AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow For Heater Location Ventilation Air

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

The space in the example in column 1 is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

 

40,000

 

_____________ Btu/Hr

Vent-free heater

+

33,000

_____________ Btu/Hr

Total

=

73,000

_____________ Btu/Hr

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills Into Adjoining Room,

Room,

Or

Option 2

4. Compare the maximum Btu/Hr the space can support with the actual

Option 1

Remove

amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,360 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

Door into Adjoining Room, Option 3

12"

Figure 3 - Ventilation Air from Inside Building

For..com

111285-01B

Image 6
Contents OWNER’S Operation Installation Manual Unvented VENT-FREE GAS Fireplace InsertWhat to do if YOU Smell GAS Table of Contents Safety InformationLocal Codes Product Identification Remote Control AccessoriesProduct Features UnpackingUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationVentilation AIR Ventilation Air From Inside BuildingInstallation Check GAS TypeVentilation Air From Outdoors Installing Surround KIT GS38 or GS43 Blower AccessoryElectrical Hookup Installing Hood Installation ClearancesInstalling GAS Piping to Fireplace Location Mantel Clearances for Insert InstallationInstallation Items Needed Connecting Fireplace Insert to GAS Supply Vent Pointing DownPressure Testing Gas Supply Piping System Checking GAS ConnectionsFireplace Insert Installation Into Masonry Fireplace Pressure Testing Fireplace Insert Gas ConnectionsAssembling and Attaching Trim Installing Logs Attaching Trim to Fireplace SurroundInstalling 9-VOLT Batteries Installing 9-Volt Battery Not Included in ReceiverFor Your Safety Read Before Lighting Operating Fireplace InsertLighting Instructions Optional HAND-HELD Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance ON/OFF Series Model GhrcbSafety Features Manual ModeAuto Thermostatic Mode Thermostat Series Model GhrctbBurner Flame Pattern Inspecting BurnersPilot Flame Pattern Burner Primary AIR HolesCleaning Maintenance Cleaning Burner Injector Holder and Pilot AIR Inlet HoleLogs Wiring Diagrams SpecificationsTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement Service Hints Replacement PartsTechnical Service Parts Under WarrantyIllustrated Parts Breakdown Models VI33NR and VI33PRParts List KEY Part Number VI33NR VI33PR Description QTYFireplace Insert VI33NR and VI33PR KEY Part Number Description QTY WALL-MOUNT ON/OFF Switch GWMS2 Receiver and HAND-HELD Remote Control KIT Ghrcb SeriesWALL-MOUNT Thermostat Switch GWMT1 Cleaning KIT GCKOwners Registration Form Tape 111285-01B Warranty Information