Heat Controller DMH24DB-1, DMC24DB-1 manual To remove the Motor Cover

Page 45

 

Disassembly

Unhook the tab on the right inside of the chassis

 

at the same time, slightly pull the evaporator

 

toward you until the tab is clear of the slot.

5.To remove the Motor Cover

Remove 2 securing screw.

Pull the motor cover out from the chassis carefully.

6.To remove the Cross-Flow Fan

Loosen the screw securing the cross-flow fan to the fan motor (do not remove).

Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.

Remove the left end of the cross-flow fan from the self-aligning bearing.

Motor cover

Bearing

Cross-flow fan

Service Manual 45

Image 45
Contents Heat CONTROLLER, INC Table of Contents Combination table Symbols Used in this ManualInstallation Safety PrecautionsBe sure not to do Be sure to follow the instruction Control box securely Cuit and breakerDo not install the product on a Do not install, remove, or reDefective installation stand Do not allow water to run into electric partsWhen the product is soaked Not enter the productFlooded or submerged, contact Install the drain hose to ensure that Keep level even when Installing the productUse two or more people to lift and transport the product Operational Be careful and avoid personal injury Dimensions Indoor UnitSplit Type Indoor 24kBtu/h Outdoor UnitDMC24DB-1 Product SpecificationsOperation UnitDMH24DB-1 Installation Installation PartsInstallation Tools Select the best location Rooftop InstallationsIndoor unit Outdoor unitPiping length and elevation Multi Piping Type24k Fixing Installation PlateStandard Type Flaring work Flaring Work and Connection of PipingConnecting the Piping CheckIndoor Wrap the insulation material around the connecting por- tion For left rear piping Plastic bands Insulation material Connection Indoor Remote Control Preparationoptional Outdoor unit OutdoorConnect the cable to the Indoor unit Connecting the Cable between Indoor Unit and Outdoor UnitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Connection method of the connecting cableExampleConnect the cable to the indoor unit Checking the drainage To check the drainageDrain piping Down to up Forming the pipingChecking method Air Purging and EvacuationRepeat evacuation procedure for each indoor unit EvacuationFinishing the job Additional ChargingSplit Type Test RunningSoft Dry Operation Mode Cooling Mode OperationHeating Mode Operation OperationDefrost ControlHeating Fuzzy OperationFuzzy Operation for Cooling Off-Timer Operation On-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationSleep Timer Operation Off-Timer = On-Timer OperationChaos Swing Mode Chaos Natural Wind ModeBuzzer Sounding Operation Forced OperationSplit Type Indoor Unit Function of Indoor UnitFunction of Outdoor Unit Remote Control Operation Cooling Model , Heat Pump Model 15 2nd F Button To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Schematic Diagram Electronic Control DeviceIndoor Unit TMP87CM41F Outdoor UnitRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Room Type Indoor Unit Wiring DiagramBottom View Components LocationsDisplay Assembly Split Type 6871A20680 Component side Solder side Refrigeration Cycle Diagram Troubleshooting GuideDMH24DB-1 DMC24DB-1Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are dont operateNector Trouble 4 When indoor Fan does not operateTroubleshooting Guide Check Point Error CodeIndoor air sensor Indoor inlet pipe sensorCommunication line is shorted at GND Power input AC 230V.Outdoor, IndoorError Title Cause of error Check point & Normal condition Outdoor air sensor Title Cause of error Check point & Normal conditionCondensor pipe sensor Pipe sensorWay Valve Liguid Side Way, 3-way ValvePumping down ProcedureAir purging of the charge hose Set the liquid side valve to the closed positionMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Gas Charging Mount the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderHeat CONTROLLER, INC
Related manuals
Manual 35 pages 26.68 Kb Manual 29 pages 18.54 Kb