5.5Disabling some of the HP-COMPACT functions

Each different function charger, inverter and transfer can be disabled. This is useful for specific applications witch required to disable some of these three functions.

If you press the buttons 19 and 20 more than 2 seconds you can have access to the different possibilities shown in the following diagram.

In programming mode the display shows only the different types of program with the three LED’s 2, 7 and 9 to each function. To change the type of programming, press shortly the button 20 until you reach the right function used according to the table below. After 30 seconds the HP-COMPACT exits the programming mode and loads the new change.

In user mode, the disabled functions are displayed by blinking LED. So you can see which mode is disabled.

5.5.1 Diagram of the different modes

Shows an off LED

Shows a blinking LED

Shows a lighted LED

All the functions are enabled. This is the factory setting.

The inverter is disabled. Only the transfer switch and the charger will work normally.

Charger and transfer switch are disabled. the inverter will work continuously even if there is a correct AC voltage at the input

Inverter and charger are both disabled. Only the transfer switch function is enabled in input voltage and frequency is OK.

6 Installation Maintenance

Apart from the periodic controls mentioned for the connections, the HP-COMPACT does need any maintenance. Keep the appliance clean and from time to time, wipe it clean with a damp cloth.

7 Declaration of CE Compliance

Hereby we state that the products described in this user manual comply with the following standards:

EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, Dir. 89/336/EEC, LVD 73/23/EEC, EN 50091-2, EN 60950-1.

CH - 1950 Sion, the 31st of January 2002

STUDER INNOTEC (R. Studer)

HP-COMPACT V5.4

27/80

Image 25
Contents HP-COMPACT HPC Sine wave Inverter, Battery charger, TransfersystemHP-COMPACT Warranty Disclaimer Quality and WarrantyGeneral Information Operating instructionsLiability Disclaimer Special precautionsIntroduction Principle schematicDescription of the main functions Battery connecting Installation place Mounting and installingFixing ConnectionsCabling Pre-installation settingsConnection to battery 3.6.1.1 On the appliance side Connection to Temperature Sensor Temp Connection to Remote controlConnection to the 230Vac-consumer appliances AC Output Connection to the 230Vac Input AC InputDisplay and control parameters ControlLED Light Emitting Diodes LEDTurning Knobs Push buttonsInverter Charge detection system „StandbyOverheating Over Temp Battery ConditionDefault values for battery voltage thresholds Battery chargerCycle of charge Equalization chargingSet the Input Limit Input current repartition Power sharingCharging current Transfer system Delayed mode of the Transfer System Fast UPS- Mode for the Transfer SwitchMultifunctional Contact Set the transfer voltage thresholdHP-COMPACT Remote Control RCC-01Standard setting Remote control for „Power Sharing RPS-01Programming Battery voltages and absorption time Reset value default settingsSet the voltage and timing threshold Table of voltage and timing threshold Auxiliary contactPrinciple Programming of the Auxiliary ContactManual operating of Auxiliary Contact Power cut of the second priority loadsDiagram of the different modes Installation MaintenanceDisabling some of the HP-COMPACT functions Declaration of CE ComplianceTechnical Data