including the battery. If after the fuse replacement and after re-connection of the battery with the right polarity, the HP-COMPACT remains out of order, it must be brought back to your merchant for service.

3.6.2 Connection to the 230Vac-consumer appliances (AC OUTPUT)

The 230V consumer appliances must be connected to the terminals AC OUTPUT with cables which cross section has to follow the local rules in force (usually 2.5mm2). Connections are marked as follows “N“ Neutral, “PE“ Earth (connected to the appliance box), “L“ Live.

Caution: High voltages can be there. Make sure that the HP-COMPACT is turned off (LED 13 lighting) before the connection.

3.6.3 Connection to the 230Vac Input (AC INPUT)

The 230V-supply from network or from a generator must be connected to the input terminals AC INPUT with cables which cross section depends on the power source (usually 2.5mm2). Connections are marked as follows: “N“ Neutral, “PE“ Earth, “L“ Live (connected to the appliance case).

3.6.4 Connection to Auxiliary Contact

This contact is a potential free change over contact the currents and voltages allowed for this contact are max. 16A/250Vac. The LED 5 “Contact active” shows the position of them: alight mind active and off mind non-active. The schematic view of the connections on the front, show the relay in the non-active mode.

3.6.5 Connection to Remote control

The Remote Control RCC-01 is connected in the terminal marked „Remote control“ with a 20m long cable and a RJ11/8 connector. The Remote Control can be plugged IN or plugged OUT during any operation situation. Push in the connector softly until you hear the „click“ showing that the connector is locked. The same applies to the plug in the Remote Control.

The length of the cable for Remote Control should not exceed 40m. We deliver it with 20m cable.

3.6.6Connection to Temperature Sensor (Temp.)

The temperature sensor CT-35 is connected in the terminal marked „Temp“ with a 3m long cable and a RJ11/6 connector. The temperature sensor can be plugged IN or plugged OUT during any operating situation. Push in the connector softly until you hear the „click“ showing that the connector is locked. The temperature sensor must be glued to the wall of the battery or near it. The Temperature Sensor cable must not be tied together with the battery cables or laid in a rope/bundle.

3.6.7 Connection to the Remote Control for the „Power Sharing“ (RPS-01)

This remote control is connected with a 20m long cable and a RJ11/6 connector in the connection terminal „F“ (Temp. sensor). It can be connected and disconnected at any time. Push in the connector softly until you hear the „click“ showing that the connector is locked. In case the remote control is connected together with the Temp. sensor, a short cable with a Y-connector will be connected in the terminal „F“ (can be supply as an option).

HP-COMPACT V5.4

13/80

Image 11
Contents HP-COMPACT HPC Sine wave Inverter, Battery charger, TransfersystemHP-COMPACT Operating instructions Quality and WarrantyWarranty Disclaimer General InformationLiability Disclaimer Special precautionsIntroduction Principle schematicDescription of the main functions Battery connecting Connections Mounting and installingInstallation place FixingCabling Pre-installation settingsConnection to battery 3.6.1.1 On the appliance side Connection to the 230Vac Input AC Input Connection to Remote controlConnection to Temperature Sensor Temp Connection to the 230Vac-consumer appliances AC OutputDisplay and control parameters ControlLED Light Emitting Diodes LEDCharge detection system „Standby Push buttonsTurning Knobs InverterOverheating Over Temp Battery ConditionEqualization charging Battery chargerDefault values for battery voltage thresholds Cycle of chargeCharging current Input current repartition Power sharingSet the Input Limit Transfer system Set the transfer voltage threshold Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Multifunctional ContactHP-COMPACT Remote Control RCC-01Programming Remote control for „Power Sharing RPS-01Standard setting Set the voltage and timing threshold Reset value default settingsBattery voltages and absorption time Programming of the Auxiliary Contact Auxiliary contactTable of voltage and timing threshold PrincipleManual operating of Auxiliary Contact Power cut of the second priority loadsDeclaration of CE Compliance Installation MaintenanceDiagram of the different modes Disabling some of the HP-COMPACT functionsTechnical Data