Friedrich SS12N10*, SS14N10*, SS15N30*, SS10N10*, SM18N30* service manual Electrical Shock Hazard

Page 11

WARNING

Electrical Shock Hazard

Make sure your electrical receptacle has the same configuration as your air conditioner’s plug. If different, consult a Licensed Electrician.

Do not use plug adapters.

Do not use an extension cord. Do not remove ground prong.

Always plug into a grounded 3 prong oulet. Failure to follow these instructions can result in death, fire, or electrical shock.

If you have fuses, they should be of the time delay type. Before you install or relocate this unit, be sure that the amperage rating of the circuit breaker or time delay fuse does not exceed the amp rating listed in Table 1.

The cord provided will carry the proper amount of electrical power to the unit; an extension cord may not.

Proper grounding must be maintained at all times. Two prong receptacles

The grounded receptacle should meet all national and local codes and ordinances. You must use the three prong plug furnished with the air conditioner. Under no circumstances should you remove the ground prong from the plug.

NOTICE

Do not use the LCDI device as an ON/OFF switch.

Failure to adhere to this precaution may cause premature equipment malfunction.

Once plugged in, the unit will operate normally without the need to reset the LCDI device. If the LCDI device fails to trip when tested or if the power supply cord is damaged, it must be replaced with a new power supply cord from the manufacturer. Contact our Technical Assistance Line at (800) 541-6645. To expedite service, please have your model number available.

Table 1.

 

CIRCUIT RATING

REQUIRED

 

OR TIME DELAY

WALL

MODEL

FUSE

RECEPTACLE

 

AMP

VOLT

NEMA

 

 

NO.

 

 

 

 

 

SS08N10, SS10N10,

 

 

 

 

SS12N10, SS14N10,

15

125

5-15R

 

SM15N10,YS10M10

 

 

 

 

SS12N30, SS15N30,

15

250

6-15R

 

SM18N30, SM21N30

 

SL22N30

 

 

 

 

SL24N30, SL28N30,

 

 

 

 

ES12N33, ES15N33,

20

250

6-20R

 

YS12N33

 

 

 

 

 

 

 

 

 

SL36N30, EM18N34,

 

 

 

 

EL36N35, EM24N34,

30

250

6-30R

 

YM18N34, YL24N35

 

 

 

 

 

 

 

 

 

All Friedrich room air conditioners are shipped from the factory with a Leakage Current Detection Interrupter (LCDI) equipped power cord. The LCDI device on the end of the cord meets the UL and NEC requirements for cord connected air conditioners.

To test your power supply cord:

1.Plug power supply cord into a grounded 3 prong outlet.

2.Press RESET (See Figure 1).

3.Press TEST, listen for click; the RESET button trips and pops out.

4.Press and release RESET (Listen for click; RESET button latches and remains in). The power cord is ready for use.

Note: in case of power failure, unit will resume operation according to the last input settings.

Figure 1

RESET TEST

WARNING

TEST BEFORE EACH USE

1.PRESS RESET BUTTON

2.PLUG LCDI INTO POWER RECEPTACLE

3.PRESS TEST BUTTON, RESET BUTTON SHOULD

POP UP

4.PRESS TEST BUTTON, FOR USE

DO NOT USE IF ABOVE TEST

FAILS

WHEN GREEN LIGHT IS ON

IT IS WORKING PROPERLY

TEST

RESET

WARNING

TEST BEFORE EACH USE

1.PRESS RESET BUTTON

2.PLUG LCDI INTO POWER RECEPTACLE

3.PRESS TEST BUTTON, RESET BUTTON SHOULD POP UP

4.PRESS TEST BUTTON, FOR USE

DO NOT USE IF ABOVE TEST FAILS

WHEN GREEN LIGHT IS ON IT IS WORKING PROPERLY

15/20A LCDI Device

30A LCDI Device

FRR001

10

Image 11
Contents Heat Pump Cool OnlyTable Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Repair Hazards Property Damage Hazards Model and Serial Number Location IntroductionComponents Identification Unit Identification Refrigeration System Performance Data SpecificationsProvide good air flow Keep the filter cleanUnit placement Proper installation of seal gasketFire Hazard Electrical DataElectric Shock Hazard Electrical Shock Hazard FriedrichLink Adapter Kuhl Control OptionsControl Panel and Display Identification Control Panel Operation Instructions ºF ºC Select Timer Schedule ButtonExternal Control Status DIM FunctionAlerts Control Panel LockTimer or Schedule Options 1 or 2 Selection To Turn On the Timer or Schedule SelectedTimer Settings Timer Start TimeTimer on Scenarios Set theTimer Stop TimeTimer Schedule Control Block Timer OFF ScenariosRemote Control Operation Remote Control Operation Front Panel Unit OperationCompressor Operation Electronic Control Sequence of OperationHeat Control Heat Pump Only Heating Mode Control OperationCondition Heat Pump With Electric Heat OperationElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Mode UsingRemoving the Front Cover Swing Out Replacing the Indoor Coil ThermistorFresh air and exhaust control Air flow direction adjustmentFAN Motor Components TestingCapacitor Check with Capacitor Analyzer Capacitor ConnectionsDrain PAN Valve Testing the Heating Element Electric Shock HazardHeating Element Heating Element Heat Pump ModelsUser Interface Control Board Refrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRefrigerant Charging 410A Sealed Refrigeration System RepairsFreeze Hazard Method Of Charging / RepairsBurn Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckReversing Valve DESCRIPTION/OPERATION Reversing Valve in Heating Mode Testing the Reversing Valve Solenoid CoilExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Determine L.R.V Single Phase ConnectionsSingle Phase Running and L.R.A. Test Locked Rotor Voltage L.R.V. TestChecking Compressor Efficiency Single Phase Resistance TestGround Test High Temperatures Recommended procedure for compressor replacementHigh Pressure Hazard Routine Maintenance Clearances Sleeve / DrainDecorative Front Cover Filter assembly Noises Heat pumps operate differentlyCondensation is normal FrostingCarbon Filter Kits If you require further assistanceOur specialists are able to assist you with DC-2 Drain Kit Part NoSee codes chart on next Error Codes and Alarm Status Test Mode Temp = SQ/CU/FT Room AIR Conditioner Unit Performance Test Data SheetHOW is ALL of the INSTALLATION? Good BAD JOB Name Techs NameProblem Possible Cause Possible Solution Troubleshooting TipsTroubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Heat / Cool only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause Action Heat Pump Room AIR Conditioners Trouble Shooting TipsYES System Cools When Heating is DesiredMalfunction of Valve Normal Function of ValveElectronic Control Board Components Identification Friedrich Electronic Control KIT Friedrich Model Prefix ContentsProcedure Schematic Part NO. REV 92170013 Kϋhl Electronic Control Cool only Models SL36N30-A Wiring Diagram Wiring Diagram 92170015 92170016 Kϋhl Electronic Control Heat Pump model YL24N35-A Air Conditioner Message Remote Control Message Need to Configure it. Follow the steps below to configureAir Conditioning Unit Display Remote Control Display Replacement Instructions Parts Section Parts Section Kühl & Kühl+ Small-Chassis 2012 Parts List SHROUD, SML Kühl & Kühl+ Medium-Chassis 2012 Parts List SHROUD, MED Kühl & Kühl+ Large-Chassis 2012 Parts List Deck LRG Schedule Table with Energy Saving Values AddendumRoom AIR Conditioners Limited Warranty Customer Satisfaction and Quality Assurance AAA Refrigeration ServiceFriedrich AIR Conditioning CO

SM18N30*, SS10N10*, SS15N30*, SS12N10*, SS14N10* specifications

Friedrich air conditioners, particularly models SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30*, are renowned for their reliable performance, innovative technologies, and user-friendly features. Designed for both residential and commercial use, these units stand out due to their energy efficiency, advanced cooling capabilities, and versatile operation.

One of the standout features across these models is their energy efficiency. Equipped with high SEER (Seasonal Energy Efficiency Ratio) ratings, they help users save on energy costs while reducing their carbon footprint. Specifically, the SS14N10* and SS12N10* models excel in cooling efficiency, ensuring that the spaces they occupy remain comfortably cool even in the hottest conditions. This not only contributes to lower energy bills but also promotes environmental sustainability.

The cooling technologies integrated into these units include advanced inverter technology. This feature allows the compressor to adjust its speed according to the cooling demand of a room. As a result, these air conditioners maintain desired temperatures with minimal fluctuations, ensuring optimal comfort and significant energy savings. Models like SS15N30* and SM18N30* are particularly stellar in maintaining efficiency even during peak usage hours.

Moreover, these air conditioners are equipped with multi-stage filtration systems that enhance indoor air quality. The filters effectively capture dust, allergens, and other pollutants, resulting in cleaner and healthier air for occupants. This is especially important for individuals with allergies or respiratory issues.

User-friendly controls add another layer of convenience. Many models incorporate smart technology allowing users to control the units via mobile apps or home automation systems. This feature enables remote operation, scheduling, and real-time monitoring, making it easier to manage climate conditions effectively.

In terms of design, models like SS10N10* prioritize aesthetics without compromising functionality. They feature sleek, modern designs that seamlessly integrate into various decors, whether in a home or an office. Additionally, quiet operation technology reduces noise levels during functionality, enhancing comfort, particularly in bedrooms or quiet office environments.

Overall, Friedrich’s SS14N10*, SS12N10*, SS15N30*, SS10N10*, and SM18N30* models embody the brand's commitment to innovation and customer satisfaction. Their blend of energy efficiency, advanced cooling technology, air quality enhancement, and smart controls positions them as leaders in the air conditioning market, catering to diverse cooling needs while promoting a sustainable future.