Vermont Casting 36CDVTRN, 36CDVRRN Vertical Sidewall Installation, Maximum horizontal vent run

Page 16

CDV Series Direct Vent Gas Fireplace

the horizontal vent it must be reduced to 17’ (5.2 m). In Figure 23 Dimension A plus B must not be greater than 17’ (5.2 m).

Maximum

3' (914mm)

7TCDV90

CFM142

Fig. 22 Maximum horizontal vent run.

7 ft.

(2134 mm)

10 ft.

(3048 mm)

90° Elbow = 3 ft.

A + B = 17 ft. (Max.)

7 ft. 6 in.

(2286 mm)

CFM147

Fig. 23 Maximum vent run with elbows.

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (45 cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system is 270°. (Fig. 24)

•IMPORTANT• Minimum clearance between vent pipes and combustible materials is one (1”) inch (25 mm) on bottom, sides and top.

Twist Lock Vent Starter Kit 7TCRVT, plus Elbow 7TCDV90 must be used in Vertical Sidewall installations.

Canadian & USA Installations:

The venting system must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition, or CSA B149.1 Installation Code.

Example:

 

 

 

Elbow 1

=

90˚

4

Elbow 2

=

45˚

Elbow 3

=

45˚

 

Elbow 4

=

90˚

 

Total angular variation = 270˚

1 + 2 + 3 + 4 = 270o

3

2

1

CFM132

Fig. 24 Maximum number of elbows.

Only CFM Corporation venting components specifically approved and labelled for this fireplace may be used.

Vertical Sidewall Installation

STEP 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 25)

For combustible walls first frame in opening.

Combustible Walls (Fig. 25): Cut a 9³⁄”H x 9³⁄” W (240 x 240 mm) hole through the exterior wall and frame.

Noncombustible Walls (Fig. 25): Hole opening must be 7.5” (190 mm) in diameter.

Vent Opening for Combustible Wall

9³⁄

(240mm)

9³⁄

(240mm)

Framing Detail

Fireplace Hearth

Opening for Noncombustible Wall

7¹⁄

(190mm)

VO584-100

Fig. 25 Locate vent opening on wall.

16

20010175

Image 16
Contents Builder Direct Vent Models Table of Contents Locating Your Fireplace Installation & Operating InstructionsPlease Review the Following Carefully Fireplace Dimensions Rear Vent Framing Dimensions36CDVR Must be adhered toFireplace Dimensions Top Vent 36CDVTMantels Clearance to CombustiblesHearth Hood Installation Framing and FinishingFinal Finishing Gas SpecificationsGas Line Installation Remote ON/OFF SwitchGas Inlet and Manifold Pressures High ElevationsGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationCanadian Installations USA InstallationsGeneral Information Assembling Vent Pipes Flex Vent PipesHow to Use the Vent Graph 36CDVR VentingRear Wall Venting Applications From Rear of UnitRear Wall Installation Twist Lock Pipe StepRear Wall Vent Installations Flex Vent Pipe Bend flex pipe up 90 as close to fireplace as pos- sibleVertical Sidewall Applications Secure collar in place, slide termination into collarVertical Sidewall Installation Maximum horizontal vent runAlways install hori- zontal venting on a level plane Below Grade Installations Vertical Through-the-Roof ApplicationsVertical Through-the-Roof Installation Enlarged ends of the vent section always face downward. FigTypical straight-up installation 36CDVT Vertical Venting+ B = 17 5.2m Max Vertical Sidewall Installations Always install horizontal venting on a level planeThrough the wall Example Maximum horizontal length Roof and ceiling supports Min 610 mm Venting Components Glass Cleaning Window Frame Assembly RemovalOperating Instructions Glass InformationFlame Characteristics Flame & Temperature AdjustmentLogs RN/RP & EN/EP ModelsTo Turn Off Gas to Fireplace Lighting and Operating InstructionsWhat to do if YOU Smell GAS Turning Off the Gas to the Appliance Lighting InstructionsValve in the on position Troubleshooting the Gas Control System SIT top Convertible Pilot Fuel Conversion InstructionsSIT 820 Nova Gas Control Valve Fig Cleaning the Standing Pilot Control System MaintenanceBurner and Burner Compartment Description 36CDVCDV Fuel Conversion KitsOptional Accessories Available Wiring InstructionsRemote Controls Fan KitsCDV Series Direct Vent Gas Fireplace Limited Lifetime Warranty Product Covered by this WarrantyCFM Corporation