D-4

MAINTENANCE

D-4

 

 

 

GFCI RECEPTACLE TESTING AND RESET-

TING PROCEDURE

The GFCI receptacle should be properly tested at least once every month or whenever it is tripped. To properly test and reset the GFCI receptacle:

If the receptacle has tripped, first carefully remove any load and check it for damage.

If the equipment has been shut down, it must be restarted.

The equipment needs to be operating at high idle speed and any necessary adjustments made on the control panel so that the equipment is providing at least 80 volts to the receptacle input terminals.

The circuit breaker for this receptacle must not be tripped. Reset if necessary.

Push the "Reset" button located on the GFCI recep- tacle. This will assure normal GFCI operation.

Plug a night-light (with an "ON/OFF" switch) or other product (such as a lamp) into the GFCI receptacle and turn the product "ON".

Push the "Test" button located on the GFCI recepta- cle. The night-light or other product should go "OFF".

Push the "Reset" button, again. The light or other product should go "ON" again.

If the light or other product remains "ON" when the "Test" button is pushed, the GFCI is not working prop- erly or has been incorrectly installed (miswired). If your GFCI is not working properly, contact a qualified, certified electrician who can assess the situation, rewire the GFCI if necessary or replace the device.

WELDMARK 225

Image 28
Contents Weldmark Safety California Proposition 65 WarningsElectric Shock can kill Cylinder may explode if damaged Précautions DE Sûreté Sûreté Pour Soudage a L’ArcThank You Table of Contents Height Width Depth Weight InstallationWeldmark Specifications Installation Instructions Machine GroundingSpark Arrester LiftingPRE-OPERATION Service Welding Output CablesTotal Combined Length Electrode and Work Cables GasolineConnection of Wire Feeders Angle of OperationHigh Altitude Operation Location / VentilationAdditional Safety Precautions Auxiliary PowerInstructions Connection of K930- TIG Module to the WeldmarkDuplex Receptacles Motor StartingThese Devices Without Simultaneous Welding and Power Auxiliary Power While WeldingStandby Power Connections Connection of Weldmark 225 to Premises Wiring Design Features Other FeaturesEngine Features Operation20 H.P. Command Polarity SwitchRange Switch Control SwitchBREAK-IN Period Stopping the EngineWire Feed Welding Processes Constant Voltage Welding ProcessDuty Cycle Stick Constant Current WeldingHigh Accessories K1745-1 Single GAS Cylinder HolderWire Feed Recommended EquipmentStick TIGMaintenance Safety PrecautionsRoutine Maintenance Engine OIL ChangeOIL Filter Change RangerEngine Adjustments Gfci Receptacle Testing and Reset Ting Procedure Troubleshooting HOW to USE Troubleshooting GuideTroubleshooting Troubleshooting Weldmark 225 Wiring Diagram Code DiagramsWeldmark 225 / LN-25 Across the ARC Connection Diagram Connection of Weldmark 225 to LN-7 & K240 Contactor KITM17215-2 30-98E Precaucion Warnung Manufactured by Lincoln Electric Company