5.2Reset value (default settings)
To come back to the default settings, press simultaneously on the push buttons 20/21 during at least 2 seconds. A beep will confirm the comeback to the factory settings. The inverter switches off after this operation. It can be turned on again after the beep.
5.3Battery voltages and absorption time
5.3.1 Set the voltage and timing threshold
The programming is done in accordance with the following steps:
Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for minimum 2 seconds simultaneously.
With the Push Button 20 (select) select which of the battery level and of the absorption time have to be changed.
These four red LED’s show the function set:
Low voltage | LED 13 | (ON/OFF) |
Float charge | LED 12 | (Batt. Low/high) |
Absorption (End of charge) | LED 11 | (Overload) |
Equalization | LED 10 | (Overtemp.) |
Absorption Time | LED 10/11/12/13 (altogether) |
With the Push Button 19 (Change status) set the desired parameter (voltage or time) to modify (LED 14/ 15/16/17/18). Push Button 19 (Change status) to set the desired value according to the table 5.3.2.
If desired, repeat the operation with any other parameter (voltage or time) to be changed.
If during 30 seconds no buttons are pressed, the selected values are automatically stored and the HP- COMPACT switches back in to the normal operating status.
The voltage levels and times changed through programming are only first active with the next charge cycle!
The voltage level which is not suitable can greatly reduce the battery life or could even destroy it ! Therefore check beforehand with your battery supplier.