Friedrich SS14N10*, SS12N10*, SS15N30* Heating Mode Control Operation, Heat Control Heat Pump Only

Page 25

Heating Mode Control Operation

There are two heating methods: Heat Pump and Electric Resistance Heat.

There are 3 types of units that provide heating: Heat Pump Only (Model YS10M10)

Heat Pump with Electric Heat and Cool with Electric Heat.

Heat Control Operation Heat Pump Only Unit (YS10M10 has no electric heat back-up)

Once the ambient temperature falls below the Heating Demand Threshold

(1.5 ˚F Below the Heat Set Point Temperature), the heating cycle begins. The fan is turned on 5 seconds before. Once the ambient temperature has been raised to the Heat Satisfied Point (Set point + .25 ˚F), the compressor is turned off. The fan is turned off 15 seconds later. The figure below illustrates the basic heat pump operation.

Satisfied Point

Heat Control (Heat Pump Only)

YS10M10 Heat Pump Defrost Cycle Operation

The defrost in this unit is an active reverse cycle. The defrost control runs in the background and determines when a defrost cycle is required. Once initiated, the defrost cycle runs to completion.

The defrost cycle can only be initiated when the heat pump is in operation. The compressor will not be turned off to avoid activating the compressor's time delay. The reversing valve will be switched to the cool mode position. The indoor fan/blower will be turned off. Once the defrost cycle is finished, the system should re-enter a heating demand cycle if required.

When the heat pump run time is 60 minutes or greater with an outdoor coil temperature of 26F degrees or lower, the control will run an active defrost for up to 6 minutes. When the temperature at the outdoor coil reaches 54F degrees, the heat pump heat will resume.

24

Image 25
Contents Heat Pump Cool OnlyTable Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Repair Hazards Property Damage Hazards Components Identification IntroductionModel and Serial Number Location Unit Identification Refrigeration System Performance Data SpecificationsUnit placement Keep the filter cleanProper installation of seal gasket Provide good air flowElectric Shock Hazard Electrical DataFire Hazard Electrical Shock Hazard FriedrichLink Adapter Kuhl Control OptionsControl Panel and Display Identification Control Panel Operation Instructions ºF ºC Select Timer Schedule ButtonAlerts DIM FunctionControl Panel Lock External Control StatusTimer or Schedule Options 1 or 2 Selection To Turn On the Timer or Schedule SelectedTimer Settings Timer Start TimeTimer on Scenarios Set theTimer Stop TimeTimer Schedule Control Block Timer OFF ScenariosRemote Control Operation Remote Control Operation Front Panel Unit OperationCompressor Operation Electronic Control Sequence of OperationHeat Control Heat Pump Only Heating Mode Control OperationCondition Heat Pump With Electric Heat OperationElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Mode UsingRemoving the Front Cover Swing Out Replacing the Indoor Coil ThermistorFresh air and exhaust control Air flow direction adjustmentCapacitor Check with Capacitor Analyzer Components TestingCapacitor Connections FAN MotorHeating Element Testing the Heating Element Electric Shock HazardHeating Element Heat Pump Models Drain PAN ValveUser Interface Control Board Refrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRefrigerant Charging 410A Sealed Refrigeration System RepairsBurn Hazard Method Of Charging / RepairsFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckReversing Valve DESCRIPTION/OPERATION Reversing Valve in Heating Mode Testing the Reversing Valve Solenoid CoilTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Single Phase Running and L.R.A. Test Single Phase ConnectionsLocked Rotor Voltage L.R.V. Test Determine L.R.VGround Test Single Phase Resistance TestChecking Compressor Efficiency High Temperatures Recommended procedure for compressor replacementHigh Pressure Hazard Routine Maintenance Decorative Front Cover Sleeve / DrainClearances Filter assembly Condensation is normal Heat pumps operate differentlyFrosting NoisesOur specialists are able to assist you with If you require further assistanceDC-2 Drain Kit Part No Carbon Filter KitsSee codes chart on next Error Codes and Alarm Status Test Mode Temp HOW is ALL of the INSTALLATION? Good BAD Room AIR Conditioner Unit Performance Test Data SheetJOB Name Techs Name = SQ/CU/FTProblem Possible Cause Possible Solution Troubleshooting TipsTroubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Heat / Cool only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause Action Heat Pump Room AIR Conditioners Trouble Shooting TipsYES System Cools When Heating is DesiredMalfunction of Valve Normal Function of ValveElectronic Control Board Components Identification Procedure ContentsFriedrich Electronic Control KIT Friedrich Model Prefix Schematic Part NO. REV 92170013 Kϋhl Electronic Control Cool only Models SL36N30-A Wiring Diagram Wiring Diagram 92170015 92170016 Kϋhl Electronic Control Heat Pump model YL24N35-A Air Conditioner Message Remote Control Message Need to Configure it. Follow the steps below to configureAir Conditioning Unit Display Remote Control Display Replacement Instructions Parts Section Parts Section Kühl & Kühl+ Small-Chassis 2012 Parts List SHROUD, SML Kühl & Kühl+ Medium-Chassis 2012 Parts List SHROUD, MED Kühl & Kühl+ Large-Chassis 2012 Parts List Deck LRG Schedule Table with Energy Saving Values AddendumRoom AIR Conditioners Limited Warranty Customer Satisfaction and Quality Assurance AAA Refrigeration ServiceFriedrich AIR Conditioning CO

SM18N30*, SS10N10*, SS15N30*, SS12N10*, SS14N10* specifications

Friedrich air conditioners, particularly models SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30*, are renowned for their reliable performance, innovative technologies, and user-friendly features. Designed for both residential and commercial use, these units stand out due to their energy efficiency, advanced cooling capabilities, and versatile operation.

One of the standout features across these models is their energy efficiency. Equipped with high SEER (Seasonal Energy Efficiency Ratio) ratings, they help users save on energy costs while reducing their carbon footprint. Specifically, the SS14N10* and SS12N10* models excel in cooling efficiency, ensuring that the spaces they occupy remain comfortably cool even in the hottest conditions. This not only contributes to lower energy bills but also promotes environmental sustainability.

The cooling technologies integrated into these units include advanced inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand of a room. As a result, these air conditioners maintain desired temperatures with minimal fluctuations, ensuring optimal comfort and significant energy savings. Models like SS15N30* and SM18N30* are particularly stellar in maintaining efficiency even during peak usage hours.

Moreover, these air conditioners are equipped with multi-stage filtration systems that enhance indoor air quality. The filters effectively capture dust, allergens, and other pollutants, resulting in cleaner and healthier air for occupants. This is especially important for individuals with allergies or respiratory issues.

User-friendly controls add another layer of convenience. Many models incorporate smart technology allowing users to control the units via mobile apps or home automation systems. This feature enables remote operation, scheduling, and real-time monitoring, making it easier to manage climate conditions effectively.

In terms of design, models like SS10N10* prioritize aesthetics without compromising functionality. They feature sleek, modern designs that seamlessly integrate into various decors, whether in a home or an office. Additionally, quiet operation technology reduces noise levels during functionality, enhancing comfort, particularly in bedrooms or quiet office environments.

Overall, Friedrich’s SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30* models embody the brand's commitment to innovation and customer satisfaction. Their blend of energy efficiency, advanced cooling technology, air quality enhancement, and smart controls positions them as leaders in the air conditioning market, catering to diverse cooling needs while promoting a sustainable future.