Troubleshooting Guide
ErrorCode
■Trouble Shooting
Error | Title | Cause of error | Check point & Normal condition | ||
code | |||||
|
|
|
| ||
|
|
|
|
| |
|
| • Open / Short | Normal resistor : 10KΩ / at 25°C(77°F) (Unplugged) | ||
01 | Indoor air sensor | • Soldered poorly | |||
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged) | |||||
|
| • Internal circuit error | |||
|
|
|
| ||
|
|
|
|
| |
|
| • Open / Short | Normal resistor : 5KΩ | / at 25°C(77°F) (Unplugged) | |
02 | Indoor inlet pipe sensor | • Soldered poorly | |||
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged) | |||||
|
| • Internal circuit error | |||
|
|
|
| ||
|
|
|
|
| |
|
| • Open / Short | Normal resistor : 5KΩ | / at 25°C(77°F) (Unplugged) | |
06 | Indoor outlet pipe sensor | • Soldered poorly | |||
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged) | |||||
|
| • Internal circuit error | |||
|
|
|
| ||
|
|
|
|
|
10KΩ |
Ω |
2.5Vdc |
V |
Check the resistance / voltage
❑Check Point
1.Unplug the sensor on Indoor unit PCB.
2.Estimate the resistance of each sensor
3. If the resistance of the sensor is 10KΩ /5KΩ at 25°C(77°F), then sensor is normal
4.If the resistance of the sensor is 0 KΩ or ∞ , then sensor is abnormal. ➔ Change the sensor.
5.Plug the sensor on Indoor unit PCB and Power ON.
6.Estimate the voltage of each sensor.
7.If the voltage of the sensor is 2.5Vdc / at 25°C(77°F), then sensor is normal.
8.If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. ➔ Repair or Change the PCB