Lincoln Electric IM819-B 120/240 Volt Dual Voltage Receptacle, Duplex Receptacles, Motor Starting

Page 13

A-6

INSTALLATION

A-6

AUXILIARY POWER

The RANGER 10,000 can provide up to 9,000 watts of 120/240 volts AC, single phase 60Hz power for con- tinuous use, and up to 10,000 watts of 120/240 volts AC, single phase 60Hz power peak use. The front of the machine includes three receptacles for connecting the AC power plugs; one 50 amp 120/240 volt NEMA 14-50R receptacle and two 20 amp 120 volt NEMA 5- 20R receptacles. Output voltage is within +/-10% at all loads up to rated capacity.

CAUTION

Do not connect any plugs that connect to the power receptacles in parallel.

------------------------------------------------------------------------

Start the engine and set the IDLERcontrol switch to the desired operating mode. Set the CONTROLto

10.Voltage is now correct at the receptacles for auxil- iary power.

120/240 VOLT DUAL VOLTAGE RECEPTACLE

The 120/240 volt receptacle can supply up to 38 amps of 240 volt power to a two wire circuit, up to 38 amps of 120 volts power from each side of a three wire cir- cuit (up to 76 amps total). Do not connect the 120 volt circuits in parallel. Current sensing for the automatic idle feature is only in one leg of the three wire circuit as shown in the following column.

GND

120 V

240 V

120 V*

*Current Sensing for Automatic Idle. (Receptacle viewed from front of Machine)

120 V DUPLEX RECEPTACLES

The 120V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs.

The current rating of any plug used with the system must be at least equal to the current load through the associated receptacle.

MOTOR STARTING

Most 1.5 hp AC single phase motors can be started if there is no load on the motor or other load connected to the machine, since the full load current rating of a 1.5 hp motor is approximately 20 amperes (10 amperes for 240 volt motors). The motor may be run at full load when plugged into only one side of the duplex receptacle. Larger motors through 2 hp can be run provided the receptacle rating as previously stated is not exceeded. This may necessitate 240V operation only.

RANGER 10,000 Extension Cord Length Recommendations

(Use the shortest length extension cord possible sized per the following table.)

Current

Voltage

Load

 

 

Maximum Allowable Cord Length in ft. (m) for Conductor Size

 

 

(Amps)

Volts

(Watts)

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG

15

120

1800

30

(9)

40

(12)

75

(23)

125

(38)

175

(53)

300

(91)

20

120

2400

 

 

30

(9)

50

(15)

88

(27)

138

(42)

225

(69)

15

240

3600

60

(18)

75

(23)

150

(46)

225

(69)

350

(107)

600

(183)

20

240

4800

 

 

60

(18)

100

(30)

175

(53)

275

(84)

450

(137)

38

240

9000

 

 

 

 

50

(15)

90

(27)

150

(46)

225

(69)

 

 

 

 

Conductor size is based on maximum 2.0% voltage drop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGER 10,000

Image 13
Contents Ranger 10,000 Safety Electric Shock can kill Cylinder may explode if damaged Précautions DE Sûreté Thank You Table of Contents Height Width Depth Weight InstallationSafety Precautions Fuel Vehicle Mounting OIL Falling AWGConnection of K930-2 TIG Module to the Ranger 10,000 Connection of the LN-25 to the RangerWelder Output Duplex Receptacles 120/240 Volt Dual Voltage ReceptacleMotor Starting These Devices Without Additional Resistive Type Loads Electrical Device USE with the Ranger 10,000Not USE These Devices With a Ranger 10,000 Simultaneous Welding and Power Auxiliary Power While WeldingStandby Power Connections Connection of Ranger 10,000 to Premises Wiring InstallationEngine Switch Safety PrecautionsOperation Range Switch Polarity SwitchRanger 10,000 Approximate Fuel Consumption Control DialBREAK-IN Period STARTING/SHUTDOWN InstructionsStarting the Engine Stopping the EngineWelding Process Wire Feed Welding Processes Constant VoltageStick Constant Current Welding TIG Constant Current WeldingStick Auto K1745-1 GAS Cylinder Holder AccessoriesStick Wire FeedTIG Welding Plasma CuttingEngine OIL Change MaintenanceEngine OIL Refill Capacities Kohler HondaOIL Filter Change AIR Cleaner and Other MaintenanceBattery Engine AdjustmentsOverspeed is Hazardous Slip RingsHOW to USE Troubleshooting Guide TroubleshootingTroubleshooting Troubleshooting Ranger 10,000 Kohler CSA Wiring Diagram for DiagramsRanger 10,000 Honda Wiring Diagram for Code M20431 Engine Welder Kohler , Honda and Robin / Subaru Precaucion Warnung