Friedrich 2003 Thermal Overload External, Winding Test, Checking Compressor Efficiency

Page 14

COMPONENTS:

OPERATION & TESTING

WARNING

DISCONNECT ELECTRICAL POWER TO

UNIT BEFORE SERVICING OR TESTING

COMPRESSORS

Compressors are single phase, 115 or 230/208 volt, depending on the model unit. All compressor motors are permanent split capacitor type using only a running capacitor across the start and run terminal.

All compressors are internally spring mounted and externally mounted on rubber isolators.

WINDING TEST

Remove compressor terminal box cover and disconnect wires from terminals. Using an ohmmeter, check continuity across the following: (See Figure 1)

1.Terminal "C" and "S" - no continuity - open winding - replace compressor.

2.Terminal "C" and "R" - no continuity - open winding - replace compressor.

3.Terminal "R" and "S" - no continuity - open winding - replace compressor.

Figure 1

GROUND TEST

Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good con- nection is a must) and the other probe in turn to each com- pressor terminal (see Figure 2.) If a reading is obtained, the compressor is grounded and must be replaced.

Figure 2

Typical Ground Test

CHECKING COMPRESSOR EFFICIENCY

The reason for compressor inefficiency is normally due to broken or damaged suction and/or discharge valves, reducing the ability of the compressor to pump refrigerant gas.

This condition can be checked as follows:

1.Install a piercing valve on the suction and discharge or liquid process tube.

2.Attach gauges to the high and low sides of the system.

3.Start the system and run a “cooling or heating performance test.”

If test shows:

A.Below normal high side pressure

B.Above normal low side pressure

C.Low temperature difference across coil

The compressor valves are faulty - replace the compressor.

THERMAL OVERLOAD (External)

Some compressors are equipped with an external overload which is located in the compressor terminal box adjacent to the compressor body (See Figure 3.)

The overload is wired in series with the common motor terminal. The overload senses both major amperage and compressor temperature. High motor temperature or amperage heats the disc causing it to open and break the circuit to the common motor terminal.

Figure 3- External Overload

14

Image 14
Contents 2003 Table of Contents 00001 1st Digit FunctionRAC Serial Number Identification Guide Page Data Evaporator AIR Operating Electrical Breaker Pressures Ratings Refrig Fuse Performance Evaporator AIR Operating Electrical Breaker Data SS10J10AR-A TEMP. DEG. F Pressures Ratings Heating SC06H10EAmps WY09A33F-A WY12A33F-A HeatingBtuh Refrigeration System Sequence of Operation Breaker Wire SizeFuse/Circuit GroundingChecking Compressor Efficiency Thermal Overload ExternalWinding Test Checking the Internal Overload Terminal Overload TestTerminal Overload Internal FAN MotorResistor EQ Model Only See Figure System Control Panel KQ Models Only- See FigureSystem Control Panel System Control Panel YQ Model Only System Control Switch WE & WY Models See Figure System Control Switch TestSystem Control Switch KS, SS, KM, SM, SL Models See Figure System Control Panel See FigureSystem Control Switch Heat Pump & Electric Heat Models See FigureTo Adjust FAN Speed To SET Mode of OperationTo Adjust Temperature Smart Center Electronic Control CenterTesting the Electronic Control Error Code Listings To SET the TimerTesting the Electronic Control To SET Hour ClockThermostat YQ Model Only See Figure TestThermostat SQ & KQ Models See Figure Thermostat Models ES, YS, EM, YM, EL, YL See FigureThermostat Bulb Location Thermostat AdjustmentDefrost Thermostat Heat Pump Models Only Capacitor Test Defrost Bulb Location Heat Pump Models OnlyCAPACITOR, RUN See Figure Check Valve Operation Heat Pumps Reversing Valve See FigureTo Test Testing Reversing ValveSolenoid Coil Heat Pump Models Only See Figure Sealed Refrigeration System Repairs VALVE, Drain PAN See FigureHeating Element See Figure Equipment RequiredRotary Compressor Special Troubleshooting and Service Hermetic Component ReplacementSpecial Procedure in the Case Compressor Motor Burnout Equipment Must be CapableUndercharged Refrigerant Systems Method of ChargingOvercharged Refrigerant Systems Restricted Refrigerant System Routine Maintenance Troubleshooting Touch Test Chart To Service Reversing Valves Troubleshooting Cooling Problem To CorrectProblem Possible Cause To Correct Cycles Problem Possible Cause To Correct Troubleshooting Heating Heat pumps Problem Possible Cause To Correct Off and the electric element is energized Troubleshooting Heating Cooling/Electric Models Troubleshooting Chart Cooling System Cools When Heating is Desired YESModels SQ06J10B-B, SQ06J10B-A, SQ08J10C-A, SQ08J10D-A Models KQ08J10B-1, KQ08J10B-A, KQ08J10C-A Schematic Model YQ06J10B-AModel SC06H10D 619-405-06 SL28J30B-A, SL35J30-A, SL35J30-B AlternateConductor Or Brown RED Blue To Capacitor Bracket Wiring Diagram YS12J33-A, YM18J34B-A, YL24J35C-A Model EQ08J11-A, EQ08J11-B IDT Ovld Neutral WE09A33E-B, WE12A33E-A, WE15A33-A WY09A33F-A, WY12A33G-A Testing The Electronic Control XQ Boards & QME Boards Checking Room TemperatureFriedrich AIR Conditioning CO