Friedrich 2003 service manual Check Valve Operation, Heat Pumps Reversing Valve See Figure

Page 27

CHECK VALVE (See Figure 39)

A unique two-way check valve is used on the reverse cycle heat pumps. It is pressure operated and used to direct the flow of refrigerant through a single filter drier and to the proper capillary tube during either the heating or cooling cycle

Figure 39

One-way Check Valve

(Heat Pump Models)

Figure 40

(TO INDOOR COIL)

(TO OUTDOOR COIL)

NOTE: The slide (check) inside the valve is made of teflon. Should it become necessary to replace the check valve, place a wet cloth around the valve to prevent overheating during the brazing operation.

CHECK VALVE OPERATION

In the cooling mode of operation, high pressure liquid enters the check valve forcing the slide to close the opposite port (liquid line) to the indoor coil. Refer to refrigerant flow chart. This directs the refrigerant through the filter drier and cooling capillary tube to the indoor coil.

In the heating mode of operation, high pressure refrigerant enters the check valve from the opposite direction, closing the port (liquid line) to the outdoor coil. The flow path of the refrigerant is then through the filter drier and heating capillary to the outdoor coil.

Failure of the slide in the check valve to seat properly in either mode of operation will cause flooding of the cooling coil. This is due to the refrigerant bypassing the heating or cooling capillary tube and entering the liquid line.

COOLING MODE (See Figure 40)

In the cooling mode of operation, liquid refrigerant from con- denser (liquid line) enters the cooling check valve forcing the heating check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through cooling capillary tubes to evaporator. (Note: liquid refrigerant will also be directed through the heating capillary tubes in a continuous loop during the cooling mode).

HEATING MODE (see Figure 41)

In the heating mode of operation, liquid refrigerant from the indoor coil enters the heating check valve forcing the cooling check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through the heating capillary tubes to outdoor coils. (Note: liquid refriger- ant will also be directed through the cooling capillary tubes in a continuous loop during the heating mode).

Figure 41

(TO INDOOR COIL)

(TO OUTDOOR COIL)

HEAT PUMPS: REVERSING VALVE (See Figure 42)

A reversing valve is used to change the refrigerant flow within the system to permit heating or cooling.

The reversing valve consists of a main valve body which houses the slide and piston, plus a pilot valve which is activated by a solenoid.

27

Image 27
Contents 2003 Table of Contents 1st Digit Function RAC Serial Number Identification Guide00001 Page Data Evaporator AIR Operating Electrical Breaker Pressures Ratings Refrig Fuse Performance Evaporator AIR Operating Electrical Breaker Data SS10J10AR-A TEMP. DEG. F Pressures Ratings SC06H10E HeatingWY09A33F-A WY12A33F-A Heating BtuhAmps Refrigeration System Sequence of Operation Grounding Wire SizeFuse/Circuit BreakerThermal Overload External Winding TestChecking Compressor Efficiency FAN Motor Terminal Overload TestTerminal Overload Internal Checking the Internal OverloadResistor System Control Panel KQ Models Only- See Figure System Control PanelEQ Model Only See Figure System Control Panel YQ Model Only System Control Switch Test System Control Switch WE & WY Models See FigureSystem Control Panel See Figure System Control Switch KS, SS, KM, SM, SL Models See FigureHeat Pump & Electric Heat Models See Figure System Control SwitchSmart Center Electronic Control Center To SET Mode of OperationTo Adjust Temperature To Adjust FAN SpeedTo SET Hour Clock To SET the TimerTesting the Electronic Control Testing the Electronic Control Error Code ListingsThermostat Models ES, YS, EM, YM, EL, YL See Figure TestThermostat SQ & KQ Models See Figure Thermostat YQ Model Only See FigureThermostat Adjustment Defrost Thermostat Heat Pump Models OnlyThermostat Bulb Location Defrost Bulb Location Heat Pump Models Only CAPACITOR, RUN See FigureCapacitor Test Heat Pumps Reversing Valve See Figure Check Valve OperationTesting Reversing Valve Solenoid Coil Heat Pump Models Only See FigureTo Test Equipment Required VALVE, Drain PAN See FigureHeating Element See Figure Sealed Refrigeration System RepairsEquipment Must be Capable Hermetic Component ReplacementSpecial Procedure in the Case Compressor Motor Burnout Rotary Compressor Special Troubleshooting and ServiceMethod of Charging Undercharged Refrigerant SystemsOvercharged Refrigerant Systems Restricted Refrigerant System Routine Maintenance Troubleshooting Touch Test Chart To Service Reversing Valves Problem To Correct Troubleshooting CoolingProblem Possible Cause To Correct Cycles Problem Possible Cause To Correct Troubleshooting Heating Heat pumps Problem Possible Cause To Correct Off and the electric element is energized Troubleshooting Heating Cooling/Electric Models Troubleshooting Chart Cooling YES System Cools When Heating is DesiredModels SQ06J10B-B, SQ06J10B-A, SQ08J10C-A, SQ08J10D-A Models KQ08J10B-1, KQ08J10B-A, KQ08J10C-A Schematic YQ06J10B-A ModelModel SC06H10D 619-405-06 Alternate SL28J30B-A, SL35J30-A, SL35J30-BConductor Or Brown RED Blue To Capacitor Bracket Wiring Diagram YS12J33-A, YM18J34B-A, YL24J35C-A Model EQ08J11-A, EQ08J11-B IDT Ovld Neutral WE09A33E-B, WE12A33E-A, WE15A33-A WY09A33F-A, WY12A33G-A Checking Room Temperature Testing The Electronic Control XQ Boards & QME BoardsFriedrich AIR Conditioning CO