VALVE, DRAIN PAN (See Figure 43)

During the cooling mode of operation, condensate which collects in the drain pan is picked up by the condenser fan blade and sprayed onto the condenser coil. This assists in cooling the refrigerant plus evaporating the water.

During the heating mode of operation, it is necessary that water be removed to prevent it from freezing during cold outside temperatures. This could cause the condenser fan blade to freeze in the accumulated water and prevent it from turning.

To provide a means of draining this water, a bellows type drain valve is installed over a drain opening in the base pan.

This valve is temperature sensitive and will open when the outside temperature reaches 40°F. The valve will close gradually as the temperature rises above 40°F to fully close at 60°F.

HEATING ELEMENT (See Figure 44)

All heat pumps and electric heat models are equipped with a heating element with the exception of the YS09J10. The "YS", "ES" and "EK12" models are equipped with a 3.3 KW element. The "YM", "EM" and "EK18" models are equipped with a 4.0 KW element. The "YL" and "EL" models are equipped with a 5.2 KW element.

The heating element contains a fuse link and a heater limit switch. The fuse link is in series with the power supply and will open and interrupt the power when the temperature reaches 161.6°F, or a short circuit occurs in the heating element. Once the fuse link separates, a new fuse link must be installed.

NOTE: Always replace with the exact replacement.

The heater element has a high limit control. This control is a bimetal thermostat mounted in the top of the heating element.

Figure 44 - Heating Element

Should the fan motor fail or filter become clogged, the high limit control will open and interrupt power to the heater before reaching an unsafe temperature condition.

The control is designed to open at 110°F ±6°F. Test continuity below 110°F and for open above 110°F.

The heating element for the "Y" model is energized by an outdoor thermostat. The outdoor thermostat is adjusted at a predetermined temperature to bring on the heating element and turn off the compressor. The room thermostat will then control the cycling of the element when the selected indoor temperature is reached.

Testing of the elements can be made with an ohmmeter across the terminals after the connecting wires have been removed. A cold resistance reading of approximately 14.5 ohms for the

3.3KW heater, 11.9 ohms for the 4.0 KW heater and 9.15 ohms for the 5.2 KW heater should be registered.

SEALED REFRIGERATION SYSTEM REPAIRS

IMPORTANT

ANY SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRES THE INSTALLATION OF A SUCTION LINE DRIER IN THE SUCTION LINE BETWEEN THE EVAPORATOR AND THE REVERSING VALVE.

EQUIPMENT REQUIRED

1.Voltmeter

2.Ammeter

3.Ohmmeter

4.E.P.A. Approved Refrigerant Recovery System.

5.Vacuum Pump (capable of 200 microns or less vacuum.)

6.Acetylene Welder

7.Electronic Halogen Leak Detector (G.E. Type H-6 or equivalent.)

8.Accurate refrigerant charge measuring device such as:

a.Balance Scales - 1/2 oz. accuracy

b.Charging Board - 1/2 oz. accuracy

9.High Pressure Gauge - (0 - 400 lbs.)

10.Low Pressure Gauge - (30 - 150 lbs.)

11.Vacuum Gauge - (0 - 1000 microns)

29

Image 29
Contents 2003 Table of Contents 00001 1st Digit FunctionRAC Serial Number Identification Guide Page Data Evaporator AIR Operating Electrical Breaker Pressures Ratings Refrig Fuse Performance Evaporator AIR Operating Electrical Breaker Data SS10J10AR-A TEMP. DEG. F Pressures Ratings SC06H10E HeatingAmps WY09A33F-A WY12A33F-A HeatingBtuh Refrigeration System Sequence of Operation Fuse/Circuit Wire SizeBreaker GroundingChecking Compressor Efficiency Thermal Overload ExternalWinding Test Terminal Overload Internal Terminal Overload TestChecking the Internal Overload FAN MotorResistor EQ Model Only See Figure System Control Panel KQ Models Only- See FigureSystem Control Panel System Control Panel YQ Model Only System Control Switch Test System Control Switch WE & WY Models See FigureSystem Control Panel See Figure System Control Switch KS, SS, KM, SM, SL Models See FigureHeat Pump & Electric Heat Models See Figure System Control SwitchTo Adjust Temperature To SET Mode of OperationTo Adjust FAN Speed Smart Center Electronic Control CenterTesting the Electronic Control To SET the TimerTesting the Electronic Control Error Code Listings To SET Hour ClockThermostat SQ & KQ Models See Figure TestThermostat YQ Model Only See Figure Thermostat Models ES, YS, EM, YM, EL, YL See FigureThermostat Bulb Location Thermostat AdjustmentDefrost Thermostat Heat Pump Models Only Capacitor Test Defrost Bulb Location Heat Pump Models OnlyCAPACITOR, RUN See Figure Heat Pumps Reversing Valve See Figure Check Valve OperationTo Test Testing Reversing ValveSolenoid Coil Heat Pump Models Only See Figure Heating Element See Figure VALVE, Drain PAN See FigureSealed Refrigeration System Repairs Equipment RequiredSpecial Procedure in the Case Compressor Motor Burnout Hermetic Component ReplacementRotary Compressor Special Troubleshooting and Service Equipment Must be CapableMethod of Charging Undercharged Refrigerant SystemsOvercharged Refrigerant Systems Restricted Refrigerant System Routine Maintenance Troubleshooting Touch Test Chart To Service Reversing Valves Problem To Correct Troubleshooting CoolingProblem Possible Cause To Correct Cycles Problem Possible Cause To Correct Troubleshooting Heating Heat pumps Problem Possible Cause To Correct Off and the electric element is energized Troubleshooting Heating Cooling/Electric Models Troubleshooting Chart Cooling YES System Cools When Heating is DesiredModels SQ06J10B-B, SQ06J10B-A, SQ08J10C-A, SQ08J10D-A Models KQ08J10B-1, KQ08J10B-A, KQ08J10C-A Schematic YQ06J10B-A ModelModel SC06H10D 619-405-06 Alternate SL28J30B-A, SL35J30-A, SL35J30-BConductor Or Brown RED Blue To Capacitor Bracket Wiring Diagram YS12J33-A, YM18J34B-A, YL24J35C-A Model EQ08J11-A, EQ08J11-B IDT Ovld Neutral WE09A33E-B, WE12A33E-A, WE15A33-A WY09A33F-A, WY12A33G-A Checking Room Temperature Testing The Electronic Control XQ Boards & QME BoardsFriedrich AIR Conditioning CO