INSTALLATION | ||
|
|
|
GND
115 V
230 V
115 V*
*Current Sensing for Automatic Idle. (Receptacle viewed from front of Machine)
115 V Duplex Receptacles
The 115V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs.
The current rating of any plug used with the system must be at least equal to the current load through the associated receptacle (Refer to Tables I and II). Do not attempt to connect power receptacles in parallel.
Motor Starting
Most 1.5 hp AC single phase motors can be started if there is no load on the motor or other load connected to the machine, since the full load current rating of a
1.5hp motor is approximately 20 amperes (10 amperes for 230 volt motors). The motor may be run at full load when plugged into only one side of the duplex receptacle. Larger motors through 2 hp can be run provided the receptacle rating as previously stated is not exceeded. This may necessitate 230V opera- tion only.
TABLE I Maximum Current Draw from 115V Duplex Receptacles - No Welding
| Load From |
| |||||||
| 115V/230V |
|
|
|
| CSA Machines |
| ||
| Dual Voltage | Each Half of |
| Total From | Each Half of |
| Total From |
| |
|
|
|
| ||||||
| Receptacle | Each 115V |
| Both 115V | Each 115V |
| Both 115V |
| |
|
|
| Duplex |
| Duplexes | Duplex |
| Duplexes |
|
| 0 |
| 20* |
| 70 | 15 |
| 60 |
|
| 1.1 KW | 20* |
| 60 | 15 |
| 60 |
| |
| 3.4 KW | 20* |
| 40 | 15 |
| 40 |
| |
| 5.7 KW | 20* |
| 20 | 15 |
| 20 |
| |
| 8.0 KW | 0 |
| 0 | 0 |
| 0 |
| |
|
|
|
|
|
|
|
|
|
|
*NEMA
TABLE II Maximum Current Draw from 115V GFCI Duplex Receptacles - No Welding
| Load From |
| |||||||
| 115V/230V |
|
|
|
| CSA Machines |
| ||
| Dual Voltage | Each Half of |
| Total From | Each Half of |
| Total From |
| |
|
|
|
| ||||||
| Receptacle | Each 115V |
| Both 115V | Each 115V |
| Both 115V |
| |
|
|
| Duplex |
| Duplexes | Duplex |
| Duplexes |
|
| 0 |
| 15 |
| 40* | 15 |
| 30** |
|
| 1.1 KW | 15 |
| 40* | 15 |
| 30** |
| |
| 3.4 KW | 15 |
| 40* | 15 |
| 30** |
| |
| 5.7 KW | 15 |
| 20* | 15 |
| 20** |
| |
| 8.0 KW | 0 |
| 0 | 0 |
| 0 |
| |
|
|
|
|
|
|
|
|
|
|
*Maximum current draw from each 115V GFCI Duplex is 20 amps *Maximum current draw from each 115V GFCI Duplex is 15 amps