Friedrich SS12N10* Locked Rotor Voltage L.R.V. Test, Single Phase Connections, Determine L.R.V

Page 46

COMPRESSOR CHECKS

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

Locked Rotor Voltage (L.R.V.) Test

Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition.

Single Phase Connections

Disconnect power from unit. Using a voltmeter, attach one lead of the meter to the run “R” terminal on the compressor and the other lead to the common “C” terminal of the com- pressor. Restore power to unit.

Determine L.R.V.

Start the compressor with the volt meter attached; then stop the unit. Attempt to restart the compressor within a couple of seconds and immediately read the voltage on the meter. The compressor under these conditions will not start and will usually kick out on overload within a few seconds since the pressures in the system will not have had time to equalize. Voltage should be at or above minimum voltage of 197 VAC, as specified on the rating plate. If less than minimum, check for cause of inadequate power supply; i.e., incorrect wire size, loose electrical connections, etc.

Amperage (L.R.A.) Test

The running amperage of the compressor is the most important of these readings. A running amperage higher than that indicated in the performance data indicates that a problem exists mechanically or electrically.

Single Phase Running and L.R.A. Test

NOTE: Consult the specification and performance section for running amperage. The L.R.A. can also be found on the rating plate.

Select the proper amperage scale and clamp the meter probe around the wire to the “C” terminal of the compressor.

Turn on the unit and read the running amperage on the meter. If the compressor does not start, the reading will indicate the locked rotor amperage (L.R.A.).

Overloads

The compressor is equipped with either an external or internal overload which senses both motor amperage and winding temperature. High motor temperature or amperage heats the overload causing it to open, breaking the common circuit within the compressor.

Heat generated within the compressor shell, usually due to recycling of the motor, is slow to dissipate. It may take anywhere from a few minutes to several hours for the overload to reset.

Checking the Overloads

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

WARNING

BURN HAZARD

Certain unit components operate at temperatures hot enough to cause burns.

Proper safety procedures must be followed, and proper protective clothing must be worn.

Failure to follow this warning could result in moderate to serious injury.

External Overloads

With power off, remove the leads from compressor terminals. If the compressor is hot, allow the overload to cool before starting check. Using an ohmmeter, test continuity across the terminals of the external overload. If you do not have continuity; this indicates that the overload is open and must be replaced.

Interrnal Overloads

Some model compressors are equipped with an internal overload. The overload is embedded in the motor windings to sense the winding temperature and/or current draw. The overload is connected in series with the common motor terminal.

Should the internal temperature and/or current draw become excessive, the contacts in the overload will open, turning off the compressor. The overload will automatically reset, but may require several hours before the heat is dissipated.

Checking the Internal Overload

1.With no power to unit, remove the leads from the compressor terminals.

2.Using an ohmmeter, test continuity between terminals C-S and C-R. If no continuity, the compressor overload is open and the compressor must be replaced.

45

Image 46
Contents Cool Only Heat PumpTable Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Repair Hazards Property Damage Hazards Components Identification IntroductionModel and Serial Number Location Unit Identification Specifications Refrigeration System Performance DataProper installation of seal gasket Keep the filter cleanUnit placement Provide good air flowElectric Shock Hazard Electrical DataFire Hazard Electrical Shock Hazard Kuhl Control Options FriedrichLink AdapterControl Panel and Display Identification Control Panel Operation Instructions Timer Schedule Button ºF ºC SelectControl Panel Lock DIM FunctionAlerts External Control StatusTo Turn On the Timer or Schedule Selected Timer or Schedule Options 1 or 2 SelectionTimer Start Time Timer SettingsSet theTimer Stop Time Timer on ScenariosTimer OFF Scenarios Timer Schedule Control BlockRemote Control Operation Remote Control Operation Unit Operation Front PanelElectronic Control Sequence of Operation Compressor OperationHeating Mode Control Operation Heat Control Heat Pump OnlyHeat Pump With Electric Heat Operation ConditionElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Using ModeRemoving the Front Cover Replacing the Indoor Coil Thermistor Swing OutAir flow direction adjustment Fresh air and exhaust controlCapacitor Connections Components TestingCapacitor Check with Capacitor Analyzer FAN MotorHeating Element Heat Pump Models Testing the Heating Element Electric Shock HazardHeating Element Drain PAN ValveUser Interface Control Board Refrigeration Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Refrigerant ChargingBurn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Reversing Valve Solenoid Coil Reversing Valve in Heating ModeTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Locked Rotor Voltage L.R.V. Test Single Phase ConnectionsSingle Phase Running and L.R.A. Test Determine L.R.VGround Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement High TemperaturesHigh Pressure Hazard Routine Maintenance Decorative Front Cover Sleeve / DrainClearances Filter assembly Frosting Heat pumps operate differentlyCondensation is normal NoisesDC-2 Drain Kit Part No If you require further assistanceOur specialists are able to assist you with Carbon Filter KitsSee codes chart on next Error Codes and Alarm Status Test Mode Temp JOB Name Techs Name Room AIR Conditioner Unit Performance Test Data SheetHOW is ALL of the INSTALLATION? Good BAD = SQ/CU/FTTroubleshooting Tips Problem Possible Cause Possible SolutionTroubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Heat / Cool only Room AIR Conditioners Troubleshooting Tips Heat Pump Room AIR Conditioners Trouble Shooting Tips Problem Possible Cause ActionSystem Cools When Heating is Desired YESNormal Function of Valve Malfunction of ValveElectronic Control Board Components Identification Procedure ContentsFriedrich Electronic Control KIT Friedrich Model Prefix Schematic Part NO. REV 92170013 Kϋhl Electronic Control Cool only Models SL36N30-A Wiring Diagram Wiring Diagram 92170015 92170016 Kϋhl Electronic Control Heat Pump model YL24N35-A Need to Configure it. Follow the steps below to configure Air Conditioner Message Remote Control MessageAir Conditioning Unit Display Remote Control Display Replacement Instructions Parts Section Parts Section Kühl & Kühl+ Small-Chassis 2012 Parts List SHROUD, SML Kühl & Kühl+ Medium-Chassis 2012 Parts List SHROUD, MED Kühl & Kühl+ Large-Chassis 2012 Parts List Deck LRG Addendum Schedule Table with Energy Saving ValuesRoom AIR Conditioners Limited Warranty AAA Refrigeration Service Customer Satisfaction and Quality AssuranceFriedrich AIR Conditioning CO

SM18N30*, SS10N10*, SS15N30*, SS12N10*, SS14N10* specifications

Friedrich air conditioners, particularly models SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30*, are renowned for their reliable performance, innovative technologies, and user-friendly features. Designed for both residential and commercial use, these units stand out due to their energy efficiency, advanced cooling capabilities, and versatile operation.

One of the standout features across these models is their energy efficiency. Equipped with high SEER (Seasonal Energy Efficiency Ratio) ratings, they help users save on energy costs while reducing their carbon footprint. Specifically, the SS14N10* and SS12N10* models excel in cooling efficiency, ensuring that the spaces they occupy remain comfortably cool even in the hottest conditions. This not only contributes to lower energy bills but also promotes environmental sustainability.

The cooling technologies integrated into these units include advanced inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand of a room. As a result, these air conditioners maintain desired temperatures with minimal fluctuations, ensuring optimal comfort and significant energy savings. Models like SS15N30* and SM18N30* are particularly stellar in maintaining efficiency even during peak usage hours.

Moreover, these air conditioners are equipped with multi-stage filtration systems that enhance indoor air quality. The filters effectively capture dust, allergens, and other pollutants, resulting in cleaner and healthier air for occupants. This is especially important for individuals with allergies or respiratory issues.

User-friendly controls add another layer of convenience. Many models incorporate smart technology allowing users to control the units via mobile apps or home automation systems. This feature enables remote operation, scheduling, and real-time monitoring, making it easier to manage climate conditions effectively.

In terms of design, models like SS10N10* prioritize aesthetics without compromising functionality. They feature sleek, modern designs that seamlessly integrate into various decors, whether in a home or an office. Additionally, quiet operation technology reduces noise levels during functionality, enhancing comfort, particularly in bedrooms or quiet office environments.

Overall, Friedrich’s SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30* models embody the brand's commitment to innovation and customer satisfaction. Their blend of energy efficiency, advanced cooling technology, air quality enhancement, and smart controls positions them as leaders in the air conditioning market, catering to diverse cooling needs while promoting a sustainable future.