Outback Power Systems VFX3024E, VFX3048E, VFX2612E, FX2024ET, FX2348ET manual Charger Menu, Down INC

Page 48

MATE SCREENS

CHARGER MENU

The CHARGER section allows for adjustment of the battery charger’s operation to match the requirements of the batteries used. OutBack’s default battery charging set points may not be correct for the type of batteries being used. Please contact the battery manufacturer for correct ABSORB, FLOAT and EQUALIZE voltages. See the BATTERY CHARGING INSTRUCTIONS on page 24 for guidelines on how to set some of these values. The FX’s battery charger includes five stages. BULK raises the battery voltage to the ‘Absorb Setpoint’. ABSORB sustains the battery voltage for the ‘Absorb Time Limit’. The charger then goes into SILENT mode (no charging) until the battery voltage drops to the ‘Refloat Setpoint’. Then the FX goes into FLOAT and sustains the ‘Float Setpoint’ voltage for the ‘Float Time Period’. The charger then goes into SILENT mode and repeats the FLOAT cycle when the battery voltage drops to the ‘Refloat Setpoint’. There are additional screens for “Equalize Setpoint’ and ‘Equalize Time Period’. An equalize charge must be manually started. The time limits that it spends in the various stages are adjustable to provide control and maximize the performance of the battery charger and battery system.

ADV-----------------

choose product:

FXMATE

ADV/FX/PAGE1--------

choose category:

ADV INV CHGR PG2

ADV/FX/CHARGER

---P00

charger

4.0 aac

limit

 

 

DOWN INC

DEC

PORT

ADV/FX/CHARGER

---P00

absorb

14.4 vdc

setpoint

 

 

DOWN INC

DEC

PORT

ADV/FX/CHARGER

---P00

absorb

01.0 hrs

time

limit

 

 

DOWN

INC

DEC

PORT

ADV/FX/CHARGER

---P00

float

13.6 vdc

setpoint

 

 

DOWN INC

DEC

PORT

ADV/FX/CHARGER

---P00

float

01.0 hrs

time

period

 

 

DOWN

INC

DEC

PORT

ADV/FX/CHARGER

---P00

refloat

12.5 vdc

setpoint

 

 

DOWN INC

DEC

PORT

ADV/FX/CHARGER

---P00

equalize

14.4 vdc

setpoint

 

 

DOWN INC

DEC

PORT

ADV/FX/CHARGER

---P00

equalize

01.0 hrs

time

period

 

 

DOWN

INC

DEC

PORT

ADV/FX/CHARGER------

charger programming

completed

TOP ADV MAIN

Once the password has been correctly entered, the ADV - CHOOSE PRODUCT is displayed. Selecting <FX> allows adjustment of the FX’s advanced programming.

Selecting <CHGR> allows adjustment of the battery charger set points and operation.

The CHARGER LIMIT is the maximum amount of AC current that will be used by the FX to power the battery charger. In most systems this setting will not need to be changed. This setting has a range as low as 0.0 aac and as high as 6.0 aac to 10.0 aac (depending on the model) in 0.5 aac increments.

The ABSORB SET POINT is the voltage that the batteries will be charged to during the first stage of the charging process. This stage of charging raises the battery voltage higher than the nominal battery voltage and allows the batteries to regain their charge. The ‘Absorb Time Limit’ must be long enough for the batteries to regain 100% of their charge. This setting has a range between 13.0 vdc and 16.0 vdc in 0.1 vdc increments.

The ABSORB TIME LIMIT can be adjusted to provide enough time at the ‘Absorb Setpoint’ to achieve a fully recharged battery. For large batteries a longer time may be required – small batteries may require a lower setting. The FX automatically reduces the ‘Absorb Time Limit’ when the charger is connected to a partially charged battery. This setting has a range between 0 hours and 24 hours in 0.1 hour increments.

The FLOAT SET POINT is the voltage that the batteries will be ‘trickle’ charged to. This charge will finish the charging process by putting the last few percentage points of charge into the batteries. This set point can be adjusted to match the specific requirements of the batteries being charged. This setting has a range between 12.0 vdc and 15.0 vdc in 0.1 vdc increments.

The FLOAT TIME PERIOD can be adjusted to set the amount of time that the battery is held at the ‘Float Setpoint’. For large batteries a longer time may be required – smaller batteries may use a lower setting. Once the battery has been held at the ‘Float Setpoint’ for the ‘Float Time Period’, the battery charger goes silent and provides no charge to the battery. This setting has a range between 0 hours and 24 hours in 0.1 hour increments.

The REFLOAT SET POINT voltage is used to “trigger” the battery charger back into another FLOAT cycle when the battery voltage falls to this set point. This can provide maintenance charging of batteries and is also useful when intermittent DC loads are operated from a battery system and an AC source is available. This setting has a range between 12.0 vdc and 13.0 vdc in 0.1 vdc increments.

The EQUALIZE SET POINT voltage can be set for a high voltage to de-stratify the batteries on occasion. The user can start an equalization charge through the AC IN “hot” key. The batteries must be supervised throughout the equalization process. Consult the battery supplier as to specific instruction on the battery equalizing process. This setting has a range between 14.0 vdc and 17.0 vdc in 0.1 vdc increments.

The EQUALIZE TIME PERIOD can be adjusted to limit the amount of time that the battery is equalized. The timer starts to advance once the battery voltage exceeds the absorb voltage set point. Once the timer reaches the equalize time period, the charger goes into the silent stage of the charging process. This setting has a range between 0 hours and 24 hours in 0.1 hour increments.

Selecting TOP returns the user to the top of the ADV/FX/CHARGER menu section. Selecting ADV returns you to the advanced screen to allow selection of another product connected to the MATE. Selecting MAIN returns the display to the MAIN screen.

Installation & Programming Manual

FX & VFX “E” Series Inverter/Charger System

Copyright 2003  OutBack Power Systems, Inc.

 

900-0027-2

19009 62nd Ave NE, Arlington WA 98223 USA

Page 48

Rev 7.1

06/08/06

Tel 360 435 6030 Fax 360 435 6019

Image 48
Contents Installation and Programming Manual Export FX and VFX Inverter/Charger900-0027-2 Table of Contents Wire Sizes Warranty Registration Stacking InstructionsMate Screens EU Declaration of Conformity Declaration of ConformityInstallation Guidelines Important Safety InstructionsGeneral Precautions Personal Precautions While Working with BatteriesAdditional Notices Ratings Maximum Continuous Output Power AC Input Frequency RangeMaximum AC Output Current Maximum Overcurrent Protection AmpacityMounting ACA DCC DCAPsac Psdc PS2AC PS2DC Complete Outback Integrated SystemsAC Wiring Connections Indicators / Control Wiring Battery Temp Remote Temperature Sensor RTSInverter ON/OFF Auxiliary Output AUX + / AUXBattery FX Cabling DC Battery TerminalsBattery Terminal Covers Equipment Ground TerminalsFX Accessories FXA Accessory KITFX-ACA AC Conduit Adapter FX-DCA DC Conduit AdapterHUB Communication Manager Slave MasterTurbo KIT Information FX System Configuration Single FX System Single FX SystemFX System Configuration Paralleled Dual FX System Paralleled Dual FX SystemFX System Configuration Paralleled Quad FX System Paralleled Quad FX SystemPhase FX System FX System Configuration 3 Phase FX SystemSTART-UP & Operation Battery Charging Instructions Battery Charging Set PointsOutBack & 3-phase Stacking Methods Stacking ProcedureStack Phase Stacking InstructionsPower Save Level Master Adjust only Power Save Level Slave Adjust onlyStacked System Using OUTBACK’S Parallel Stacking Phase Stacked System 3 FX’S onlySystem Examples Automatic Generator Start Instructions Mate System Controller and Display OutBack Mate System ControllersOutBack Mate SETUP/FX/INPUT---P00 Menu StructureMate Buttons GENTOP Setup Main ‘SOFT’ KeysGEN Down Grid GENInverter Control Inverter ControlOFF Srch on OK AC Input Control Mate Menu MAP Mate Menu MAP SUM Status Setup ADV Summary ScreenMate Screens ExamplesStatus Screens Modes MenuFX MX ModesMeter Menu DownDown UP MeterBattery Menu BattError Menu ErrorWarn WarnDisconnect Menu DisconSell Menu PG3Sell Setup Screens Search MenuSrch Input SrchINC DEC Port SETUP/FX/INPUT Input MenuSrch Input Main InputPassword Code 1 4 Advanced ScreensPG2 PG4Inverter Menu INVDownmore Charger Menu Down INCGrid Menu PG1Grid GEN PG3 ADV/FX/GRIDGenerator Menu PG1 GridOFF Port Auxiliary Menu ADV INV Chgr PG2PG2 AUX Stack PG4 Down INC PortDEC Port Stacking Menu PG2 AUXStack ADV/FX/STACKSell END of Advanced Menu System Calibration MenuCAL Wire Sizes AWGTwo Year Limited Warranty Warranty900-0027-2 Extended Warranty Application Registration