Heat Controller DMC24DB-1, DMH24DB-1 manual Cycle Troubleshooting Guide, Trouble analysis

Page 56

Troubleshooting Guide

CycleTroubleshooting Guide

Trouble analysis

1. Check temperature difference between intake and discharge air, and operating current.

Temp. Difference

Operating Current

 

Temp. difference

: approx. 0°C(0°F)

 

Current

: less than 80% of

 

 

 

rated current

 

 

 

 

 

 

 

Temp. difference

: approx. 8°C(14.4°F)

 

Current

: less than 80% of

 

 

rated current

 

 

 

 

 

 

 

Temp. difference

: less than 8°C(14.4°F)

 

Current

: near the rated cur-

 

 

 

rent

 

 

 

All amount of refrigerant leaked out. Check refrigeration cycle.

Refrigerant leakage

Clog of refrigeration cycle

Defective compressor

Excessive amount of refrigerant

Temp. difference : over 8°C(14.4°F)

Normal

Notice:

Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Suction pressure

Temperature

 

 

(Compared with

(Compared with

Cause of Trouble

Description

the normal value)

the normal value)

 

 

 

 

 

 

 

High

Defective compressor

Current is low.

Higher

 

 

 

Normal

Excessive amount of

High pressure does not quickly

 

 

 

refrigerant

rise at the beginning of operation.

 

 

 

 

 

 

Insufficient amount of

Current is low.

Lower

Higher

refrigerant(Leakage)

 

 

 

Clogging

 

 

 

 

 

Notice:

1.The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.

2.The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.

56Multi type Air Conditioner

Image 56
Contents Heat CONTROLLER, INC Table of Contents Symbols Used in this Manual Combination tableSafety Precautions InstallationBe sure not to do Be sure to follow the instruction Control box securely Cuit and breakerDo not install, remove, or re Do not install the product on aDefective installation stand Do not allow water to run into electric partsFlooded or submerged, contact When the product is soakedNot enter the product Use two or more people to lift and transport the product Install the drain hose to ensure that Keep level even whenInstalling the product Operational Be careful and avoid personal injury Split Type Indoor DimensionsIndoor Unit Outdoor Unit 24kBtu/hProduct Specifications DMC24DB-1Operation UnitDMH24DB-1 Installation Tools InstallationInstallation Parts Rooftop Installations Select the best locationIndoor unit Outdoor unit24k Piping length and elevationMulti Piping Type Fixing Installation PlateStandard Type Flaring Work and Connection of Piping Flaring workIndoor Connecting the PipingCheck Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Remote Control Preparationoptional Outdoor Outdoor unitConnecting the Cable between Indoor Unit and Outdoor Unit Connect the cable to the Indoor unitConnect the cable to the Outdoor unit Outdoor unitConnection method of the connecting cableExample How to connect wiring to the terminalsConnect the cable to the indoor unit Drain piping Checking the drainageTo check the drainage Forming the piping Down to upAir Purging and Evacuation Checking methodFinishing the job Repeat evacuation procedure for each indoor unitEvacuation Charging AdditionalTest Running Split TypeCooling Mode Operation Soft Dry Operation ModeHeating Mode Operation OperationFuzzy Operation for Cooling Defrost ControlHeatingFuzzy Operation On-Timer Operation Off-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationOff-Timer = On-Timer Operation Sleep Timer OperationChaos Swing Mode Chaos Natural Wind ModeForced Operation Buzzer Sounding OperationFunction of Indoor Unit Split Type Indoor UnitFunction of Outdoor Unit 15 2nd F Button Remote Control OperationCooling Model , Heat Pump Model Disassembly To remove the Grille from the ChassisTo remove the Control Box To remove the Motor Cover Indoor Unit Schematic DiagramElectronic Control Device Outdoor Unit TMP87CM41FRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Wiring Diagram Room Type Indoor UnitComponents Locations Bottom ViewDisplay Assembly Split Type 6871A20680 Component side Solder side Troubleshooting Guide Refrigeration Cycle DiagramDMH24DB-1 DMC24DB-1Indoor Error Outdoor ErrorError Indicator Self-diagnosis FunctionCycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Procedure Specification RemedyProduct doesnt operate with the remote controller Compressor/Outdoor Fan are dont operate Check Point Comp. on Comp. OFFTrouble 4 When indoor Fan does not operate NectorTroubleshooting Guide Error Code Check PointIndoor air sensor Indoor inlet pipe sensorPower input AC 230V.Outdoor, Indoor Communication line is shorted at GNDError Title Cause of error Check point & Normal condition Title Cause of error Check point & Normal condition Outdoor air sensorCondensor pipe sensor Pipe sensorWay, 3-way Valve Way Valve Liguid SideProcedure Pumping downAir purging of the charge hose Set the liquid side valve to the closed positionAll amount of refrigerant leaked Mount the valve caps and the service port capsEvacuation Mount the valve stem nuts and the service port nut Gas ChargingAfter Evacuation Connect the gauge to the charging cylinderHeat CONTROLLER, INC