Charging

Charging

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.

Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot).

 

Max total length

Max length of

Min length of

Max Elevation

Max elevation

Additional

 

between each indoor

Capacity (Btu/h)

of all pipes

between indoor

each pipe (A/B)

each pipe (A/B)

unit and outdoor unit

Refrigerant

 

(A+B)

 

 

(h1)

units (h2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24k

30m(100ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

Example: A 80ft line set is used for dual - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit. Unit is critically charged.

Service Manual 33

Image 33
Contents Heat CONTROLLER, INC Table of Contents Combination table Symbols Used in this ManualInstallation Safety PrecautionsBe sure not to do Be sure to follow the instruction Control box securely Cuit and breakerDo not install the product on a Do not install, remove, or reDefective installation stand Do not allow water to run into electric partsWhen the product is soaked Not enter the productFlooded or submerged, contact Install the drain hose to ensure that Keep level even when Installing the productUse two or more people to lift and transport the product Operational Be careful and avoid personal injury Dimensions Indoor UnitSplit Type Indoor 24kBtu/h Outdoor UnitDMC24DB-1 Product SpecificationsOperation UnitDMH24DB-1 Installation Installation PartsInstallation Tools Select the best location Rooftop InstallationsIndoor unit Outdoor unitPiping length and elevation Multi Piping Type24k Fixing Installation PlateStandard Type Flaring work Flaring Work and Connection of PipingConnecting the Piping CheckIndoor Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Remote Control Preparationoptional Outdoor unit OutdoorConnect the cable to the Indoor unit Connecting the Cable between Indoor Unit and Outdoor UnitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Connection method of the connecting cableExampleConnect the cable to the indoor unit Checking the drainage To check the drainageDrain piping Down to up Forming the pipingChecking method Air Purging and EvacuationRepeat evacuation procedure for each indoor unit EvacuationFinishing the job Additional ChargingSplit Type Test RunningSoft Dry Operation Mode Cooling Mode OperationHeating Mode Operation OperationDefrost ControlHeating Fuzzy OperationFuzzy Operation for Cooling Off-Timer Operation On-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationSleep Timer Operation Off-Timer = On-Timer OperationChaos Swing Mode Chaos Natural Wind ModeBuzzer Sounding Operation Forced OperationSplit Type Indoor Unit Function of Indoor UnitFunction of Outdoor Unit Remote Control Operation Cooling Model , Heat Pump Model15 2nd F Button To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Schematic Diagram Electronic Control DeviceIndoor Unit TMP87CM41F Outdoor UnitRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Room Type Indoor Unit Wiring DiagramBottom View Components LocationsDisplay Assembly Split Type 6871A20680 Component side Solder side Refrigeration Cycle Diagram Troubleshooting GuideDMH24DB-1 DMC24DB-1Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are dont operateNector Trouble 4 When indoor Fan does not operateTroubleshooting Guide Check Point Error CodeIndoor air sensor Indoor inlet pipe sensorCommunication line is shorted at GND Power input AC 230V.Outdoor, IndoorError Title Cause of error Check point & Normal condition Outdoor air sensor Title Cause of error Check point & Normal conditionCondensor pipe sensor Pipe sensorWay Valve Liguid Side Way, 3-way ValvePumping down ProcedureAir purging of the charge hose Set the liquid side valve to the closed positionMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Gas Charging Mount the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderHeat CONTROLLER, INC