Lincoln Electric IM826-A manual Remote Control, Output, Auxiliary Power Receptacles

Page 14

A-6

INSTALLATION

A-6

REMOTE CONTROL

OUTPUT

The AIR VANTAGE® 500 is equipped with a 6-pin and a 14-pin connector. The 6-pin connector is for connecting the K857 or K857-1 Remote Control or for TIG welding, the K870 foot Amptrol or the K936-2 hand Amptrol. When in the CC-STICK, DOWNHILL PIPE, or CV-WIRE modes and when a remote control is connected to the 6-pin Connector, the auto-sensing circuit automatically switches the OUTPUT control from control at the welder to remote control.

When in TOUCH START TIG mode and when a Amptrol is connected to the 6-Pin Connector, the OUTPUT dial is used to set the maximum current range of the CURRENT CONTROL of the Amptrol.

When in the DOWNHILL PIPE mode and when a remote control is connected to the 6-Pin or 14-Pin connector, the output control is used to set the maximum current range of the remote.

EXAMPLE: When the OUTPUT CONTROL on the welder is set to 200 amps the current range on the remote control will be 40-200 amps, rather than the full 40-300 amps. Any current range that is less than the full range provides finer current resolution for more fine tuning of the output.

The 14-pin connector is used to directly connect a wire feeder control cable. In the CV-WIRE mode, when the control cable is connected to the 14-pin connector, the auto-sensing circuit automatically makes the Output Control inactive and the wire feeder voltage control active

WARNING

NOTE: When a wire feeder with a built in welding voltage control is connected to the 14-pin connector, do not connect anything to the 6-pin connector.

--------------------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

Start the engine and set the “IDLER” control switch to the “High Idle” mode. Voltage is now correct at the receptacles for auxiliary power. This must be done before a tripped GFCI receptacle can be reset properly. See the MAINTENANCE section for detailed information on testing and resetting the GFCI receptacle.

The auxiliary power capacity of the AIR VANTAGE® 500 is 12,000 watts of 60 Hz, single phase or 20,000 watts of 60Hz, three phase power. The auxiliary power capacity rating in watts is equivalent to volt-amperes at unity power factor. The maximum permissible current of the 240 VAC output is 50 A. The 240 VAC single phase output can be split to provide two separate 120 VAC outputs with a maximum permissible current of 50 A per output to two separate 120 VAC branch circuits. The output voltage is within ± 10% at all loads up to rated capacity.

The AIR VANTAGE® 500 has two 20 Amp-120VAC single phase(5-20R) GFCI duplex receptacles, one 50 Amp-120/240 single phase VAC (14-50R) receptacle and one 240VAC three phase (15-50R) receptacle. The auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

A 240VAC 3 phase plug is provided loose with the machine.

NOTE: The two 120V GFCI receptacles and the two 120 volt circuits of the 120/240V receptacle are connected to different phases and can not be paralleled.

STANDBY POWER CONNECTIONS

The AIR VANTAGE® 500 is suitable for temporary, standby or emergency power using the engine manufacturer’s recommended maintenance schedule.

The AIR VANTAGE® 500 can be permanently installed as a standby power unit for 240 volt-3 wire, 50 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes. The following information can be used as a guide by the electrician for most applications. Refer to the connection diagram shown in Figure A.2.

1.Install the double-pole, double-throw switch between the power company meter and the premises disconnect.

Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.

AIR VANTAGE® 500 CUMMINS

Image 14
Contents AIR Vantage 500 Cummins Safety California Proposition 65 WarningsElectric Shock can kill Welding and Cutting Sparks can Cause fire or explosion Précautions DE Sûreté Sûreté Pour Soudage a L’ArcThank You Customer Assistance PolicyTable of Contents Vii AIR Vantage 500 Cummins InstallationTechnical Specifications AIR Vantage 500 Cummins K2325-1 Storing Safety PrecautionsLocation / Ventilation Stacking High Altitude Operation High Temperature Operation Lifting TowingPRE-OPERATION Engine and Compressor Service Welding Terminals Standby Power Connections Remote ControlAuxiliary Power Receptacles OutputCompany Connection of LN-15 to the AIR Vantage Connection of Lincoln Electric Wire FeedersConnection of LN-7, LN-8 or LN-742 to AIR Vantage Connection of the LN-25 to the AIR Vantage Terminals onGeneral Description Safety InstructionsOperation Controls and Settings 2OPERATIONB-2OIL Pressure Gauge Battery Charging LightIdler Switch Engine ProtectionAuxiliary Power Controls Engine Operation BREAK-IN Period Welder OperationAIR Vantage 500 Settings When Using K930-2 TIG Module For Tungsten ElectrodesAuxiliary Power Operation Weld Phase Both 1 and 3 Phase Amps Watts PlusTIG Options AccessoriesOptional Field Installed Accessories K2641-2 Four Wheeled Steerable Yard TrailerEngine Maintenance MaintenanceRoutine and Periodic Maintenance Service Instructions & Installation Tips 2MAINTENANCED-2Cooling System Battery HandlingFuel Filters Welder / Generator Maintenance Troubleshooting HOW to USE Troubleshooting GuideCourse of Action SymptomsRecommended Function Problems Troubleshooting Diagrams 2DIAGRAMSF-2 Connection Diagram AIR Vantage 500 CumminsCommander / K867 / K775 / LN-7 Connection Diagram 4DIAGRAMSF-4 5DIAGRAMSF-5 Connection Diagram Cummins7DIAGRAMSF-7 8DIAGRAMSF-8 9DIAGRAMSF-9 10DIAGRAMSF-10 11DIAGRAMSF-11 12DIAGRAMSF-12 Dimension Print M18962-4Ne laissez ni la peau ni des GroundMojada Inflammable Votre corpsRespiración Alimentación de poder de la Guardas quitadas Keep your head out of fumesGuards off Humos. Utilice ventilación o Servicio Aspiración para gases