Studer Innotec HPC 2800-12, HPC 4400-24, HPC 6000-48, HPC 8000-48 manual

Page 6

STUDER INNOTEC

HP-COMPACT

connection between Neutral and earth in inverter mode only may be done by installing a bridge internally to the unit. Please contact your installer regarding this point.

(2) Remote control for remote adjustment of the input limit. (see chap. 4.6.3)

2.2Description of the main functions

2.2.1 The inverter

The sine wave inverter HP-COMPACT generates a sinusoidal AC voltage with an exceptionally precise voltage and stabilized frequency. In order to start large electric motors, the user has the possibility to use a short surge power which is 3 times the nominal power of the HP-COMPACT.

The inverter is protected against overload and short circuit. A power stage with the latest MOS-FET power transistors, a toroidal transformer, and a fast regulating system makes a robust and reliable inverter with the highest efficiency. A 1-20 Watt adjustable charge detection system allows the smallest energy consumption and ensures a long life for the battery.

2.2.2 The transfer system

HP-COMPACT can be connected to an AC source. For example a stand-by emergency generator or the AC network. With the transfer system, on one side you have an alternating voltage at the output for the use of consumer appliances. On the other side the battery park is being charged. The distribution of energy between the consumer appliances and battery charger is automatic.

2.2.3 The battery charger

The built-in battery charger is so designed that it can charge the battery quickly and fully. A microprocessor controlled, Step charging process, ensures the optimal charging of the battery. The desired charging current can be set continuously from 0 to 70/90/100/110 A, as per the model. The setting is made accordingly to the battery capacity and power available.

The battery charger is designed for lead-acid and lead-gel batteries. Thanks to the floating charge system the batteries can remain continuously connected.

2.2.4 Remote control

As an option, a remote control RCC-01 can be connected to HP-COMPACT. All operating features and displays, save the adjustment levels (22/23/24/26), are available on the re-mote control. It is supplied with a 20m long cable. This cable can be up to 40m long. On the remote control, output power and charging current are also displayed.

2.2.5 Remote control for Power Sharing

This remote control RPS-01 can be connected to the HP-COMPACT in the gland for the temperature sensor. The maximum current available from the energy source can be adjusted by the turning button.

HP-COMPACT V5.4

8/80

Image 6
Contents Sine wave Inverter, Battery charger, Transfersystem HP-COMPACT HPCHP-COMPACT General Information Quality and WarrantyWarranty Disclaimer Operating instructionsSpecial precautions Liability DisclaimerPrinciple schematic IntroductionDescription of the main functions Battery connecting Fixing Mounting and installingInstallation place ConnectionsPre-installation settings CablingConnection to battery 3.6.1.1 On the appliance side Connection to the 230Vac-consumer appliances AC Output Connection to Remote controlConnection to Temperature Sensor Temp Connection to the 230Vac Input AC InputControl Display and control parametersLight Emitting Diodes LED LEDInverter Push buttonsTurning Knobs Charge detection system „StandbyBattery Condition Overheating Over TempCycle of charge Battery chargerDefault values for battery voltage thresholds Equalization chargingInput current repartition Power sharing Set the Input LimitCharging current Transfer system Multifunctional Contact Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Set the transfer voltage thresholdRemote Control RCC-01 HP-COMPACTRemote control for „Power Sharing RPS-01 Standard settingProgramming Reset value default settings Battery voltages and absorption timeSet the voltage and timing threshold Principle Auxiliary contactTable of voltage and timing threshold Programming of the Auxiliary ContactPower cut of the second priority loads Manual operating of Auxiliary ContactDisabling some of the HP-COMPACT functions Installation MaintenanceDiagram of the different modes Declaration of CE ComplianceTechnical Data