Friedrich 2003 Terminal Overload Test, Terminal Overload Internal, Checking the Internal Overload

Page 15

Heat generated within the compressor shell is usually due to:

1.High amperage

2.Low refrigerant charge

3.Frequent recycling

4.Dirty condenser

TERMINAL OVERLOAD - TEST

(Compressor - External Type)

1.Remove overload.

2.Allow time for overload to reset before attempting to test.

3.Apply ohmmeter probes to terminals on overload wires. There should be continuity through the overload.

TERMINAL OVERLOAD (Internal)

Some model compressors are equipped with an internal overload. The overload is embedded in the motor windings to sense the winding temperature and/or current draw. The overload is connected in series with the common motor terminal.

Should the internal temperature and/or current draw become excessive, the contacts in the overload will open, turning off the compressor. The overload will automatically reset, but may require several hours before the heat is dissipated.

CHECKING THE INTERNAL OVERLOAD

(See Figure 4)

Figure 4

Internal Overload

1.With no power to unit, remove the leads from the com- pressor terminals.

2.Using an ohmmeter, test continuity between terminals C-S and C-R. If no continuity, the compressor overload is open and the compressor must be replaced.

FAN MOTOR

A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting over- load is located inside the motor to protect against high tem- perature and high amperage conditions. (See Figure 5)

FAN MOTOR - TEST

1.Determine that capacitor is serviceable.

2.Disconnect fan motor wires from fan speed switch or system switch.

3.Apply "live" test cord probes on black wire and common terminal of capacitor. Motor should run at high speed.

4.Apply "live" test cord probes on red wire and common terminal of capacitor. Motor should run at low speed.

5.Apply "live" test cord probes on each of the remaining wires from the speed switch or system switch to test intermediate speeds. If the control is in the "MoneySaver" mode and the thermostat calls for cooling, the fan will start - then stop after approximately 2 minutes; then the fan and compressor will start together approximately 2 minutes later.

Figure 5

Fan Motor

SYSTEM CONTROL PANEL- SQ Models (See Figure 6) A five-position control switch is used to regulate the operation of the fan motor and compressor. The compressor can be operated with the fan operating at low, medium or high speed. The fan motor can also be operated independently on medium speed. See switch section as indicated on the decorative control panel.

Figure 6

System Control Panel (SQ Models Only)

15

Image 15
Contents 2003 Table of Contents 1st Digit Function RAC Serial Number Identification Guide00001 Page Data Evaporator AIR Operating Electrical Breaker Pressures Ratings Refrig Fuse Performance Evaporator AIR Operating Electrical Breaker Data SS10J10AR-A TEMP. DEG. F Pressures Ratings SC06H10E HeatingWY09A33F-A WY12A33F-A Heating BtuhAmps Refrigeration System Sequence of Operation Grounding Wire SizeFuse/Circuit BreakerThermal Overload External Winding TestChecking Compressor Efficiency FAN Motor Terminal Overload TestTerminal Overload Internal Checking the Internal OverloadResistor System Control Panel KQ Models Only- See Figure System Control PanelEQ Model Only See Figure System Control Panel YQ Model Only System Control Switch Test System Control Switch WE & WY Models See FigureSystem Control Panel See Figure System Control Switch KS, SS, KM, SM, SL Models See FigureHeat Pump & Electric Heat Models See Figure System Control SwitchSmart Center Electronic Control Center To SET Mode of OperationTo Adjust Temperature To Adjust FAN SpeedTo SET Hour Clock To SET the TimerTesting the Electronic Control Testing the Electronic Control Error Code ListingsThermostat Models ES, YS, EM, YM, EL, YL See Figure TestThermostat SQ & KQ Models See Figure Thermostat YQ Model Only See FigureThermostat Adjustment Defrost Thermostat Heat Pump Models OnlyThermostat Bulb Location Defrost Bulb Location Heat Pump Models Only CAPACITOR, RUN See FigureCapacitor Test Heat Pumps Reversing Valve See Figure Check Valve OperationTesting Reversing Valve Solenoid Coil Heat Pump Models Only See FigureTo Test Equipment Required VALVE, Drain PAN See FigureHeating Element See Figure Sealed Refrigeration System RepairsEquipment Must be Capable Hermetic Component ReplacementSpecial Procedure in the Case Compressor Motor Burnout Rotary Compressor Special Troubleshooting and ServiceMethod of Charging Undercharged Refrigerant SystemsOvercharged Refrigerant Systems Restricted Refrigerant System Routine Maintenance Troubleshooting Touch Test Chart To Service Reversing Valves Problem To Correct Troubleshooting CoolingProblem Possible Cause To Correct Cycles Problem Possible Cause To Correct Troubleshooting Heating Heat pumps Problem Possible Cause To Correct Off and the electric element is energized Troubleshooting Heating Cooling/Electric Models Troubleshooting Chart Cooling YES System Cools When Heating is DesiredModels SQ06J10B-B, SQ06J10B-A, SQ08J10C-A, SQ08J10D-A Models KQ08J10B-1, KQ08J10B-A, KQ08J10C-A Schematic YQ06J10B-A ModelModel SC06H10D 619-405-06 Alternate SL28J30B-A, SL35J30-A, SL35J30-BConductor Or Brown RED Blue To Capacitor Bracket Wiring Diagram YS12J33-A, YM18J34B-A, YL24J35C-A Model EQ08J11-A, EQ08J11-B IDT Ovld Neutral WE09A33E-B, WE12A33E-A, WE15A33-A WY09A33F-A, WY12A33G-A Checking Room Temperature Testing The Electronic Control XQ Boards & QME BoardsFriedrich AIR Conditioning CO