HEAT PUMP ROOM AIR CONDITIONERS: TROUBLE SHOOTING TIPS

REFRIGERANT SYSTEM DIAGNOSIS - HEATING CYCLE

LOW SUCTION PRESSURE HIGH SUCTION PRESSURE

 

 

 

 

 

Low Airflow

 

Outdoor Ambient Too High

Across Outdoor Coil

 

for Operation in Heating

 

 

 

 

 

 

 

 

 

 

Refrigerant System

 

Reversing Valve not

Restriction

 

Fully Seated

 

 

 

 

 

 

 

 

 

 

Undercharged

 

Overcharged

 

 

 

 

 

 

 

 

 

 

Moisture in System

 

Defective Compressor

 

 

 

 

 

LOW HEAD PRESSURE

Refrigerant System

Restriction

Reversing Valve not Fully Seated

Undercharged

Defective Compressor

HIGH HEAD PRESSURE

Outdoor Ambient Too High For Operation In Heating

Low Airflow Across

Indoor Coil

Overcharged

Noncondensables (air)

in System

ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP

HEAT PUMP

SYSTEM COOLS WHEN

HEATING IS DESIRED.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is Line Voltage

 

 

 

Is the Selector Switch

Present at the Solenoid

NO

 

Set for Heat?

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the Solenoid Coil Good?

 

 

 

Replace the Solenoid Coil

NO

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reversing Valve Stuck

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the Reversing Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

67

Image 68 Contents
Cool Only Heat PumpTable Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Repair Hazards Property Damage Hazards Model and Serial Number Location IntroductionComponents Identification Unit Identification Specifications Refrigeration System Performance DataKeep the filter clean Unit placementProper installation of seal gasket Provide good air flowFire Hazard Electrical DataElectric Shock Hazard Electrical Shock Hazard Kuhl Control Options FriedrichLink AdapterControl Panel and Display Identification Control Panel Operation Instructions Timer Schedule Button ºF ºC SelectDIM Function AlertsControl Panel Lock External Control StatusTo Turn On the Timer or Schedule Selected Timer or Schedule Options 1 or 2 SelectionTimer Start Time Timer SettingsSet theTimer Stop Time Timer on ScenariosTimer OFF Scenarios Timer Schedule Control BlockRemote Control Operation Remote Control Operation Unit Operation Front PanelElectronic Control Sequence of Operation Compressor OperationHeating Mode Control Operation Heat Control Heat Pump OnlyHeat Pump With Electric Heat Operation ConditionElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Using ModeRemoving the Front Cover Replacing the Indoor Coil Thermistor Swing OutAir flow direction adjustment Fresh air and exhaust controlComponents Testing Capacitor Check with Capacitor AnalyzerCapacitor Connections FAN MotorTesting the Heating Element Electric Shock Hazard Heating ElementHeating Element Heat Pump Models Drain PAN ValveUser Interface Control Board Refrigeration Sequence of Operation 410A Sealed System Repair Considerations Refrigeration system under high pressure410A Sealed Refrigeration System Repairs Refrigerant ChargingFreeze Hazard Method Of Charging / RepairsBurn Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Reversing Valve Solenoid Coil Reversing Valve in Heating ModeExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Single Phase Connections Single Phase Running and L.R.A. TestLocked Rotor Voltage L.R.V. Test Determine L.R.VChecking Compressor Efficiency Single Phase Resistance TestGround Test Recommended procedure for compressor replacement High TemperaturesHigh Pressure Hazard Routine Maintenance Clearances Sleeve / DrainDecorative Front Cover Filter assembly Heat pumps operate differently Condensation is normalFrosting NoisesIf you require further assistance Our specialists are able to assist you withDC-2 Drain Kit Part No Carbon Filter KitsSee codes chart on next Error Codes and Alarm Status Test Mode Temp Room AIR Conditioner Unit Performance Test Data Sheet HOW is ALL of the INSTALLATION? Good BADJOB Name Techs Name = SQ/CU/FTTroubleshooting Tips Problem Possible Cause Possible SolutionTroubleshooting Tips Cooling only Room AIR Conditioners Troubleshooting Tips Replace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Heat / Cool only Room AIR Conditioners Troubleshooting Tips Heat Pump Room AIR Conditioners Trouble Shooting Tips Problem Possible Cause ActionSystem Cools When Heating is Desired YESNormal Function of Valve Malfunction of ValveElectronic Control Board Components Identification Friedrich Electronic Control KIT Friedrich Model Prefix ContentsProcedure Schematic Part NO. REV 92170013 Kϋhl Electronic Control Cool only Models SL36N30-A Wiring Diagram Wiring Diagram 92170015 92170016 Kϋhl Electronic Control Heat Pump model YL24N35-A Need to Configure it. Follow the steps below to configure Air Conditioner Message Remote Control MessageAir Conditioning Unit Display Remote Control Display Replacement Instructions Parts Section Parts Section Kühl & Kühl+ Small-Chassis 2012 Parts List SHROUD, SML Kühl & Kühl+ Medium-Chassis 2012 Parts List SHROUD, MED Kühl & Kühl+ Large-Chassis 2012 Parts List Deck LRG Addendum Schedule Table with Energy Saving ValuesRoom AIR Conditioners Limited Warranty AAA Refrigeration Service Customer Satisfaction and Quality AssuranceFriedrich AIR Conditioning CO