Flaring Work and Connection of Piping

4.Indoor unit installation

Hook the indoor unit onto the upper portion of the installa- tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa- tion plate by moving it left and right.

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Connecting the piping to the indoor unit and drain hose to drain pipe.

1.Align the center of the pipes and sufficiently tighten the flare nut by hand.

2.Tighten the flare nut with a wrench.

Outside diameter

 

Torque

 

 

 

 

 

mm

inch

kg.m

 

lbf.in

Ø6.35

1/4

1.8

 

156.2

Ø9.52

3/8

4.2

 

364.5

3.When extending the drain hose at the indoor unit, install the drain pipe.

Wrap the insulation material around the connecting por- tion.

1.Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.

2.Wrap the area which accommodates the rear piping hous- ing section with vinyl tape.

3.Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.

Connecting cable

Drain hose

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit tubing

Flare nut Pipes

 

 

 

 

 

 

 

 

 

 

Open-end wrench (fixed)

Flare nut

Wrench

Connection pipe

Indoor unit tubing

Drain pipe

Indoor unit drain hose

Adhesive Vinyl tape(narrow)

Plastic bands Insulation material

Connection pipe

Indoor unit pipe

Vinyl tape (wide)

Wrap with vinyl tape

Connecting cable

Pipe

Vinyl tape(narrow)

Wrap with vinyl tape

Pipe

Vinyl tape(wide)

Drain hose

20Multi type Air Conditioner

Image 20
Contents Heat CONTROLLER, INC Table of Contents Symbols Used in this Manual Combination tableSafety Precautions InstallationBe sure not to do Be sure to follow the instruction Control box securely Cuit and breakerDo not install, remove, or re Do not install the product on aDefective installation stand Do not allow water to run into electric partsFlooded or submerged, contact When the product is soakedNot enter the product Use two or more people to lift and transport the product Install the drain hose to ensure that Keep level even whenInstalling the product Operational Be careful and avoid personal injury Split Type Indoor DimensionsIndoor Unit Outdoor Unit 24kBtu/hProduct Specifications DMC24DB-1Operation UnitDMH24DB-1 Installation Tools InstallationInstallation Parts Rooftop Installations Select the best locationIndoor unit Outdoor unit24k Piping length and elevationMulti Piping Type Fixing Installation PlateStandard Type Flaring Work and Connection of Piping Flaring workIndoor Connecting the PipingCheck Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Remote Control Preparationoptional Outdoor Outdoor unitConnecting the Cable between Indoor Unit and Outdoor Unit Connect the cable to the Indoor unitConnect the cable to the Outdoor unit Outdoor unitConnection method of the connecting cableExample How to connect wiring to the terminalsConnect the cable to the indoor unit Drain piping Checking the drainageTo check the drainage Forming the piping Down to upAir Purging and Evacuation Checking methodFinishing the job Repeat evacuation procedure for each indoor unitEvacuation Charging AdditionalTest Running Split TypeCooling Mode Operation Soft Dry Operation ModeHeating Mode Operation OperationFuzzy Operation for Cooling Defrost ControlHeatingFuzzy Operation On-Timer Operation Off-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationOff-Timer = On-Timer Operation Sleep Timer OperationChaos Swing Mode Chaos Natural Wind ModeForced Operation Buzzer Sounding OperationFunction of Indoor Unit Split Type Indoor UnitFunction of Outdoor Unit 15 2nd F Button Remote Control OperationCooling Model , Heat Pump Model Disassembly To remove the Grille from the ChassisTo remove the Control Box To remove the Motor Cover Indoor Unit Schematic DiagramElectronic Control Device Outdoor Unit TMP87CM41FRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Wiring Diagram Room Type Indoor UnitComponents Locations Bottom ViewDisplay Assembly Split Type 6871A20680 Component side Solder side Troubleshooting Guide Refrigeration Cycle DiagramDMH24DB-1 DMC24DB-1Indoor Error Outdoor ErrorError Indicator Self-diagnosis FunctionCycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Procedure Specification RemedyProduct doesnt operate with the remote controller Compressor/Outdoor Fan are dont operate Check Point Comp. on Comp. OFFTrouble 4 When indoor Fan does not operate NectorTroubleshooting Guide Error Code Check PointIndoor air sensor Indoor inlet pipe sensorPower input AC 230V.Outdoor, Indoor Communication line is shorted at GNDError Title Cause of error Check point & Normal condition Title Cause of error Check point & Normal condition Outdoor air sensorCondensor pipe sensor Pipe sensorWay, 3-way Valve Way Valve Liguid SideProcedure Pumping downAir purging of the charge hose Set the liquid side valve to the closed positionAll amount of refrigerant leaked Mount the valve caps and the service port capsEvacuation Mount the valve stem nuts and the service port nut Gas ChargingAfter Evacuation Connect the gauge to the charging cylinderHeat CONTROLLER, INC