Heat Controller DMH24DB-1, DMC24DB-1 manual Pumping down, Procedure, Air purging of the charge hose

Page 67

2-way, 3-way Valve

(1) Pumping down

Indoor unit

Liquid side

 

Close

Outdoor unit

2-Way

valve

Gas side

Open

3-Way

valve

Indoor unit

Liquid side

 

Close

2-Way

valve

Gas side

Open

3-Way

valve

manifold gauge

Low- handle

(CLOSE)Hi- handle (CLOSE)

Procedure

1.Confirm that both the gas side and liquid side valves are set to the open position.

-Remove the valve stem caps and confirm that the valve stems are in the raised position.

-Be sure to use a hexagonal wrench to operate the valve stems.

2.Operate the unit for 10 to 15 minutes.

3.Stop operation and wait for 3 minutes, then con- nect the manifold gauge to the service port of the gas side valve.

-Connect the hose of the gauge with the push pin to the service port.

4.Air purging of the charge hose.

-Open the Low-handle valve on the gauge slightly to air purge from the hose.

5.Set the liquid side valve to the closed position.

6.Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2g.

7.Immediately set the gas side valve to the closed position.

-Do this quickly so that the gauge ends up indicat- ing 1kg/ g.

8.Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut.

-Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(156.2 lbf·in) [4.2kg.m (364.5

lbf·in)/5.5kg.m (477.4 lbf·in)]

-Be sure to check for gas leakage.

• Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.

Service Manual 67

Image 67
Contents Heat CONTROLLER, INC Table of Contents Combination table Symbols Used in this ManualControl box securely Cuit and breaker Safety PrecautionsInstallation Be sure not to do Be sure to follow the instructionDo not allow water to run into electric parts Do not install, remove, or reDo not install the product on a Defective installation standNot enter the product When the product is soakedFlooded or submerged, contact Installing the product Install the drain hose to ensure that Keep level even whenUse two or more people to lift and transport the product Operational Be careful and avoid personal injury Indoor Unit DimensionsSplit Type Indoor 24kBtu/h Outdoor UnitUnit Product SpecificationsDMC24DB-1 OperationDMH24DB-1 Installation Parts InstallationInstallation Tools Outdoor unit Rooftop InstallationsSelect the best location Indoor unitMulti Piping Type Piping length and elevation24k Fixing Installation PlateStandard Type Flaring work Flaring Work and Connection of PipingCheck Connecting the PipingIndoor Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Remote Control Preparationoptional Outdoor unit OutdoorConnect the cable to the Indoor unit Connecting the Cable between Indoor Unit and Outdoor UnitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Connection method of the connecting cableExampleConnect the cable to the indoor unit To check the drainage Checking the drainageDrain piping Down to up Forming the pipingChecking method Air Purging and EvacuationEvacuation Repeat evacuation procedure for each indoor unitFinishing the job Additional ChargingSplit Type Test RunningOperation Cooling Mode OperationSoft Dry Operation Mode Heating Mode OperationFuzzy Operation Defrost ControlHeatingFuzzy Operation for Cooling Fuzzy Operation for Dehumidification On-Timer OperationOff-Timer Operation Airflow Speed SelectionChaos Natural Wind Mode Off-Timer = On-Timer OperationSleep Timer Operation Chaos Swing ModeBuzzer Sounding Operation Forced OperationSplit Type Indoor Unit Function of Indoor UnitFunction of Outdoor Unit Cooling Model , Heat Pump Model Remote Control Operation15 2nd F Button To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Electronic Control Device Schematic DiagramIndoor Unit TMP87CM41F Outdoor UnitRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Room Type Indoor Unit Wiring DiagramBottom View Components LocationsDisplay Assembly Split Type 6871A20680 Component side Solder side DMC24DB-1 Troubleshooting GuideRefrigeration Cycle Diagram DMH24DB-1Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are dont operateNector Trouble 4 When indoor Fan does not operateTroubleshooting Guide Indoor inlet pipe sensor Error CodeCheck Point Indoor air sensorCommunication line is shorted at GND Power input AC 230V.Outdoor, Indoor Error Title Cause of error Check point & Normal condition Pipe sensor Title Cause of error Check point & Normal conditionOutdoor air sensor Condensor pipe sensorWay Valve Liguid Side Way, 3-way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationHeat CONTROLLER, INC