Hitachi SJ2002 manual Overload restriction operation mode

Page 25

Func.

 

 

 

Default

Set

 

Name / Description

Value

Code

 

Value

 

 

 

–FE(F)/–FU

 

 

 

 

 

 

 

 

B021/

Overload restriction operation mode

01

 

B221

• 00 Disabled

 

 

 

 

• 01 Enabled for accel and constant speed

 

 

 

• 02 Enabled for constant speed only

 

 

 

 

 

 

B022/

Overload restriction setting

Rated

 

B222

 

 

 

current x 1.5

 

 

 

 

 

B023/

Deceleration rate at overload restriction

1.0 / 30.0

 

B223

 

 

 

 

 

 

 

 

 

B031

Software lock mode selection

01

 

 

• 00 Low-level access, [SFT] blocks edits

 

 

 

• 01 Low-level access, [SFT] blocks edits

 

 

 

(except F001 and Multi-speed parameters)

 

 

 

• 02 No access to edits

 

 

 

• 03 No access to edits except F001 and Multi-

 

 

 

speed parameters

 

 

 

 

• 03 High-level access, including B031

 

 

 

 

 

 

B080

[AM] analog signal gain

100.

 

 

 

 

 

B082

Start frequency adjustment

0.5

 

 

 

 

 

B083

Carrier frequency setting

5.0

 

 

 

 

 

B084

Initialization mode (parameters or trip history)

00

 

 

00 Trip history clear

 

 

 

01 Parameter initialization

 

 

 

• 02 Trip history clear and parameter

 

 

 

 

initialization

 

 

 

 

 

 

 

B085

Country code for initialization

01 / 02

 

 

• 00 Japan version

• 01 Europe version

 

 

 

• 02 USA version

 

 

 

 

 

 

 

B086

Frequency scaling conversion factor

1.0

 

 

 

 

 

 

B087

STOP key enable

 

00

 

 

• 00 Enable

• 01 Disable

 

 

 

 

 

 

B088

Restart mode after FRS

00

 

 

• 00 Restart from 0Hz

 

 

 

• 01 Restart from frequency detected from

 

 

 

actual speed of motor

 

 

 

 

 

 

 

B090

Dynamic braking usage ratio

0.0

 

 

 

 

 

 

B091

Stop mode selection

 

00

 

 

• 00 DEC (decelerate and stop)

 

 

 

• 01 FRS (free-run to stop)

 

 

 

 

 

 

 

B092

Cooling fan control

 

00

 

 

• 00 Fan always ON

 

 

 

 

• 01 Fan ON during Run, OFF during Stop

 

 

 

• 02 Fan is temperature-controlled

 

 

 

 

 

 

 

 

23

Image 25
Contents SJ2002 Series Inverter Quick Reference Guide Page UL Cautions, Warnings, and Instructions Wiring Warnings for Electrical Practices and Wire SizesAWG Terminal Tightening Torque and Wire SizeFuse and Circuit Breaker Sizes Wire ConnectorsMotor Overload Protection HFU2 Power Circuit TerminalsDescription Ratings and Notes Control Circuit TerminalsAL2 SJ200 Basic Wiring DiagramHitachi Inverter Keypad OperationPage Keypad Navigation Map Program ModeStep Description Via Keypad Via Logic Terminals Powerup TestBasic Error Codes Error CodesE60 Error Trip ConditionsRestoring Factory Default Settings Group Monitoring Functions Parameter TablesTrip History and Inverter Status Monitor ModeGroup Standard Functions Group Main Profile ParametersFunc Default Set Name / Description Value Code Gain setting AVR voltage select Group Fine-tuning Functions Overload restriction operation mode Group Intelligent Terminal Functions C052 PID FBV function high limit C082 OI input span calibration Group Expansion Card Functions Group Motor Constants FunctionsIntelligent Input Terminal Listing Symbol Code Input Terminal NameIntelligent Output Terminal Listing Analog Input ConfigurationOption Function Name Description Corresponding Code Analog Output Function Listing