Quick Installation Guide
Rosemount 8712 / 8700 Series
Flange Bolts
Wafer sensors require threaded studs. See Figure 7 for torque sequence. Always check for leaks at the flanges after tightening the flange bolts. All sensors require a second torquing 24 hours after initial flange bolt tightening.
Table 5. Rosemount 8711 Torque Specifications |
|
| |
|
|
|
|
Size Code | Line Size |
|
|
15F | 0.15 inch (4 mm) | 5 | 7 |
30F | 0.30 inch (8 mm) | 5 | 7 |
005 | 0.5 inch (15 mm) | 5 | 7 |
010 | 1 inch (25 mm) | 10 | 14 |
015 | 1.5 inch (40 mm) | 15 | 20 |
020 | 2 inch (50 mm) | 25 | 34 |
030 | 3 inch (80 mm) | 40 | 54 |
040 | 4 inch (100 mm) | 30 | 41 |
060 | 6 inch (150 mm) | 50 | 68 |
080 | 8 inch (200 mm) | 70 | 95 |
Sanitary Sensors
Gaskets
The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. Gaskets are supplied between the IDF fitting and the process connection fitting, such as a
Alignment and Bolting
Standard plant practices should be followed when installing a magmeter with sanitary fittings. Unique torque values and bolting techniques are not required.
Figure 9. Rosemount 8721 Sanitary Installation
User supplied clamp
User supplied gasket
15