Friedrich SS14N10*, SS12N10* Undercharged Refrigerant Systems, Overcharged Refrigerant Systems

Page 40

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation.

Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

WARNING

HIGH PRESSURE HAZARD

Sealed Refrigeration System contains refrigerant and oil under high pressure.

Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.

Failure to follow these procedures could result in serious injury or death.

Undercharged Refrigerant Systems

 

A check of the amperage drawn by the compressor

An undercharged system will result in poor performance

motor should show a lower reading. (Check the Unit

(low pressures, etc.) in both the heating and cooling cycle.

Specification.) After the unit has run 10 to 15 minutes,

Whenever you service a unit with an undercharge

of

check the gauge pressures. Gauges connected to system

with an undercharge will have low head pressures and

refrigerant, always suspect a leak. The leak must

be

substantially low suction pressures.

repaired before charging the unit.

 

 

 

To check for an undercharged system, turn the unit on, allow the compressor to run long enough to establish working pressures in the system (15 to 20 minutes).

During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator; an intermittent hissing and gurgling sound indicates a low refrigerant charge. Intermittent frosting and thawing of the evaporator is another indication of a low charge, however, frosting and thawing can also be caused by insufficient air over the evaporator.

Checks for an undercharged system can be made at the compressor. If the compressor seems quieter than normal, it is an indication of a low refrigerant charge.

Overcharged Refrigerant Systems

of the evaporator will not be encountered because the

Compressor amps will be near normal or higher.

refrigerant will boil later if at all. Gauges connected to

system will usually have higher head pressure (depending

Noncondensables can also cause these symptoms.

upon amount of over charge). Suction pressure should be

To confirm, remove some of the charge, if conditions

slightly higher.

improve, system may be overcharged. If conditions don’t

 

 

 

improve, Noncondensables are indicated.

 

 

 

Whenever an overcharged system is indicated, always

 

 

 

make sure that the problem is not caused by air flow

 

 

 

problems. Improper air flow over the evaporator coil may

 

 

 

indicate some of the same symptoms as an over charged

 

 

 

system.

 

 

 

An overcharge can cause the compressor to fail, since it

 

 

 

would be “slugged” with liquid refrigerant.

 

 

 

The charge for any system is critical. When the compressor

 

 

 

is noisy, suspect an overcharge, when you are sure that

 

 

 

the air quantity over the evaporator coil is correct. Icing

 

 

 

 

 

 

 

39

Image 40 Contents
Cool Only Heat PumpTable Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Repair Hazards Property Damage Hazards Components Identification IntroductionModel and Serial Number Location Unit Identification Specifications Refrigeration System Performance DataKeep the filter clean Unit placementProper installation of seal gasket Provide good air flowElectric Shock Hazard Electrical DataFire Hazard Electrical Shock Hazard Kuhl Control Options FriedrichLink AdapterControl Panel and Display Identification Control Panel Operation Instructions Timer Schedule Button ºF ºC SelectDIM Function AlertsControl Panel Lock External Control StatusTo Turn On the Timer or Schedule Selected Timer or Schedule Options 1 or 2 SelectionTimer Start Time Timer SettingsSet theTimer Stop Time Timer on ScenariosTimer OFF Scenarios Timer Schedule Control BlockRemote Control Operation Remote Control Operation Unit Operation Front PanelElectronic Control Sequence of Operation Compressor OperationHeating Mode Control Operation Heat Control Heat Pump OnlyHeat Pump With Electric Heat Operation ConditionElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Using ModeRemoving the Front Cover Replacing the Indoor Coil Thermistor Swing OutAir flow direction adjustment Fresh air and exhaust controlComponents Testing Capacitor Check with Capacitor AnalyzerCapacitor Connections FAN MotorTesting the Heating Element Electric Shock Hazard Heating ElementHeating Element Heat Pump Models Drain PAN ValveUser Interface Control Board Refrigeration Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Refrigerant ChargingBurn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Reversing Valve Solenoid Coil Reversing Valve in Heating ModeTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Single Phase Connections Single Phase Running and L.R.A. TestLocked Rotor Voltage L.R.V. Test Determine L.R.VGround Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement High TemperaturesHigh Pressure Hazard Routine Maintenance Decorative Front Cover Sleeve / DrainClearances Filter assembly Heat pumps operate differently Condensation is normalFrosting NoisesIf you require further assistance Our specialists are able to assist you withDC-2 Drain Kit Part No Carbon Filter KitsSee codes chart on next Error Codes and Alarm Status Test Mode Temp Room AIR Conditioner Unit Performance Test Data Sheet HOW is ALL of the INSTALLATION? Good BADJOB Name Techs Name = SQ/CU/FTTroubleshooting Tips Problem Possible Cause Possible SolutionTroubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Heat / Cool only Room AIR Conditioners Troubleshooting Tips Heat Pump Room AIR Conditioners Trouble Shooting Tips Problem Possible Cause ActionSystem Cools When Heating is Desired YESNormal Function of Valve Malfunction of ValveElectronic Control Board Components Identification Procedure ContentsFriedrich Electronic Control KIT Friedrich Model Prefix Schematic Part NO. REV 92170013 Kϋhl Electronic Control Cool only Models SL36N30-A Wiring Diagram Wiring Diagram 92170015 92170016 Kϋhl Electronic Control Heat Pump model YL24N35-A Need to Configure it. Follow the steps below to configure Air Conditioner Message Remote Control MessageAir Conditioning Unit Display Remote Control Display Replacement Instructions Parts Section Parts Section Kühl & Kühl+ Small-Chassis 2012 Parts List SHROUD, SML Kühl & Kühl+ Medium-Chassis 2012 Parts List SHROUD, MED Kühl & Kühl+ Large-Chassis 2012 Parts List Deck LRG Addendum Schedule Table with Energy Saving ValuesRoom AIR Conditioners Limited Warranty AAA Refrigeration Service Customer Satisfaction and Quality AssuranceFriedrich AIR Conditioning CO