Troubleshooting Guide
Error | Title | Cause of error | Check point & Normal condition | |
code | ||||
|
|
| ||
|
|
|
| |
|
| • Discharge sensor | • Check the discharge pipe sensor. | |
33 | • Check the install condition for over load. | |||
temp. high | • Check the leakage of refrigerent. | |||
|
| |||
|
|
| • Check the SVC V/V open. | |
|
|
|
|
COMP OFF
115° C(239° F)
LEV OPEN(16PULSE/MIN)
100° C(212° F)
LEV OPEN(10PULSE/MIN)
95° C(203° F)
NORMAL
A2UH243FA0/A2UC243FA0
❑Check Point
1.Check the install condition for over load.
2.Check the SVC V/V open.
3.Check the leakage of refrigerent.
4.Check the constant compressor.
Error | Title | Cause of error | Check point & Normal condition | |
code | ||||
|
|
| ||
|
|
|
| |
51 | Capacitor error | • Over Capacitor com- | • Check the indoor unit capacity. | |
bination | • Check the combination table | |||
|
| |||
|
|
|
|
❑Check Point
1.Check the indoor unit capacity.
2.Check the combination table.
★In the tropical model case
➔single cycle has no error for over capacity.
64Multi type Air Conditioner