400V Models
Motor output  | Inverter Model  | Ampere Rating for  | |
  | 
  | ||
kW  | HP  | 
  | Fuse or Breaker | 
  | 
  | ||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
0.4  | 1/2  | 3  | |
  | 
  | 
  | 
  | 
0.75  | 1  | 6  | |
  | 
  | 
  | 
  | 
1.5  | 2  | 10  | |
  | 
  | 
  | 
  | 
2.2  | 3  | 10  | |
  | 
  | 
  | 
  | 
3.0  | 4  | 15  | |
  | 
  | 
  | 
  | 
4.0  | 5  | 15  | |
  | 
  | 
  | 
  | 
5.5  | 7 1/2  | 20  | |
  | 
  | 
  | 
  | 
7.5  | 10  | 25  | |
  | 
  | 
  | 
  | 
Motor Overload Protection
Hitachi SJ2002 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters:
•B012 “electronic overload protection”
•B212 “electronic overload protection, 2nd motor”
Set the rated current [Amperes] of the motor(s) with the above parame- ters. The setting range is 0.2 * rated current to 1.2 * rated current.
Warning: When two or more motors are connected to the inverter, they cannot be protected by the electronic overload pro- tection. Install an external thermal relay on each motor.