Friedrich 2003 service manual Smart Center Electronic Control Center, To SET Mode of Operation

Page 22

SYSTEM CONTROL SWITCH - TEST (See Figure 28) Disconnect leads from control switch. Turn control to position being tested. There must be continuity as follows:

1."Off" Position - no continuity between terminals.

2."Lo Cool" Position - between terminals "C" and "3", "C2" and "2", "LO" and "M/S", "AR" and "5".

3."Med Cool" Position - between terminals "C" and "3", "C2" and "2", "M" and "M/S", "AR" and "5".

4."Hi Cool" Position - between terminals "C" and "3", "C2" and "2", "H" and "M/S", "AR" and "5".

5."Hi Heat" Position - between terminals "C" and "1", "C2" and "4", "H" and "M/S", "AR" and "5".

6."Med Heat" Position - between terminals "C" and "1", "C2" and "4", "M" and "M/S", "AR" and "5".

7."Lo Cool" Position - between terminals "C" and "1", "C2" and "4", "LO" and "M/S", "AR" and "5".

8."Fan Only" Position - between terminals "L1" and "M".

Figure 28

System Control Switch

(Heat Pump / Electric

Heat Models

Smart Center Electronic Control Center

(See Figure 29)

FILTER ALERT light will come on after 250 hours of use. Touch FILTER ALERT to reset.

TO SET MODE OF OPERATION

When unit is first turned on, it will be in the COOL mode (light on), with constant fan.

Touch MONEYSAVER (light on) to activate the MoneySaver feature. (MoneySaver is a feature that cycles the fan with the compressor so that the fan does not run all the time. This saves energy and improves dehumidification.) If customer prefers a constant fan for more air movement, touch MONEYSAVER again and unit will return to constant fan.

Touch FAN ONLY (light on) and only the fan will run. This feature may be used in conjunction with the FRESH AIR/ EXHAUST lever to bring outside air into a room, or to exhaust stale air.

TO ADJUST TEMPERATURE

COOLER - Touch COOLER to see setting, touch again to change.

WARMER - Touch WARMER to see setting, touch again to change.

Touch °F/°C to show desired temperature in Fahrenheit or Celsius.

TO ADJUST FAN SPEED

Touch SPEED to see current setting. Touch again to change speed. F1 is lowest setting (sleep setting), F2 is LOW, F3 is MED, and F4 is HIGH.

TO ACTIVATE SMART FAN

Touch SMART FAN (light on). Smart Fan will adjust the fan speed automatically to maintain the desired comfort level. For example, if the outside doors in the home are open for an extended period of time, or more people enter a room, Smart Fan may adjust to a higher fan speed to compensate for the increased heat load. This keeps from having to adjust the fan speed on your own, or from having to change the desired temperature you have selected. Smart Fan will also run to test temperature if the off cycle is long.

Figure 29

Electronic Control

22

Image 22
Contents 2003 Table of Contents RAC Serial Number Identification Guide 1st Digit Function00001 Page Data Evaporator AIR Operating Electrical Breaker Pressures Ratings Refrig Fuse Performance Evaporator AIR Operating Electrical Breaker Data SS10J10AR-A TEMP. DEG. F Pressures Ratings Heating SC06H10EBtuh WY09A33F-A WY12A33F-A HeatingAmps Refrigeration System Sequence of Operation Breaker Wire SizeFuse/Circuit GroundingWinding Test Thermal Overload ExternalChecking Compressor Efficiency Checking the Internal Overload Terminal Overload TestTerminal Overload Internal FAN MotorResistor System Control Panel System Control Panel KQ Models Only- See FigureEQ Model Only See Figure System Control Panel YQ Model Only System Control Switch WE & WY Models See Figure System Control Switch TestSystem Control Switch KS, SS, KM, SM, SL Models See Figure System Control Panel See FigureSystem Control Switch Heat Pump & Electric Heat Models See FigureTo Adjust FAN Speed To SET Mode of OperationTo Adjust Temperature Smart Center Electronic Control CenterTesting the Electronic Control Error Code Listings To SET the TimerTesting the Electronic Control To SET Hour ClockThermostat YQ Model Only See Figure TestThermostat SQ & KQ Models See Figure Thermostat Models ES, YS, EM, YM, EL, YL See FigureDefrost Thermostat Heat Pump Models Only Thermostat AdjustmentThermostat Bulb Location CAPACITOR, RUN See Figure Defrost Bulb Location Heat Pump Models OnlyCapacitor Test Check Valve Operation Heat Pumps Reversing Valve See FigureSolenoid Coil Heat Pump Models Only See Figure Testing Reversing ValveTo Test Sealed Refrigeration System Repairs VALVE, Drain PAN See FigureHeating Element See Figure Equipment RequiredRotary Compressor Special Troubleshooting and Service Hermetic Component ReplacementSpecial Procedure in the Case Compressor Motor Burnout Equipment Must be CapableUndercharged Refrigerant Systems Method of ChargingOvercharged Refrigerant Systems Restricted Refrigerant System Routine Maintenance Troubleshooting Touch Test Chart To Service Reversing Valves Troubleshooting Cooling Problem To CorrectProblem Possible Cause To Correct Cycles Problem Possible Cause To Correct Troubleshooting Heating Heat pumps Problem Possible Cause To Correct Off and the electric element is energized Troubleshooting Heating Cooling/Electric Models Troubleshooting Chart Cooling System Cools When Heating is Desired YESModels SQ06J10B-B, SQ06J10B-A, SQ08J10C-A, SQ08J10D-A Models KQ08J10B-1, KQ08J10B-A, KQ08J10C-A Schematic Model YQ06J10B-AModel SC06H10D 619-405-06 SL28J30B-A, SL35J30-A, SL35J30-B AlternateConductor Or Brown RED Blue To Capacitor Bracket Wiring Diagram YS12J33-A, YM18J34B-A, YL24J35C-A Model EQ08J11-A, EQ08J11-B IDT Ovld Neutral WE09A33E-B, WE12A33E-A, WE15A33-A WY09A33F-A, WY12A33G-A Testing The Electronic Control XQ Boards & QME Boards Checking Room TemperatureFriedrich AIR Conditioning CO