Friedrich SM18N30* Testing the Reversing Valve Solenoid Coil, Reversing Valve in Heating Mode

Page 44

TESTING THE REVERSING VALVE SOLENOID COIL

WARNING

ELECTRIC SHOCK HAZARD

Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service.

Failure to do so could result in electric shock, serious injury or death.

The solenoid coil is an electromagnetic type coil mounted on the reversing valve and is energized during the operation of the compressor in the heating cycle.

1.Turn off high voltage electrical power to unit.

2.Unplug line voltage lead from reversing valve coil.

3.Check for electrical continuity through the coil. If you do not have continuity replace the coil.

4.Check from each lead of coil to the copper liquid line as it leaves the unit or the ground lug. There should be no continuity between either of the coil leads and ground; if there is, coil is grounded and must be replaced.

5.If coil tests okay, reconnect the electrical leads.

6.Make sure coil has been assembled correctly.

NOTE: Do not start unit with solenoid coil removed from valve, or do not remove coil after unit is in operation. This will cause the coil to burn out.

CHECKING THE REVERSING VALVE

NOTE: You must have normal operating pressures before the reversing valve can shift.

WARNING

HIGH PRESSURE HAZARD

Sealed Refrigeration System contains refrigerant and oil under high pressure.

Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.

Failure to follow these procedures could result in serious injury or death.

Check the operation of the valve by starting the system and switching the operation from “Cooling” to “Heating” and then back to “Cooling”. Do not hammer on valve.

Occasionally, the reversing valve may stick in the heating or cooling position or in the mid-position.

When sluggish or stuck in the mid-position, part of the discharge gas from the compressor is directed back to the suction side, resulting in excessively high suction pressure.

Should the valve fail to shift from coooling to heating, block the air flow through the outdoor coil and allow the discharge pressure to build in the system. Then switch the system from heating to cooling.

If the valve is stuck in the heating position, block the air flow through the indoor coil and allow discharge pressure to build in the system. Then switch the system from heating to cooling.

Should the valve fail to shift in either position after increasing the discharge pressure, replace the valve.

Dented or damaged valve body or capillary tubes can prevent the main slide in the valve body from shifting.

If you determing this is the problem, replace the reversing valve.

After all of the previous inspections and checks have been made and determined correct, then perform the “Touch Test” on the reversing valve.

Reversing Valve in Heating Mode

43

Image 44
Contents Cool Only Heat PumpTable Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Repair Hazards Property Damage Hazards Model and Serial Number Location IntroductionComponents Identification Unit Identification Specifications Refrigeration System Performance DataKeep the filter clean Unit placementProper installation of seal gasket Provide good air flowFire Hazard Electrical DataElectric Shock Hazard Electrical Shock Hazard Kuhl Control Options FriedrichLink AdapterControl Panel and Display Identification Control Panel Operation Instructions Timer Schedule Button ºF ºC SelectDIM Function AlertsControl Panel Lock External Control StatusTo Turn On the Timer or Schedule Selected Timer or Schedule Options 1 or 2 SelectionTimer Start Time Timer SettingsSet theTimer Stop Time Timer on ScenariosTimer OFF Scenarios Timer Schedule Control BlockRemote Control Operation Remote Control Operation Unit Operation Front PanelElectronic Control Sequence of Operation Compressor OperationHeating Mode Control Operation Heat Control Heat Pump OnlyHeat Pump With Electric Heat Operation ConditionElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Using ModeRemoving the Front Cover Replacing the Indoor Coil Thermistor Swing OutAir flow direction adjustment Fresh air and exhaust controlComponents Testing Capacitor Check with Capacitor AnalyzerCapacitor Connections FAN MotorTesting the Heating Element Electric Shock Hazard Heating ElementHeating Element Heat Pump Models Drain PAN ValveUser Interface Control Board Refrigeration Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Refrigerant ChargingFreeze Hazard Method Of Charging / RepairsBurn Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Reversing Valve Solenoid Coil Reversing Valve in Heating ModeExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Single Phase Connections Single Phase Running and L.R.A. TestLocked Rotor Voltage L.R.V. Test Determine L.R.VChecking Compressor Efficiency Single Phase Resistance TestGround Test Recommended procedure for compressor replacement High TemperaturesHigh Pressure Hazard Routine Maintenance Clearances Sleeve / DrainDecorative Front Cover Filter assembly Heat pumps operate differently Condensation is normalFrosting NoisesIf you require further assistance Our specialists are able to assist you withDC-2 Drain Kit Part No Carbon Filter KitsSee codes chart on next Error Codes and Alarm Status Test Mode Temp Room AIR Conditioner Unit Performance Test Data Sheet HOW is ALL of the INSTALLATION? Good BADJOB Name Techs Name = SQ/CU/FTTroubleshooting Tips Problem Possible Cause Possible SolutionTroubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Heat / Cool only Room AIR Conditioners Troubleshooting Tips Heat Pump Room AIR Conditioners Trouble Shooting Tips Problem Possible Cause ActionSystem Cools When Heating is Desired YESNormal Function of Valve Malfunction of ValveElectronic Control Board Components Identification Friedrich Electronic Control KIT Friedrich Model Prefix ContentsProcedure Schematic Part NO. REV 92170013 Kϋhl Electronic Control Cool only Models SL36N30-A Wiring Diagram Wiring Diagram 92170015 92170016 Kϋhl Electronic Control Heat Pump model YL24N35-A Need to Configure it. Follow the steps below to configure Air Conditioner Message Remote Control MessageAir Conditioning Unit Display Remote Control Display Replacement Instructions Parts Section Parts Section Kühl & Kühl+ Small-Chassis 2012 Parts List SHROUD, SML Kühl & Kühl+ Medium-Chassis 2012 Parts List SHROUD, MED Kühl & Kühl+ Large-Chassis 2012 Parts List Deck LRG Addendum Schedule Table with Energy Saving ValuesRoom AIR Conditioners Limited Warranty AAA Refrigeration Service Customer Satisfaction and Quality AssuranceFriedrich AIR Conditioning CO

SM18N30*, SS10N10*, SS15N30*, SS12N10*, SS14N10* specifications

Friedrich air conditioners, particularly models SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30*, are renowned for their reliable performance, innovative technologies, and user-friendly features. Designed for both residential and commercial use, these units stand out due to their energy efficiency, advanced cooling capabilities, and versatile operation.

One of the standout features across these models is their energy efficiency. Equipped with high SEER (Seasonal Energy Efficiency Ratio) ratings, they help users save on energy costs while reducing their carbon footprint. Specifically, the SS14N10* and SS12N10* models excel in cooling efficiency, ensuring that the spaces they occupy remain comfortably cool even in the hottest conditions. This not only contributes to lower energy bills but also promotes environmental sustainability.

The cooling technologies integrated into these units include advanced inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand of a room. As a result, these air conditioners maintain desired temperatures with minimal fluctuations, ensuring optimal comfort and significant energy savings. Models like SS15N30* and SM18N30* are particularly stellar in maintaining efficiency even during peak usage hours.

Moreover, these air conditioners are equipped with multi-stage filtration systems that enhance indoor air quality. The filters effectively capture dust, allergens, and other pollutants, resulting in cleaner and healthier air for occupants. This is especially important for individuals with allergies or respiratory issues.

User-friendly controls add another layer of convenience. Many models incorporate smart technology allowing users to control the units via mobile apps or home automation systems. This feature enables remote operation, scheduling, and real-time monitoring, making it easier to manage climate conditions effectively.

In terms of design, models like SS10N10* prioritize aesthetics without compromising functionality. They feature sleek, modern designs that seamlessly integrate into various decors, whether in a home or an office. Additionally, quiet operation technology reduces noise levels during functionality, enhancing comfort, particularly in bedrooms or quiet office environments.

Overall, Friedrich’s SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30* models embody the brand's commitment to innovation and customer satisfaction. Their blend of energy efficiency, advanced cooling technology, air quality enhancement, and smart controls positions them as leaders in the air conditioning market, catering to diverse cooling needs while promoting a sustainable future.