Troubleshooting: Heating (Cooling/Electric Models)
PROBLEM | POSSIBLE CAUSE | TO CORRECT |
|
|
|
| Heater relay or contactor coil open. | Check continuity of coil. |
Fan Operates – | Heater relay or contactor stuck open, | Inspect, test continuity with ohmmeter. |
pitted or burned. |
| |
heating element does | High limit control open. | Check continuity – if open, replace. |
not come on. | Open thermal fuse. | Check continuity. Check reason for failure. |
| Open or shorted element. | Check voltage across heater terminals. Check |
|
| amperage draw of heater. |
| Loose connections. | Tighten all terminals. |
|
|
|
PROBLEM | POSSIBLE CAUSE | TO CORRECT |
|
|
|
| Restricted filter. | Clean as recommended in Owner’s Manual. |
Heating inadequate. | Cycling high limit control. | Control is set to open at 155°F ± 5°F and close at |
| 130°F ± 8°F. If cycling prematurely, replace control. | |
|
|
|
| Exhaust or fresh air door open. | Check position of fresh air door control slide. Adjust |
|
| cable if door does not close properly. |
|
|
|
PROBLEM | POSSIBLE CAUSE | TO CORRECT |
|
|
|
| Fan relay contacts open. | Check continuity of fan relay. NOTE: Some models |
Fan operates in "Con- |
| have the fan relay energized during the heating |
stant" position, but not in |
| cycle while others do not. |
"Automatic" (Money- | Inoperative system switch. | Check continuity between terminals "L2" and "3" of |
Saver). |
| the system switch. |
| Loose connection. | Check connections on system switch and fan relay. |
|
|
|
PROBLEM | POSSIBLE CAUSE | TO CORRECT |
|
|
|
| Heat anticipator (resistor) shorted. | Disconnect power to unit. Remove resistor from |
Long "off" and "on" |
| thermostat bulb block. Plug in unit and allow to |
| operate. Feel resistor for heat. If no heat is felt, | |
cycles. |
| |
| replace resistor. | |
|
| |
| Defective thermostat. | Replace thermostat and check operation. |
|
|
|
PROBLEM | POSSIBLE CAUSE | TO CORRECT | |
|
|
| |
Fan motor does not | Defective motor. | Check and replace. | |
Open or shorted capacitor. | Replace capacitor and check. | ||
operate in "Constant" | |||
Condenser fan frozen to base pan. | Check if drain pan valve is open. If not, replace. | ||
or "MoneySaver" | |||
Loose connections. | Check all connections. Check voltage to fan motor. | ||
position. | |||
|
| ||
|
|
|
PROBLEM | POSSIBLE CAUSE | TO CORRECT |
|
|
|
|
|
|
| Heating capillary tube partially restricted. | Check for partially starved outer coil. Replace |
|
| heating capillary tube. |
Cooling adequate, | Check valve leaking internally. | Switch unit several times from heating to cooling. |
| Check temperature rise across coil. Refer to specifi- | |
heating insufficient. |
| |
| cation sheet for correct temperature rise. | |
|
| |
| Reversing valve failing to shift | Deenergize solenoid coil, raise head pressure, |
| energize solenoid to break loose. If valve fails to | |
| completely – bypassing hot gas. | |
| make complete shift, replace valve. | |
|
| |
|
|
|
43