Outback Power Systems FX2348ET, VFX3024E, VFX3048E, VFX2612E, FX2024ET, FX2012ET Down INC, DEC Port

Page 52

MATE SCREENS

AUXILIARY MENU (CONTINUED)

This page contains to settings for the various functions that can be chosen in the AUX OUTPUT FUNCTION screen described on the previous page. There are voltage and time period settings for ‘GenAlert’, ‘LoadShed’, ‘VentFan’, and ‘Diversion’.

The following displays allow the adjustment of the particular AUX OUTPUT FUNCTION that was selected on the previous screen in the AUX menu section.

ADV/FX/AUX-------

P00

genalert

11.0 vdc

on setpoint

 

 

DOWN

INC

DEC

PORT

 

 

 

 

 

 

 

 

 

 

ADV/FX/AUX-------

P00

genalert

 

4 min

on delay

 

 

DOWN

INC

DEC

PORT

 

 

 

 

 

 

 

 

 

 

ADV/FX/AUX-------

P00

genalert

14.0 vdc

off setpoint

 

DOWN

INC

DEC

PORT

 

 

 

 

 

 

 

 

 

 

ADV/FX/AUX-------

P00

genalert

 

9 min

off delay

 

 

DOWN

INC

DEC

PORT

ADV/FX/AUX-------P00

loadshed

11.0 vdc

off setpoint

DOWN INC

DEC PORT

ADV/FX/AUX-------P00

ventfan

13.0 vdc

on setpoint

 

DOWN INC

DEC PORT

ADV/FX/AUX-------P00

ventfan off

5 min

period

 

DOWN INC DEC

PORT

ADV/FX/AUX-------P00

diversion

14.6

vdc

on setpoint

 

 

DOWN

INC

DEC

PORT

 

 

 

 

 

 

 

 

 

 

ADV/FX/AUX-------

P00

diversion

30

sec

off delay

 

 

DOWN

INC

DEC

PORT

ADV/FX/AUX----------

aux output

setup completed

TOP ADV MAIN

The GENALERT ON SET POINT is the battery voltage at which the AUX output is energized when the AUX OUTPUT FUNCTION has been set to GENALERT. This setting has a range between 10.0 vdc and 14.0 vdc in 0.1 vdc increments.

The GENALERT ON DELAY is the amount of time that the battery voltage must remain below the GENALERT ON SETPOINT voltage for the AUX output to become energized. This setting is provided to allow for short periods of heavy load usage. This setting has a range between 0 minutes and 240 minutes in 1 minute increments.

The GENALERT OFF SETPOINT is the battery voltage at which the AUX output is de-energized when the AUX OUTPUT FUNCTION has been set to GENALERT. This setting has a range between 12.0 vdc and 18.0 vdc in 0.1 vdc increments.

The GENALERT OFF DELAY set point is the amount of time that the battery voltage must remain above the GENALERT OFF SETPOINT voltage set point for the AUX output to become de- energized. This setting is provided to allow the battery charger to more fully recharge the battery once it has been started. This setting has a range between 0 minutes and 240 minutes in 1 minute increments.

The LOADSHED OFF SETPOINT is the battery voltage at which the AUX output is energized to reduce the load on the inverter and battery system. Once the battery voltage has dropped below this setting for 3 seconds the AUX output will have 12 vdc available to power a DC coil relay to disconnect an AC load. Once the LOADSHED function has been triggered it will remain on for a minimum of 3 minutes. This setting has a range between 10.0 vdc and 14.0 vdc in 0.1 vdc increments.

The VENTFAN ON SETPOINT is the battery voltage at which the AUX output is energized when the AUX OUTPUT FUNCTION has been set to VENTFAN. The AUX output can be used to keep hydrogen from accumulating by exchanging the air in the battery enclosure. This setting has a range between 10.0 vdc and 16.0 vdc in 0.1 vdc increments.

The VENTFAN OFF PERIOD set point can be used to allow for intermittent operation of the battery enclosure ventilation system. Setting the time period to 5 minutes will operate the fan at a 50% duty cycle as the “on” time period is fixed at 5 minutes. Setting the VENTFAN OFF PERIOD to zero will keep the fan on continuously when the battery voltage exceeds the VENTFAN ON voltage set point. This setting has a range between 0 minutes and 30 minutes in 1 minute increments.

The DIVERSION ON SETPOINT enables the AUX output to function as a diversion controller. This can be used to send excess power from a renewable energy source to a load. This can allow control of sources such as wind turbines or hydro-generators. Two types of DIVERT are selectable

DIVERTDC and DIVERTAC. The only difference is that the AC diversion setting will quickly turn off the AUX output if the FX is overloaded. This setting has a range between 12.0 vdc and 16.0 vdc in 0.1 vdc increments.

The DIVERSION OFF DELAY is the amount of time that the AUX output will continue to be energized after the battery voltage falls below the DIVERSION ON SETPOINT voltage. In cases where the battery voltage is hovering around the DIVERSION ON SETPOINT voltage, the AUX output won’t flicker. This setting has a range between 0 seconds and 240 seconds in 1 second increments.

Selecting TOP returns the user to the top of the ADV/FX/AUX menu section. Selecting ADV returns you to the advanced screen to allow selection of another product connected to the MATE. Selecting MAIN returns the display to the MAIN screen.

Installation & Programming Manual

FX & VFX “E” Series Inverter/Charger System

Copyright 2003  OutBack Power Systems, Inc.

 

900-0027-2

19009 62nd Ave NE, Arlington WA 98223 USA

Page 52

Rev 7.1

06/08/06

Tel 360 435 6030 Fax 360 435 6019

Image 52
Contents Installation and Programming Manual Export FX and VFX Inverter/Charger900-0027-2 Table of Contents Stacking Instructions Wire Sizes Warranty RegistrationMate Screens EU Declaration of Conformity Declaration of ConformityInstallation Guidelines Important Safety InstructionsPersonal Precautions While Working with Batteries General PrecautionsAdditional Notices Ratings Maximum Continuous Output Power AC Input Frequency RangeMaximum AC Output Current Maximum Overcurrent Protection AmpacityMounting ACA DCC DCAPsac Psdc PS2AC PS2DC Complete Outback Integrated SystemsAC Wiring Connections Indicators / Control Wiring Battery Temp Remote Temperature Sensor RTSInverter ON/OFF Auxiliary Output AUX + / AUXBattery FX Cabling DC Battery TerminalsBattery Terminal Covers Equipment Ground TerminalsFX Accessories FXA Accessory KITFX-ACA AC Conduit Adapter FX-DCA DC Conduit AdapterHUB Communication Manager Slave MasterTurbo KIT Information FX System Configuration Single FX System Single FX SystemFX System Configuration Paralleled Dual FX System Paralleled Dual FX SystemFX System Configuration Paralleled Quad FX System Paralleled Quad FX SystemPhase FX System FX System Configuration 3 Phase FX SystemSTART-UP & Operation Battery Charging Instructions Battery Charging Set PointsOutBack & 3-phase Stacking Methods Stacking ProcedureStack Phase Stacking InstructionsPower Save Level Master Adjust only Power Save Level Slave Adjust onlyPhase Stacked System 3 FX’S only Stacked System Using OUTBACK’S Parallel StackingSystem Examples Automatic Generator Start Instructions Mate System Controller and Display OutBack Mate System ControllersOutBack Mate SETUP/FX/INPUT---P00 Menu StructureMate Buttons GENTOP Setup Main ‘SOFT’ KeysGEN Down Grid GENInverter Control Inverter ControlOFF Srch on OK AC Input Control Mate Menu MAP Mate Menu MAP SUM Status Setup ADV Summary ScreenMate Screens ExamplesStatus Screens Modes MenuFX MX ModesMeter Menu DownDown UP MeterBattery Menu BattError Menu ErrorWarn WarnDisconnect Menu DisconPG3 Sell MenuSell Setup Screens Search MenuSrch Input SrchINC DEC Port SETUP/FX/INPUT Input MenuSrch Input Main InputPassword Code 1 4 Advanced ScreensPG2 PG4INV Inverter MenuDownmore Charger Menu Down INCGrid Menu PG1Grid GEN PG3 ADV/FX/GRIDPG1 Grid Generator MenuOFF Port Auxiliary Menu ADV INV Chgr PG2PG2 AUX Stack PG4 Down INC PortDEC Port Stacking Menu PG2 AUXStack ADV/FX/STACKSell Calibration Menu END of Advanced Menu SystemCAL Wire Sizes AWGTwo Year Limited Warranty Warranty900-0027-2 Extended Warranty Application Registration