| Troubleshooting Guide | |
|
|
|
|
|
Error | Title | Cause of error | Check point & Normal condition |
|
code |
| |||
|
|
|
| |
|
|
|
|
|
|
| • Open / Short | Normal resistor : 10KΩ / at 25°C(77°F) (Unplugged) |
|
44 | Outdoor air sensor | • Soldered poorly |
| |
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged) |
| |||
|
| • Internal circuit error |
| |
|
|
|
| |
|
|
|
|
|
|
| • Open / Short | Normal resistor : 5KΩ / at 25°C(77°F) (Unplugged) |
|
45 | Condensor pipe sensor | • Soldered poorly |
| |
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged) |
| |||
|
| • Internal circuit error |
| |
|
|
|
| |
|
|
|
|
|
|
| • Open / Short | Normal resistor : 200KΩ / at 25°C(77°F) (Unplugged) |
|
47 |
| • Soldered poorly |
| |
Normal voltage : 4.5Vdc / at 25°C(77°F) (plugged) |
| |||
|
| • Internal circuit error |
| |
|
|
|
| |
|
|
|
|
|
Ω |
Ω |
Check the resistance
❑Check Point
1.Estimate the resistance of each sensor.(Unplugged)
2.Estimate the voltage of each sensor.(Plugged)
3.If the resistance is 0V or 5Vdc, then sensor is abnormal
Service Manual 65