Troubleshooting Guide

 

 

 

 

 

Error

Title

Cause of error

Check point & Normal condition

 

code

 

 

 

 

 

 

 

 

 

 

 

 

 

• Power input AC 230V.(Outdoor, Indoor)

 

 

 

 

• The connector for transmission is disconnected.

 

05 / 53

Communication

 

• The connecting wires are misconnected.

 

(Indoor Outdoor)

• Communication poorly

• The GND 1,2 is not connected at main GND.

 

 

 

 

 

 

• The communication line is shorted at GND.

 

 

 

 

• Transmission circuit of outdoor PCB is abnormal.

 

 

 

 

• Transmission circuit of indoor PCB is abnormal.

 

 

 

 

 

 

Check Point

1.Check the input power AC 230V.(Outdoor, Indoor)

2.Check the communication wires are correctly connected.

Adjust the connection of wire

Confirm the wire of "Live", "Neutral".

3.Check the resistance between communication line and GND.(Normal : Over 2M)

4.Check the connector for communication is correctly connected.

5.Check the connection of GND1, GND2, and main GND.

6.If one indoor unit is operated normally, outdoor PCB is no problem.

Check the another indoor unit.

* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.

Service Manual 63

Image 63
Contents Heat CONTROLLER, INC Table of Contents Combination table Symbols Used in this ManualControl box securely Cuit and breaker Safety PrecautionsInstallation Be sure not to do Be sure to follow the instructionDo not allow water to run into electric parts Do not install, remove, or reDo not install the product on a Defective installation standWhen the product is soaked Not enter the productFlooded or submerged, contact Install the drain hose to ensure that Keep level even when Installing the productUse two or more people to lift and transport the product Operational Be careful and avoid personal injury Dimensions Indoor UnitSplit Type Indoor 24kBtu/h Outdoor UnitUnit Product SpecificationsDMC24DB-1 OperationDMH24DB-1 Installation Installation PartsInstallation Tools Outdoor unit Rooftop InstallationsSelect the best location Indoor unitPiping length and elevation Multi Piping Type24k Fixing Installation PlateStandard Type Flaring work Flaring Work and Connection of PipingConnecting the Piping CheckIndoor Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Remote Control Preparationoptional Outdoor unit OutdoorConnect the cable to the Indoor unit Connecting the Cable between Indoor Unit and Outdoor UnitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Connection method of the connecting cableExampleConnect the cable to the indoor unit Checking the drainage To check the drainageDrain piping Down to up Forming the pipingChecking method Air Purging and EvacuationRepeat evacuation procedure for each indoor unit EvacuationFinishing the job Additional ChargingSplit Type Test RunningOperation Cooling Mode OperationSoft Dry Operation Mode Heating Mode OperationDefrost ControlHeating Fuzzy OperationFuzzy Operation for Cooling Fuzzy Operation for Dehumidification On-Timer OperationOff-Timer Operation Airflow Speed SelectionChaos Natural Wind Mode Off-Timer = On-Timer OperationSleep Timer Operation Chaos Swing ModeBuzzer Sounding Operation Forced OperationSplit Type Indoor Unit Function of Indoor UnitFunction of Outdoor Unit Remote Control Operation Cooling Model , Heat Pump Model15 2nd F Button To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Schematic Diagram Electronic Control DeviceIndoor Unit TMP87CM41F Outdoor UnitRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Room Type Indoor Unit Wiring DiagramBottom View Components LocationsDisplay Assembly Split Type 6871A20680 Component side Solder side DMC24DB-1 Troubleshooting GuideRefrigeration Cycle Diagram DMH24DB-1Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are dont operate Nector Trouble 4 When indoor Fan does not operateTroubleshooting Guide Indoor inlet pipe sensor Error CodeCheck Point Indoor air sensorCommunication line is shorted at GND Power input AC 230V.Outdoor, IndoorError Title Cause of error Check point & Normal condition Pipe sensor Title Cause of error Check point & Normal conditionOutdoor air sensor Condensor pipe sensorWay Valve Liguid Side Way, 3-way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationHeat CONTROLLER, INC