Desa (V)T32EN-A Series, (V)T32EP-A Series Troubleshooting, Observed Problem Possible Cause Remedy

Page 27

TROUBLESHOOTING

27

TROUBLESHOOTING

Note: Before troubleshooting the system, make sure the gas shutoff valve is ON.

The two most common causes of a malfunctioning gas appliance are:

1.Loose wiring connections

2.Construction debris clogging the pilot and/or gas control valve filter

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle or similar object to clean pilot. This can damage pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

 

Ignitor will not spark or pilot will not light

1.

No gas supply or shutoff valve is OFF

1.

Check to see if you have gas supply and

 

 

 

 

that equipment shutoff valve is opened

 

2.

Air in gas line

2.

Repeat lighting procedure several times

 

 

 

 

to purge all air out of lines. If after re-

 

 

 

 

peated attempts appliance does not light,

 

 

 

 

call for qualified service and repair.

 

3.

Construction debris clogging pilot orifice

3.

Remove debris and dirt, inspect and

 

 

 

 

clean any other possible obstructions

 

4.

Low gas pressure

4.

Contact your gas supplier to check

 

 

 

 

pressure

 

5.

Kinked pilot line

5.

Have a qualified technician replace pilot

 

 

 

 

line

 

6.

Control valve is not opening

6.

Replace control valve (refer to Replace-

 

 

 

 

ment Parts, page 29)

 

7.

No power to unit or the ignition module

7.

Check that main power is on and that all

 

 

or power transformer is bad

 

wire connections are made correctly to

 

 

 

 

the ignition model (see Wiring Diagram,

 

 

 

 

page 23). Check for 24 VAC at the

 

 

 

 

secondary side of the transformer. If 24

 

 

 

 

VAC is present and the module does not

 

 

 

 

operate, have the module replaced oth-

 

 

 

 

erwise have the transformer replaced

 

8.

Vent damper not fully open

8.

Open vent damper until fully locked in

 

 

 

 

OPEN position

 

 

 

 

 

Pilot will not stay lit

1.

Loose wiring on ignitor wire to ignition

1.

Check wiring connection. Refer to wir-

 

 

module and/or poor ground to ignition

 

ing diagram (see Wiring Diagram, page

 

 

module

 

23) and/or check ground wire to ignition

 

 

 

 

module

 

2.

Pilot flame too low to sense

2.

Clean and adjust pilot burner and check

 

 

 

 

gas supply and inlet pressure to unit

 

 

 

Note: Have a qualified technician replace

 

 

 

pilot assembly if broken or corroded

 

 

 

 

 

No gas to burner, although wall switch is

1.

Wall switch wires defective or too

1.

Check electrical connections

set to the ON position

 

long

 

 

 

 

 

 

 

Frequent pilot outage

1.

Pilot flame may be too low, causing

1.

Clean and adjust pilot flame for maximum

 

 

safety pilot to “drop out”

 

flame impingement on thermopile

 

2.

Improper venting or excessive blockage

2.

Have the vent system inspected, includ-

 

 

 

 

ing the termination cap. Remove any

 

 

 

 

restriction or obstruction

116647-01A

www.desatech.com

Image 27
Contents For Your Safety For Your Safety What to do if YOU Smell GASSave this manual for future reference Safety Information Table of ContentsLocal Codes Safety Information Product IdentificationProduct Features PRE-INSTALLATION PreparationLocation and Space Requirements Framing and Finishing ClearancesTermination CAP AIR Supply Inlet GAS Meter Location of Termination CAPHorizontal Termination Installation Venting Installation InstructionsInstallation Precautions Installation PlanningVent Pipe Connections Any wall. This will cause a fire hazardConnecting Vent Cap with Horizontal Vent Pipe Vertical Horizontal H Venting InstallationInstructions Horizontal Termination ConfigurationsVenting with Two 90 Elbows Horizontal H Vertical Min Max 12 max 18 max 20 max20 max Max Installation for Vertical Termination Horizontal H 1 +Vertical Horizontal H Min Max 12 max 18 max 20 max Flat Ceiling Installation Vertical Termination ConfigurationsVertical V Horizontal H1 + Horizontal H2 Min Max 20 max Vertical Venting Venting with One 90 ElbowVertical Horizontal H Min Max 20 max Vertical V Horizontal H Min Max 12 max 18 max 20 maxHigh Altitude Installation Desa 5/8 Pipe & Vent KitsNumber Description Installing Optional Blower Accessory Fireplace Installation Check GAS TypeFireplace Installation Model BKT InstallationBlower Wiring Diagram Installation Items Needed Installing GAS Piping to Fireplace LocationConnecting Fireplace to GAS Supply Pressure Testing Gas Supply Piping SystemChecking GAS Connections Removing Glass Door Pressure Testing Fireplace Gas ConnectionsCleaning Glass Door REMOVING/REPLACING Glass DoorInstalling LOGS, Lava Rock and Glowing Embers Installing Optional Brick Liner Model BL32DInstalling Logs No and No For Your Safety Read Before Lighting Wiring DiagramWall Switch Installation Optional Remote ControlOptional Remote Operating Optional Blower AccessoryLighting To Turn OFF GAS To ApplianceGlass Door Cleaning MaintenancePilot Assembly Inspecting BurnersPilot and Burners LogsVenting System Observed Problem Possible Cause Remedy TroubleshootingTop Gas leak. See Warning statement atParts Under Warranty Replacement PartsSpecifications Service Hints Technical ServiceIllustrated Parts Breakdown Illustrated Parts BreakdownParts List Parts List109 Burner Assembly ModelsKEY Part Number Description QTY Accessories Owners Registration Form Postage Required 116647-01A Keep this Warranty Warranty Information