Restricted Refrigerant System

Troubleshooting a restricted refrigerant system can be difficult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.

A partial restriction allows some of the refrigerant to circulate through the system.

With a complete restriction there is no circulation of refrigerant in the system.

Restricted refrigerant systems display the same symptoms as a “low-charge condition.”

When the unit is shut off, the gauges may equalize very slowly.

Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the

gauges will not equalize at all.

A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds

at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.

Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.

With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specifi cation. With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.

The following conditions are based primarily on a system in the cooling mode.

40

Image 41
Contents Heat Pump Cool OnlyTable Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Repair Hazards Property Damage Hazards Model and Serial Number Location IntroductionComponents Identification Unit Identification Refrigeration System Performance Data SpecificationsUnit placement Keep the filter cleanProper installation of seal gasket Provide good air flowFire Hazard Electrical DataElectric Shock Hazard Electrical Shock Hazard FriedrichLink Adapter Kuhl Control OptionsControl Panel and Display Identification Control Panel Operation Instructions ºF ºC Select Timer Schedule ButtonAlerts DIM FunctionControl Panel Lock External Control StatusTimer or Schedule Options 1 or 2 Selection To Turn On the Timer or Schedule SelectedTimer Settings Timer Start TimeTimer on Scenarios Set theTimer Stop TimeTimer Schedule Control Block Timer OFF ScenariosRemote Control Operation Remote Control Operation Front Panel Unit OperationCompressor Operation Electronic Control Sequence of OperationHeat Control Heat Pump Only Heating Mode Control OperationCondition Heat Pump With Electric Heat OperationElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Mode UsingRemoving the Front Cover Swing Out Replacing the Indoor Coil ThermistorFresh air and exhaust control Air flow direction adjustmentCapacitor Check with Capacitor Analyzer Components TestingCapacitor Connections FAN MotorHeating Element Testing the Heating Element Electric Shock HazardHeating Element Heat Pump Models Drain PAN ValveUser Interface Control Board Refrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRefrigerant Charging 410A Sealed Refrigeration System RepairsFreeze Hazard Method Of Charging / RepairsBurn Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckReversing Valve DESCRIPTION/OPERATION Reversing Valve in Heating Mode Testing the Reversing Valve Solenoid CoilExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Single Phase Running and L.R.A. Test Single Phase ConnectionsLocked Rotor Voltage L.R.V. Test Determine L.R.VChecking Compressor Efficiency Single Phase Resistance TestGround Test High Temperatures Recommended procedure for compressor replacementHigh Pressure Hazard Routine Maintenance Clearances Sleeve / DrainDecorative Front Cover Filter assembly Condensation is normal Heat pumps operate differentlyFrosting NoisesOur specialists are able to assist you with If you require further assistanceDC-2 Drain Kit Part No Carbon Filter KitsSee codes chart on next Error Codes and Alarm Status Test Mode Temp HOW is ALL of the INSTALLATION? Good BAD Room AIR Conditioner Unit Performance Test Data SheetJOB Name Techs Name = SQ/CU/FTProblem Possible Cause Possible Solution Troubleshooting TipsTroubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Heat / Cool only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause Action Heat Pump Room AIR Conditioners Trouble Shooting TipsYES System Cools When Heating is DesiredMalfunction of Valve Normal Function of ValveElectronic Control Board Components Identification Friedrich Electronic Control KIT Friedrich Model Prefix ContentsProcedure Schematic Part NO. REV 92170013 Kϋhl Electronic Control Cool only Models SL36N30-A Wiring Diagram Wiring Diagram 92170015 92170016 Kϋhl Electronic Control Heat Pump model YL24N35-A Air Conditioner Message Remote Control Message Need to Configure it. Follow the steps below to configureAir Conditioning Unit Display Remote Control Display Replacement Instructions Parts Section Parts Section Kühl & Kühl+ Small-Chassis 2012 Parts List SHROUD, SML Kühl & Kühl+ Medium-Chassis 2012 Parts List SHROUD, MED Kühl & Kühl+ Large-Chassis 2012 Parts List Deck LRG Schedule Table with Energy Saving Values AddendumRoom AIR Conditioners Limited Warranty Customer Satisfaction and Quality Assurance AAA Refrigeration ServiceFriedrich AIR Conditioning CO

SM18N30*, SS10N10*, SS15N30*, SS12N10*, SS14N10* specifications

Friedrich air conditioners, particularly models SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30*, are renowned for their reliable performance, innovative technologies, and user-friendly features. Designed for both residential and commercial use, these units stand out due to their energy efficiency, advanced cooling capabilities, and versatile operation.

One of the standout features across these models is their energy efficiency. Equipped with high SEER (Seasonal Energy Efficiency Ratio) ratings, they help users save on energy costs while reducing their carbon footprint. Specifically, the SS14N10* and SS12N10* models excel in cooling efficiency, ensuring that the spaces they occupy remain comfortably cool even in the hottest conditions. This not only contributes to lower energy bills but also promotes environmental sustainability.

The cooling technologies integrated into these units include advanced inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand of a room. As a result, these air conditioners maintain desired temperatures with minimal fluctuations, ensuring optimal comfort and significant energy savings. Models like SS15N30* and SM18N30* are particularly stellar in maintaining efficiency even during peak usage hours.

Moreover, these air conditioners are equipped with multi-stage filtration systems that enhance indoor air quality. The filters effectively capture dust, allergens, and other pollutants, resulting in cleaner and healthier air for occupants. This is especially important for individuals with allergies or respiratory issues.

User-friendly controls add another layer of convenience. Many models incorporate smart technology allowing users to control the units via mobile apps or home automation systems. This feature enables remote operation, scheduling, and real-time monitoring, making it easier to manage climate conditions effectively.

In terms of design, models like SS10N10* prioritize aesthetics without compromising functionality. They feature sleek, modern designs that seamlessly integrate into various decors, whether in a home or an office. Additionally, quiet operation technology reduces noise levels during functionality, enhancing comfort, particularly in bedrooms or quiet office environments.

Overall, Friedrich’s SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30* models embody the brand's commitment to innovation and customer satisfaction. Their blend of energy efficiency, advanced cooling technology, air quality enhancement, and smart controls positions them as leaders in the air conditioning market, catering to diverse cooling needs while promoting a sustainable future.