Emerson 8712E manual Wiring the Transmitter to the Sensor, Description, Part Number

Page 20

Quick Installation Guide

Rosemount 8712 / 8700 Series

00825-0100-4664, Rev BB January 2013

STEP 6 CONTINUED...

To order cable specify length as quantity desired. 25 feet = Qty (25) 08732-0753-1003

Table 7. Cable Requirements

 

 

Description

Length

Part Number

Coil Drive Cable (14 AWG)

ft

08712-0060-0001

Belden 8720, Alpha 2442

m

08712-0060-2013

or equivalent

 

 

Signal Cable (20 AWG)

ft

08712-0061-0001

Belden 8762, Alpha 2411

m

08712-0061-2003

or equivalent

 

 

Combination Cable

ft

08732-0753-1003

Coil Drive Cable (18 AWG) and

m

08732-0753-2004

Signal Cable (20 AWG)

 

 

WARNING

Potential Shock Hazard Across Terminals 1 & 2 (40 Vac).

Wiring the Transmitter to the Sensor

When using individual cables for coil drive and signal refer to Table 8. If using the combination coil drive and signal cable, refer to Table 9. See Figure 16 for transmitter specific wiring diagram.

1.Connect the coil drive cable using terminals 1, 2, and 3 (ground).

2.Connect the signal cable using terminals 17, 18, and 19.

Table 8. Individual Coil and Signal Cables

 

 

Transmitter Terminal

Sensor Terminal

Wire Gauge

Wire Color

1

1

14

Clear

2

2

14

Black

3 or Ground

3 or Ground

14

Shield

17

17

20

Shield

18

18

20

Black

19

19

20

Clear

Table 9. Combination Coil and Signal Cable

 

 

Transmitter Terminal

Sensor Terminal

Wire Gauge

Wire Color

1

1

18

Red

2

2

18

Green

3 or Ground

3 or Ground

18

Shield

17

17

20

Shield

18

18

20

Black

19

19

20

White

20

Image 20
Contents Quick Installation Guide Management Asia Pacific Private LimitedPRE-INSTALLATION Mechanical ConsiderationsDimensions are in inches millimeters 10912.02 305Installation Procedures Identify Options and ConfigurationsHardware Jumpers/Switches Environmental ConsiderationsHandling Electrical ConsiderationsMounting Upstream/Downstream PipingFlow Direction Sensor OrientationFlow Installation Flanged SensorsGaskets Flange BoltsPound-feet Size ClassCode Newton Code Meter PTFE/ETFE liner PN10 SizeNewton Polyurethane, Linatex, Adiprene and Neoprene Liners Size Nominal Sensor Size Wafer SensorsAlignment Rosemount Alignment Spacer Table Line Size Dash No Pound-feet Newton-meter Sanitary SensorsAlignment and Bolting Grounding Process Grounding Options Type of PipeLining StrapsGrounding with Grounding Electrode Wiring Power OutputsCoil Drive and Electrode Cables Power Outputs Conduit Ports and ConnectionsTransmitter to Sensor Wiring Remote Mount Cable Requirements and PreparationWiring the Transmitter to the Sensor Transmitter Terminal Sensor Terminal Wire Gauge Wire ColorDescription Part NumberRemote Mount Wiring Diagrams Connect the 4-20 mA Analog Signal Internal Power SourceExternal Power Source Cabling considerationsPowering the Transmitter Supply Wire RequirementsInstallation Category DisconnectsFuse 8712E Power SupplyAC Ground or DC Ground Transmitter Power Cable Basic Setup Basic Setup Local Operator InterfaceFunction Fast Keys Process Variables PV ReviewProduct Certifications Approved Manufacturing LocationsEuropean Directive Information International CertificatesEuropean Certifications N1 Atex Type n Special Conditions for Safe UseInternational Certifications N7 IECEx Type nSensor Approval Information Maximum Process Meter Size Inches Maximum Ambient TemperatureRosemount 8705 and 8711 Sensors EC Declaration of Conformity Schedule