Studer Innotec HPC 2800-12, HPC 4400-24, HPC 6000-48, HPC 8000-48 Programming, Standard setting

Page 21

STUDER INNOTEC

HP-COMPACT

actual temperatures, a temperature sensor can be connected to the HP-COMPACT. The compensation through the sensor is –3mV/°C/Cell.

Order Number: CT-35

Dimensions: H x B x T / 58 x 51.5 x 22mm

4.11 Remote control for „Power Sharing“ RPS-01

If the Remote control RPS-01 is installed, the Trimmer

(26)“INPUT LIMIT“ has to be set on the value max.. The HP-COMPACT takes into account the lowest values set on the inverter and on the Remote control.

The current available at the HP-COMPACT input will be determined by the power of the connected source (generator, grid etc...). The potentiometer on the RPS-

01 must be adjusted lower or equal to max. value of the power source.

For instance if the source is a generator of 2000 Watt, the potentiometer has to be set at max. 8A. This value is obtained in dividing 2000 Watt by 230V. If the HP- COMPACT is connected to a power source which is protected by a 6A circuit breaker, the potentiometer must be set at a max. value of 6A.

Caution: the HP-COMPACT will not limit if an appliance draws more current than available from the source ! This means that the connected generator will be over-loaded or that the circuit-breaker before the HP-COMPACT will break.

5 Programming

The HP-COMPACT (except for 60Hz versions) is equipped with a Flash processor fitted out with EEPROM Memory, which means that even when it is disconnected from the battery, the parameters that were programmed for the application remain after a new connection to the battery.

It is possible to reinitialize (RESET) the HP-COMPACT by pressing simultaneously on the three push buttons 19/20/21 during at least 2 seconds. A beep will confirm the RESET. The inverter switches off after this operation. It can be turned on again after the beep. The programmed parameters will remain.

5.1Standard setting

The HP-COMPACT is delivered with the following default settings:

Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13

Battery voltage :

Low voltage

11.6V / 23.2V / 46.4V

 

Float Charge

13.5V / 27.0V / 54.0V

 

End of Charge Voltage

14.4V / 28.8V / 57.6V

 

Equalization

15.6V / 31.2V / 62.4V

Absorption Time :

 

2 Hours

Equalizing Time :

 

20 Minutes

HP-COMPACT V5.4

23/80

Image 21
Contents HP-COMPACT HPC Sine wave Inverter, Battery charger, TransfersystemHP-COMPACT Warranty Disclaimer Quality and WarrantyGeneral Information Operating instructionsLiability Disclaimer Special precautionsIntroduction Principle schematicDescription of the main functions Battery connecting Installation place Mounting and installingFixing ConnectionsCabling Pre-installation settingsConnection to battery 3.6.1.1 On the appliance side Connection to Temperature Sensor Temp Connection to Remote controlConnection to the 230Vac-consumer appliances AC Output Connection to the 230Vac Input AC InputDisplay and control parameters ControlLED Light Emitting Diodes LEDTurning Knobs Push buttonsInverter Charge detection system „StandbyOverheating Over Temp Battery ConditionDefault values for battery voltage thresholds Battery chargerCycle of charge Equalization chargingInput current repartition Power sharing Set the Input LimitCharging current Transfer system Delayed mode of the Transfer System Fast UPS- Mode for the Transfer SwitchMultifunctional Contact Set the transfer voltage thresholdHP-COMPACT Remote Control RCC-01Remote control for „Power Sharing RPS-01 Standard settingProgramming Reset value default settings Battery voltages and absorption timeSet the voltage and timing threshold Table of voltage and timing threshold Auxiliary contactPrinciple Programming of the Auxiliary ContactManual operating of Auxiliary Contact Power cut of the second priority loadsDiagram of the different modes Installation MaintenanceDisabling some of the HP-COMPACT functions Declaration of CE ComplianceTechnical Data