Friedrich 2003 service manual TEMP. DEG. F Pressures Ratings

Page 9

WS PERFORMANCE DATA

PERFORMANCE

EVAPORATOR AIR

OPERATING

ELECTRICAL

R-22

BREAKER

DATA*

TEMP. DEG. F.

PRESSURES

RATINGS

REFRIG.

FUSE

Cooling

 

 

 

 

 

 

 

 

Discharge

Temp.

Suction

Discharge

Amps

Locked

Charge in

60 Hertz

 

Air

Drop F.

 

 

 

Rotar Amp

OZ.

Amps

 

 

 

 

 

 

 

 

 

WS07A10E-B

59.5

19.5

84

300

7.'0

32

19

15

WS07A10E-C

59.5

19.5

85

299

7.'0

32

28

15

WS07A10E-D

59.5

19.5

85

299

7.'0

32

20

15

WS10A10-A

58

22

83

307

9.8

48

25

15

WS10A10-B

58

22

83

307

9.8

48

26

15

WS12A10E-B

55

25

81

290

11.9

54

28.5

15

WS13A10-A

55

25

79

281

12

55

36

15

WS09A30E-B

58

22

86

302

4.7

44

22

15

WS12A30E-A

47.1

32.9

80

308

11.9

54

27.5

15

WS12A30E-B

46

33

80

305

11.9

54

42

15

WS15A30-A

47

33

72

310

8.5

42

43.5

15

 

 

 

 

 

 

 

 

 

 

 

WE-WY PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

DATA*

EVAPORATOR

OPERATION

ELECTRICAL

R-22

BREAKER

Cooling

TEMP. DEG. F.

PRESSURES

RATINGS

REFRIG.

FUSE

 

Discharge

Temp.

Suction

Discharge

Amps

Locked

Charge in

60 Hertz

 

Air

Drop F.

 

 

 

Rotar Amp

OZ.

Amps

WE09A33E-C

58

22

86

302

4.7

44

23

20

WE12A33E-B

55

25

80

308

6.5

54

27.5

20

WE15A33-A

47.1

32.9

71

310

8.5

42

43.5

20

WY09A33F-A

58

22

83

288

4.3

44

24

20

WY12A33G-A

55

25

81

295

6.2

54

37

20

 

 

 

 

 

 

 

 

 

PERFORMANCE

Heat Rise

 

 

 

 

 

 

 

DATA heating

 

 

 

 

 

 

 

 

WE15A33-A

40

 

 

 

16.2

 

 

 

WE09A33E-C

39

 

 

 

14.7

 

 

 

WE12A33E-B

36

 

 

 

14.7

 

 

 

 

 

 

 

 

 

 

 

 

*Rating Conditions: 80 degree F. Room Air Temperature and 50% Relative Humidity 95 degree F. Outside Air Temperature at 40% Relative Humidity

9

Image 9
Contents 2003 Table of Contents 1st Digit Function RAC Serial Number Identification Guide00001 Page Data Evaporator AIR Operating Electrical Breaker Pressures Ratings Refrig Fuse Performance Evaporator AIR Operating Electrical Breaker Data SS10J10AR-A TEMP. DEG. F Pressures Ratings SC06H10E HeatingWY09A33F-A WY12A33F-A Heating BtuhAmps Refrigeration System Sequence of Operation Fuse/Circuit Wire SizeBreaker GroundingThermal Overload External Winding TestChecking Compressor Efficiency Terminal Overload Internal Terminal Overload TestChecking the Internal Overload FAN MotorResistor System Control Panel KQ Models Only- See Figure System Control PanelEQ Model Only See Figure System Control Panel YQ Model Only System Control Switch Test System Control Switch WE & WY Models See FigureSystem Control Panel See Figure System Control Switch KS, SS, KM, SM, SL Models See FigureHeat Pump & Electric Heat Models See Figure System Control SwitchTo Adjust Temperature To SET Mode of OperationTo Adjust FAN Speed Smart Center Electronic Control CenterTesting the Electronic Control To SET the TimerTesting the Electronic Control Error Code Listings To SET Hour ClockThermostat SQ & KQ Models See Figure TestThermostat YQ Model Only See Figure Thermostat Models ES, YS, EM, YM, EL, YL See FigureThermostat Adjustment Defrost Thermostat Heat Pump Models OnlyThermostat Bulb Location Defrost Bulb Location Heat Pump Models Only CAPACITOR, RUN See FigureCapacitor Test Heat Pumps Reversing Valve See Figure Check Valve OperationTesting Reversing Valve Solenoid Coil Heat Pump Models Only See FigureTo Test Heating Element See Figure VALVE, Drain PAN See FigureSealed Refrigeration System Repairs Equipment RequiredSpecial Procedure in the Case Compressor Motor Burnout Hermetic Component ReplacementRotary Compressor Special Troubleshooting and Service Equipment Must be CapableMethod of Charging Undercharged Refrigerant SystemsOvercharged Refrigerant Systems Restricted Refrigerant System Routine Maintenance Troubleshooting Touch Test Chart To Service Reversing Valves Problem To Correct Troubleshooting CoolingProblem Possible Cause To Correct Cycles Problem Possible Cause To Correct Troubleshooting Heating Heat pumps Problem Possible Cause To Correct Off and the electric element is energized Troubleshooting Heating Cooling/Electric Models Troubleshooting Chart Cooling YES System Cools When Heating is DesiredModels SQ06J10B-B, SQ06J10B-A, SQ08J10C-A, SQ08J10D-A Models KQ08J10B-1, KQ08J10B-A, KQ08J10C-A Schematic YQ06J10B-A ModelModel SC06H10D 619-405-06 Alternate SL28J30B-A, SL35J30-A, SL35J30-BConductor Or Brown RED Blue To Capacitor Bracket Wiring Diagram YS12J33-A, YM18J34B-A, YL24J35C-A Model EQ08J11-A, EQ08J11-B IDT Ovld Neutral WE09A33E-B, WE12A33E-A, WE15A33-A WY09A33F-A, WY12A33G-A Checking Room Temperature Testing The Electronic Control XQ Boards & QME BoardsFriedrich AIR Conditioning CO