Desa LMFP33PR(A) installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free fireplace

+

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________Btu/Hr (maximum the space can support)

_________Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide ad- ditional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

 

 

3

 

12"

Figure 3 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 4 - Ventilation Air from Outdoors

111604-01L

www.desatech.com

7

Image 7
Contents What to do if YOU Smell GAS Table of Contents Safety Information Product Identification Log Base AssemblyAIR for Combustion Ventilation Product FeaturesLocal Codes UnpackingConfined and Unconfined Space Providing Adequate VentilationDetermining FRESH-AIR Flow for Fireplace Location Unusually Tight ConstructionVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallationElectrical Hookup Example Installing HoodInstalling Cabinet Mantel Conventional Fireplace InstallationInserting Fireplace Into Cabinet Mantel BUILT-IN Fireplace InstallationInstalling Shield to Support Mantel Clearances for Built-In InstallationInstallation Items Needed Installing GAS Piping to Fireplace LocationPropane/LP Natural GasRemoving Log Base Assembly From Fireplace Connecting Fireplace to GAS SupplyTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures In Excess Of 1/2 Psig 3.5 kPa Pressure Testing Fireplace Gas Connections Installing LogsModels LMFP33PR and LMFP33NR Middle Models LMFP33PRA and LMFP33NRAInstalling Battery into Remote Installing Batteries in ReceiverOperating Heater For Your Safety Read Before LightingLighting Instructions Manual Lighting ProcedureTo Turn OFF GAS To ApplianceHAND-HELD Remote Operation Main Burner Inspecting BurnersPilot Flame Pattern Burner Primary AIR HolesPilot AIR Inlet Hole Burner Injector HolderLogs Observed Problem Possible Cause Remedy TroubleshootingDiagram, See Cleaning and Mainte Statement above Gas leak. See WarningReplacement Parts SpecificationsWiring Diagram Service Hints Technical ServiceModels LMFP33PR, LMFP33PRA, LMFP33NR and LMFP33NRA Shown Illustrated Parts BreakdownParts List Firebox LMFP33PR, LMFP33PRA, LMFP33NR and LMFP33NRA KEY Part Number Description QTY Information Video AccessoriesBlower Accessory GA3750A and GA3650TB Series Equipment Shutoff Valve GA5010111604-01L Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace