vent Installations Flex Vent Pipe Bend flex pipe up 90 as close to fireplace as pos- sibleVertical Sidewall Applications Secure collar in place, slide termination into collarVertical Sidewall Installation Maximum horizontal vent runAlways install hori- zontal venting on a level plane Below Grade Installations Vertical Through-the-Roof ApplicationsVertical Through-the-Roof Installation Enlarged ends of the vent section always face downward. FigTypical straight-up installation 36CDVT Vertical Venting+ B = 17 5.2m Max Vertical Sidewall Installations Always install horizontal venting on a level planeThrough the wall Example Maximum horizontal length Roof and ceiling supports Min 610 mm Venting Components Glass Cleaning Window Frame Assembly RemovalOperating Instructions Glass InformationFlame Characteristics Flame & Temperature AdjustmentLogs RN/RP & EN/EP ModelsWhat to do if YOU Smell GAS Lighting and Operating InstructionsTo Turn Off Gas to Fireplace Valve in the on position Lighting InstructionsTurning Off the Gas to the Appliance Troubleshooting the Gas Control System SIT 820 Nova Gas Control Valve Fig Fuel Conversion InstructionsSIT top Convertible Pilot Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Description 36CDVCDV Fuel Conversion KitsOptional Accessories Available Wiring InstructionsRemote Controls Fan KitsCDV Series Direct Vent Gas Fireplace Limited Lifetime Warranty Product Covered by this WarrantyCFM Corporation