Studer Innotec HPC 2800-12, HPC 4400-24, HPC 6000-48, HPC 8000-48 Auxiliary contact, Principle

Page 23

STUDER INNOTEC

HP-COMPACT

5.3.2 Table of voltage and timing threshold

The voltage levels (low voltage, float charge, end of charge and equalization) and the du-ration of the absorption charge can be changed.

The display of these voltages and the times in the program mode are in accordance with the diagram shown below:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Absorption

Equali-

LED

Low voltage

Float charge

Absorption

Equalization

zation

time

 

 

 

 

 

 

 

 

 

 

 

 

 

time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED 13

 

 

LED 12

 

 

LED 11

 

 

LED 10

 

LED

LED 10/11

 

 

 

 

 

 

 

 

 

10/11/12/13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

24

48

12

24

48

12

24

48

12

24

48

12/24/48

12/24/48

14

12.0

 

24.0

48.0

13.7

27.4

54.8

16.2

32.4

64.8

16.2

32.4

64.8

4h

3h

15

11.8

 

23.6

47.2

13.6

27.2

54.4

15.6

31.2

62.4

15.9

31.8

63.6

3h

2h

16

11.6

 

23.2

46.4

13.5

27.0

54.0

15

30

60

15.6

31.2

62.4

2h

1h

17

11.4

 

22.8

45.6

13.4

26.8

53.6

14.4

28.8

57.6

15.3

30.6

61.2

1h

40’

18

11.2

 

22.4

44.8

13.3

26.6

53.2

14.2

28.4

56.8

15

30

60

0 – 1’

20’

The heavy printed values show the standard settings.

5.4Auxiliary contact

5.4.1 Principle

The Auxiliary Contact can be basically programmed for any operating situation of the HP-COMPACT which is indicated with a LED. The programming is possible for one or more operating situations. If the contact is programmed for many situations, it is activated as soon as the HP-COMPACT finds itself in any one of the programmed situations. That means that the work of the contact meets that of the logic OR– Function.

5.4.2 The programming of the Auxiliary Contact

The programming of the Auxiliary Contact is carried out in the following Steps:

The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4 „Program“ is lit as an indication, that the HP-COMPACT is in program mode.

A blinking LED shows the programmed condition for the auxiliary contact (LED 10/11/ 12/13 factory setting).

With the Push Button 20 (select), select the desired condition in which the contact should be activated.

With the Push Button 19 (Change status) confirm or change the status for this condition. If desired, with the Push Button 20 (select) select another condition in which the contact should be activated.

With the Push Button 19 (Change status) confirm or change the status for this condition. If during 30 seconds no buttons are pushed, then the settled values are automatically stored and the HP-COMPACT switches back to normal operating condition.

5.4.3Auxiliary Contact as generator starter

As per the battery capacity

When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18) is used as a condition, you must then take note of the following requirements.

If you have to start an emergency back-up supply with a battery having a certain residual capacity, then two battery levels must be programmed. The first (i.e. Battery 25% LED 17) for the starting or activating the Auxiliary Contact and the second (i.e.

Battery 100% LED15) for stopping or disabling the Auxiliary Contact. Programmed

HP-COMPACT V5.4

25/80

Image 23
Contents HP-COMPACT HPC Sine wave Inverter, Battery charger, TransfersystemHP-COMPACT Operating instructions Quality and WarrantyWarranty Disclaimer General InformationLiability Disclaimer Special precautionsIntroduction Principle schematicDescription of the main functions Battery connecting Connections Mounting and installingInstallation place FixingCabling Pre-installation settingsConnection to battery 3.6.1.1 On the appliance side Connection to the 230Vac Input AC Input Connection to Remote controlConnection to Temperature Sensor Temp Connection to the 230Vac-consumer appliances AC OutputDisplay and control parameters ControlLED Light Emitting Diodes LEDCharge detection system „Standby Push buttonsTurning Knobs InverterOverheating Over Temp Battery ConditionEqualization charging Battery chargerDefault values for battery voltage thresholds Cycle of chargeCharging current Input current repartition Power sharingSet the Input Limit Transfer system Set the transfer voltage threshold Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Multifunctional ContactHP-COMPACT Remote Control RCC-01Programming Remote control for „Power Sharing RPS-01Standard setting Set the voltage and timing threshold Reset value default settingsBattery voltages and absorption time Programming of the Auxiliary Contact Auxiliary contactTable of voltage and timing threshold PrincipleManual operating of Auxiliary Contact Power cut of the second priority loadsDeclaration of CE Compliance Installation MaintenanceDiagram of the different modes Disabling some of the HP-COMPACT functionsTechnical Data