Heat Controller DMC24DB-1, DMH24DB-1 manual Test Running, Split Type

Page 34

Test Running

Test Running

Split Type

1.Check that all tubing and wiring have been properly con- nected.

2.Check that the gas and liquid side service valves are fully open.

1) Prepare remote controller

Remove the battery cover by pulling it according to the arrow direction.

Insert new batteries making sure that the (+) and (–) of battery are installed correctly.

Reattach the cover by pushing it back into position.

NOTE:

Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.

Remove the batteries from the remote controller if the sys- tem is not going to be used for a long time.

2)Precautions in test run

The initial power supply must provide at least 90% of the rated voltage.

Otherwise, the air conditioner should not be operated.

For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compres- sor. Then attention must be paid.

Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later auto- matically)

The test run is started by pressing timer cancel button five times continuously. (Room type)

To cancel the test run, press any button.

3)Settlement of outdoor unit

Bolt

Tubing connection

4) Evaluation of the performance

Operate unit for 15~20 minutes, then check the system refrigerant charge:

1.Measure the pressure of the gas side service valve.

2.Measure the temperature of the intake and discharge of air.

3.Ensure the difference between the intake temperature and the discharge is more than 8°C(14.4°F) (Cooling) or reversely (Heating).

Refrigerant

Outside ambient

The pressure of the gas side

TEMP.

service valve.

 

R-410A

35°C (95°F)

8.5~9.5kg/cm2G(120~135 P.S.I.G.)

 

 

 

Intake temperature

Discharge air

Discharge temperature

Anchor the outdoor unit with a bolt and nut(ø 10mm) tightly and horizontally on a concrete or rigid mount.

When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.

In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration rubber.

34Multi type Air Conditioner

Image 34
Contents Heat CONTROLLER, INC Table of Contents Symbols Used in this Manual Combination tableBe sure not to do Be sure to follow the instruction Safety PrecautionsInstallation Control box securely Cuit and breakerDefective installation stand Do not install, remove, or reDo not install the product on a Do not allow water to run into electric partsNot enter the product When the product is soakedFlooded or submerged, contact Installing the product Install the drain hose to ensure that Keep level even whenUse two or more people to lift and transport the product Operational Be careful and avoid personal injury Indoor Unit DimensionsSplit Type Indoor Outdoor Unit 24kBtu/hOperation Product SpecificationsDMC24DB-1 UnitDMH24DB-1 Installation Parts InstallationInstallation Tools Indoor unit Rooftop InstallationsSelect the best location Outdoor unitMulti Piping Type Piping length and elevation24k Fixing Installation PlateStandard Type Flaring Work and Connection of Piping Flaring workCheck Connecting the PipingIndoor Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Remote Control Preparationoptional Outdoor Outdoor unitConnecting the Cable between Indoor Unit and Outdoor Unit Connect the cable to the Indoor unitConnect the cable to the Outdoor unit Outdoor unitConnection method of the connecting cableExample How to connect wiring to the terminalsConnect the cable to the indoor unit To check the drainage Checking the drainageDrain piping Forming the piping Down to up Air Purging and Evacuation Checking methodEvacuation Repeat evacuation procedure for each indoor unitFinishing the job Charging AdditionalTest Running Split TypeHeating Mode Operation Cooling Mode OperationSoft Dry Operation Mode OperationFuzzy Operation Defrost ControlHeatingFuzzy Operation for Cooling Airflow Speed Selection On-Timer OperationOff-Timer Operation Fuzzy Operation for DehumidificationChaos Swing Mode Off-Timer = On-Timer OperationSleep Timer Operation Chaos Natural Wind ModeForced Operation Buzzer Sounding OperationFunction of Indoor Unit Split Type Indoor UnitFunction of Outdoor Unit Cooling Model , Heat Pump Model Remote Control Operation15 2nd F Button Disassembly To remove the Grille from the ChassisTo remove the Control Box To remove the Motor Cover Electronic Control Device Schematic DiagramIndoor Unit Outdoor Unit TMP87CM41FRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Wiring Diagram Room Type Indoor UnitComponents Locations Bottom ViewDisplay Assembly Split Type 6871A20680 Component side Solder side DMH24DB-1 Troubleshooting GuideRefrigeration Cycle Diagram DMC24DB-1Error Indicator Indoor ErrorOutdoor Error Self-diagnosis FunctionCycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Procedure Specification RemedyProduct doesnt operate with the remote controller Compressor/Outdoor Fan are dont operate Check Point Comp. on Comp. OFFTrouble 4 When indoor Fan does not operate NectorTroubleshooting Guide Indoor air sensor Error CodeCheck Point Indoor inlet pipe sensorPower input AC 230V.Outdoor, Indoor Communication line is shorted at GNDError Title Cause of error Check point & Normal condition Condensor pipe sensor Title Cause of error Check point & Normal conditionOutdoor air sensor Pipe sensorWay, 3-way Valve Way Valve Liguid SideAir purging of the charge hose ProcedurePumping down Set the liquid side valve to the closed positionEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked After Evacuation Mount the valve stem nuts and the service port nutGas Charging Connect the gauge to the charging cylinderHeat CONTROLLER, INC