Hitachi SJ2002 manual Basic Error Codes

Page 15

Error Codes

The SJ2002 series inverters will trip on over-current, over-voltage, and under-voltage to protect the inverter. The motor output turns OFF, allow- ing the motor to free-run to a stop. Press the Stop/Reset key to reset the inverter and clear the error.

Basic Error Codes

Error

Name

Probable Cause(s)

Code

 

 

 

 

 

 

 

 

E01

Over current event while at

• Inverter output was short-circuited

constant speed

• Motor shaft is locked

 

 

 

• Load is too heavy

E02

Over current event during

• A dual-voltage motor is wired

deceleration

incorrectly

 

 

Note: The SJ2002 will over current trip at

E03

Over current event during

nominally 200% of rated current

 

acceleration

 

E04

Over current event for other

• DC braking power(A054) set too high

 

conditions

• Current transformer / noise error

E05

Overload protection

• Motor overload is detected by the

 

 

electronic thermal function

E06

Braking resistor overload

• Regenerative braking resistor exceeds

 

 

the usage time or usage ratio

E07

Over voltage protection

• DC bus voltage exceeds a threshold,

 

 

due to regenerative energy from motor

E08

EEPROM error

Built-in EEPROM memory experi-

 

 

enced noise, high temperature, etc.

E09

Under-voltage error

• DC bus voltage decreased enough to

 

 

cause a control circuit fault

E11

CPU error

Built-in CPU had internal error

 

 

E22

 

 

 

 

 

E12

External trip

• [EXT] input signal detected

 

 

 

 

 

E13

USP (Unattended Start

• When (USP) was enabled, an error

Protection)

occurred when power was applied while

 

 

 

a Run signal was present

 

 

 

E14

Ground fault

• A ground fault was detected between

 

the inverter output and the motor. This

 

 

 

 

feature protects the inverter, and does not

 

 

protect humans.

 

 

 

E15

Input over-voltage

• Input voltage was higher than specified

 

value, after 60 sec. in Stop Mode

 

 

 

 

 

E21

Inverter thermal trip

• Inverter internal temperature is above

 

the threshold

 

 

 

 

 

13

Image 15
Contents SJ2002 Series Inverter Quick Reference Guide Page UL Cautions, Warnings, and Instructions Wiring Warnings for Electrical Practices and Wire SizesAWG Terminal Tightening Torque and Wire SizeFuse and Circuit Breaker Sizes Wire ConnectorsMotor Overload Protection HFU2 Power Circuit TerminalsDescription Ratings and Notes Control Circuit TerminalsAL2 SJ200 Basic Wiring DiagramHitachi Inverter Keypad OperationPage Keypad Navigation Map Program ModeStep Description Via Keypad Via Logic Terminals Powerup TestBasic Error Codes Error CodesE60 Error Trip ConditionsRestoring Factory Default Settings Group Monitoring Functions Parameter TablesTrip History and Inverter Status Monitor ModeGroup Standard Functions Group Main Profile ParametersFunc Default Set Name / Description Value Code Gain setting AVR voltage select Group Fine-tuning Functions Overload restriction operation mode Group Intelligent Terminal Functions C052 PID FBV function high limit C082 OI input span calibration Group Expansion Card Functions Group Motor Constants FunctionsIntelligent Input Terminal Listing Symbol Code Input Terminal NameIntelligent Output Terminal Listing Analog Input ConfigurationOption Function Name Description Corresponding Code Analog Output Function Listing